Beacon Power Management System Installation Manual

This Installation manual is made up of the following separate Installation Instructions for the Power Supply
and Power Distribution Module.

52-296 - Installation Instructions for Beacon Power Supply - 

pp. 2-28

52-325 - Installation Instructions for Beacon Power Supply - Addendum A - 

p. 29

52-326 - Installation Instructions for PD Module - 

p. 30-43

Model Numbers: 

Order Numbers:

BN4-000-PD8F-UL

10003

BN4-000-PD8-UL

10002

BN4-002-PD8F-UL

10006

BN4-002-PD8-UL

10005

BN6-000-PD8F-UL

10015

BN6-000-PD8-UL

10014

BN6-002-PD8F-UL

10018

BN6-002-PD8-UL

10017

BN10-002-PD8F-UL

10053

BN10-002-PD8-UL

10054

BN10-003-PD8F-UL

10056

BN10-003-PD8-UL

10055

*May also be used for any Beacon Power Management System that
includes any combination of the following boards:

Model Numbers: 

Order Numbers:

PD8F-UL

10042

PD8-UL

10041

BN4-000-UL

10001 

BN6-000-UL

10013

BN8-000-UL

10025

BN10-000-UL

10034

BN4-004-PD8F-UL

10062

BN10-004-PD8F-UL

10079

BN8-002-PD8-UL

10060

BN64-004-PD32-UL

10074

BN1010-004-PD16-UL

10059

BN1010-004-PD16F-UL

10083

BN1010-003-PD16-UL

10090

Содержание BN10-000-UL

Страница 1: ...odule p 30 43 Model Numbers Order Numbers BN4 000 PD8F UL 10003 BN4 000 PD8 UL 10002 BN4 002 PD8F UL 10006 BN4 002 PD8 UL 10005 BN6 000 PD8F UL 10015 BN6 000 PD8 UL 10014 BN6 002 PD8F UL 10018 BN6 002...

Страница 2: ...Installation Instructions 2 8 2012 52 296 Rev B05 Page 1 of 27 AlarmSaf 65A Industrial Way Wilmington MA 01887 978 658 6717 www alarmsaf com Beacon Power Supply Operating and Installation Instruction...

Страница 3: ...k Installation and service should be made by qualified service personnel and should conform to all local codes III WARNING Read the instruction manual to avoid personal injury or property damage IV NO...

Страница 4: ...onnector Illustration 8 3 3 AC Input Connection 9 10 3 4 Accessory Board Connectors ABC 10 3 5 ABC Buss Voltage Selection 10 11 3 6 Output Terminals 11 3 7 FAI Input Terminals 12 3 8 Fault Reporting T...

Страница 5: ...12V devices such as mag locks Expandable with accessory boards via the ABC connector All units can charge up to 38AH of battery while supplying full rated load Full fault detection including battery p...

Страница 6: ...cessory Board Installation Manual 52 352 MB8 F Accessory Board Installation Manual 52 254 APD8 F Accessory Board Installation Manual 52 326 PD8 F Accessory Board Installation Manual 52 350 SPS4 Access...

Страница 7: ...t Power BN4000 125W maximum BN6000 190W maximum BN8000 250W maximum BN10000 330W maximum Output 12 or 24VDC nominal at BN4000 4A 24V out or 8A 12V out 110W BN6000 6A 24V out or 12A 12V out 165W BN8000...

Страница 8: ...output current of supply See Section 3 1 for ratings Output deactivates upon FAI Activation DC2 DC2 Common Output TB2 DC3 and BAT Outputs DC3 DC3 Positive Output Full output current of supply See Sec...

Страница 9: ...r Supply Installation Instructions 2 8 2012 52 296 Rev B05 Page 8 of 27 AlarmSaf 65A Industrial Way Wilmington MA 01887 978 658 6717 www alarmsaf com 3 2 1 BNx000 Terminal and Connector Illustration F...

Страница 10: ...3 1 Configuring VAC Input All BNx000 power supplies are factory set for 120 VAC input 102 138VAC at 50 or 60Hz To verify 120 VAC input setting Locate the VAC SELECT jumper J5 Verify that J5 is in the...

