![Alarm SAF BN10-000-UL Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/alarm-saf/bn10-000-ul/bn10-000-ul_operating-and-installation-instruction-manual_2888746019.webp)
Beacon Power Supply Installation Instructions
2.8.2012
52-296 Rev B05
Page 18 of 27
AlarmSaf
65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com
5.2 Jumper Settings (continued)
5.2.3 JP3 (D/E)
This jumper enables or disables FAI input filtering. FAI input filtering is used if the FAI input is
connected to a coded source (i.e. pulsing input).
5.2.4 J5 (VAC SELECT)
This jumper selects the AC input voltage to be used to power the BNx000. The power supply is
factory set for 120 VAC input (J5 in the
UP position). Move the jumper to the DOWN position
or remove it to operate the power supply with 240 VAC input.
CAUTION: J5 MUST be set properly before powering the unit or damage to the
system will occur.
5.3 Visual Indicators
The BNx000 contains seven visual status indicators:
LED
Description
Color
Conditions
AC PWR (D20)
AC Power
Green
Lights when AC Power Present
ACF (D50)
AC Fault
Yellow Lights on low / missing AC Power
SYS TBL (D33)
System Trouble
Yellow Lights when a system trouble present
REV BAT (D27)
Reverse Battery
Yellow Lights when battery connection reversed
DC1 (D13)
DC1 Available
Green
Lights when DC1 output is available
DC2 / DC3 (D24)
DC2 & DC3 Available
Green
Lights when DC2 & DC3 output is available
FAI (D4)
FAI Active
Red
Lights when a valid FAI input signal is received
5.3.1 AC PWR (D20)
For safety reasons, this LED lights any time there is AC voltage present at the AC input,
regardless of the AC fault status, battery state of charge, or power supply condition.
CAUTION: Always check for AC presence with a volt meter before servicing
5.3.2 ACF (D50)
This LED lights when AC power is low or missing. It does not necessarily indicate that the
power supply is not operating. See the chart in Section 5.3.