4.2 Wiring
4.2.1 Wire Routing
All wiring must be installed in accordance with NFPA70 [NEC760], NFPA72, and all
local code requirements.
Power Limited wiring requires that power limited and non-power limited wiring
remain physically separated. Any power limited circuit entering the enclosure must
remain at least one quarter inch (
¼
”) away from any non-power limited circuit
wiring. Any power limited circuit wiring must enter and exit the enclosure through
different knockouts than non-power limited circuit wiring.
Wiring within the enclosure should be routed around the perimeter of the cabinet.
It should not be routed across the circuit boards. See the enclosure’s
documentation for complete wire routing instructions.
4.2.2 ABC Connector
See section 3.3
4.2.3 Output Wiring
Locate the output wiring terminal blocks (TB1 and TB2) and remove the terminal
block from the header. Connect the wiring for the equipment to be powered to
the terminal block. The PC board is labeled with the output numbers and polarity
(See also section 3.2). Replace the terminal block on the header.
NOTE: Wire size for these terminals must be 22-14 AWG.
4.3 Labeling
If the PD8(F) was purchased separately from the power supply unit, the supplied
label must be applied to the inside cover of the power supply’s enclosure. The label
shall not cover any ventilation holes or other labeling on the enclosure.