Страница 11: ...of available accessory modules For more detailed information on the ABC expansion port see Appendix B About the Accessory Board Connector 3 4 2 ABC Cable Types Order Model Description Used With Notes...

Страница 12: ...onnecting a Beacon Accessory Module B2 UP Removes voltage from the Accessory Board Connector P2 Because older BNx000 boards PCB 38 118 REV A02 or earlier do not have a Buss Select Fuse always check th...

Страница 13: ...inals on the BNx000 FAI input Terminal Description Use V Auxiliary Voltage Output An internal voltage source for use with dry contacts or open collectors L Positive FAI Activation Terminals These term...

Страница 14: ...5 AC FLT Normally Closed NC 6 AC FLT Common COM JP1 K3 NC NC COM COM NO NO SYS FLT AC FLT SYS TBL BPD D Figure 3 8 1 Fault Condition SYS FLT Relay Output AC FLT Relay Output Normal Condition No Fault...

Страница 15: ...em for the mounting surface CAUTION Remove all power from the system before installation Cabinet Mounting 1 Mark and pre drill two holes for the top keyhole mounting screws 2 Install two fasteners in...

Страница 16: ...not be routed across the circuit boards 4 2 2 AC Input Connection should be made via wire nut AC mains wiring should be no smaller than 14 AWG See Section 3 3 for details 4 2 3 ABC Connector See secti...

Страница 17: ...d is labeled with the connections and polarity See also section 3 2 Replace the terminal block on the header 4 2 7 Fault Relay Wiring Locate the Fault Relay Output terminal block TB4 and remove the te...

Страница 18: ...8000 10000 Figure 5 1 1 5 2 Jumper Settings For proper operation the jumpers on the BNx000 should be set appropriately All jumpers should be verified or set before powering the unit Jumper Descriptio...

Страница 19: ...n visual status indicators LED Description Color Conditions AC PWR D20 AC Power Green Lights when AC Power Present ACF D50 AC Fault Yellow Lights on low missing AC Power SYS TBL D33 System Trouble Yel...

Страница 20: ...g battery If Battery Presence is enabled 5 3 4 REV BAT D27 This LED lights when a battery set is connected to the BNx000 in a reverse polarity This LED will be accompanied by the SYS TBL LED and a blo...

Страница 21: ...per connection of the ABC cable s Bad Incorrect or Missing Battery Set Verify that a good battery set of the proper voltage is connected to the BNx000 Internal problem with BNx000 Contact AlarmSaf The...

Страница 22: ...ominal or 195 5 264 5 240VAC Nominal 50 60Hz 6 1 2 Input Power Model dependent See Sec 3 1 6 1 3 Output Voltage 12 or 24VDC Nominal 6 1 4 Output Current Model dependent See Sec 3 1 6 2 Temperature Spe...

Страница 23: ...urce a Normally closed b Normally open 2 Power from external voltage source a Switched positive b Switched negative 3 Open collector connection a Internal voltage source b External voltage 4 Direct to...

Страница 24: ...R OPEN COLLECTOR JP3 TB3 E D FAI BAT REV L L V V FAI INPUT V L L V EXTERNALPOWER EXTERNALPOWER OPEN COLLECTOR Internal source External source NAC connection JP3 TB3 E D FAI BAT REV L L V V FAI INPUT V...

Страница 25: ...us Products can be daisy chained together maintaining voltage fault FAI and DC common continuity throughout the chain NOTE There are 6 pin and 8 pin versions of the ABC The 6 pin version carries ONLY...

Страница 26: ...connected to each voltage buss before powering the system Fault Status Buss The fault status buss carries the DC Fault status between accessory boards and power supplies Any product with fault detect...

Страница 27: ...ctivation of any FAI input source will only activate accessory boards or power supplies up to the split Products after the split require their own FAI input source Note Not all accessory boards have F...

Страница 28: ...arm Interface Input present on some AlarmSaf products allowing control of output s in the system Typically used for dropping power to mag locks on egress doors during a fire alarm condition but can al...

Страница 29: ...SDH 7D Siemens 17 31 24 Door Holder SDH 6D Siemens 17 31 24 Door Holder SDH 5D Siemens 17 31 24 Door Holder SDH 4D Siemens 17 31 24 Door Holder SDH 3D Siemens 17 31 24 Door Holder SDH 2D Siemens 20 29...

Страница 30: ...REPLACE FUSES ONLY WITH AlarmSaf c 2005 OUT1 OUT2 OUT3 OUT4 OUT1 OUT2 OUT3 OUT4 OUT5 OUT5 OUT6 OUT6 OUT7 OUT7 OUT8 OUT8 DC PD8 PD8F UTILISER UN FUSIBLE DE RECHANGE DE MEME FLT FAI B1 B1 B2 B2 RET Mod...

Страница 31: ...s 8 4 Installation 9 4 1 Mounting 9 4 2 Wiring 10 5 Operating the PD8 F 11 5 1 Jumper Configuration 11 5 2 Visual Indicators 12 5 3 Troubleshooting 12 6 Specifications 13 6 1 Electrical Specifications...

Страница 32: ...utput voltage able to be selected as a group from one of two voltage busses y Available with Class 2 Power Limited outputs PD8 or Fused non power limited outputs PD8F y Each output is capable of suppl...

Страница 33: ...arm Units and Systems UL 2044 Commercal Closed Circuit Television Equipment Canadian Standards ULC S527 Standard for Control Units for Fire Alarm Systems ULC S318 Standard for Power Supplies for Burgl...

Страница 34: ...d by base power supply selected Outputs Two Inputs 0 to 24VDC Nominal 14 Amps maximum per input Inputs Product Use When installed in accordance with all standards listed in Section 2 of this document...

Страница 35: ...Output 4 Out4 Output 3 Out3 1 6A PD8 or 3A PD8F maximum Voltage determined by base supplies and jumper selection Output 3 Out3 Output 2 Out2 1 6A PD8 or 3A PD8F maximum Voltage determined by base sup...

Страница 36: ...e other ABC connector 3 3 4 Cable Types ABC 06 18 inches Red A099071 6 8 ABC 05 8 inches Red A099070 6 8 ABC 04 18 inches Brown A099069 8 8 ABC 03 8 inches Brown A099068 8 8 ABC 02 18 inches White A09...

Страница 37: ...ther an ATM 3 fuse PD8F or a 1 6A PTC PD8 If an output PTC is tripped remove the output load for 30 seconds Caution Observe the polarity of the PD8 F output terminals with respect to the load or damag...

Страница 38: ...unt the PD8 F to the standoffs using the screws removed in step 1 4 Connect ABC cable s appropriately See section 3 3 4 1 2 Mounting In a Metal Enclosure 1 Install four 6 32 x 3 4 Female Female nylon...

Страница 39: ...ntation for complete wire routing instructions 4 2 2 ABC Connector See section 3 3 4 2 3 Output Wiring Locate the output wiring terminal blocks TB1 and TB2 and remove the terminal block from the heade...

Страница 40: ...JP1 Factory Default Settings Description Jumper 5 1 1 The Voltage Buss Selection jumper JP1 is used to select which of the two voltage busses on the ABC connector s are to be used to supply the outpu...

Страница 41: ...cted LED not lit Check power supply Power supply outputting incorrect voltage Verify proper jumper setting Incorrect voltage buss selected Incorrect voltage on output Check output wiring and remove lo...

Страница 42: ...t including hardware or cables 6 3 2 Size 4 85 L x 2 10 W x 1 00 H Note Width includes terminal block overhang of 0 2 6 3 3 CAD Drawing JP1 P1 P2 F8 F7 F6 F5 F4 F3 F2 F1 3A 32V D1 R1 D2 TB1 TB2 B2 B1...

Страница 43: ...12 or 24VDC into eight individually protected outputs for use in powering locks doorstrikes or auxiliary equipment such as REX PIRs keypads egress timers or readers The diagram illustrates a common e...

Отзывы: