KEY ACT 

(KEY ACTIVE OUTPUT)

THIS IS AN NPN TRANSISTOR OPEN COLLECTOR OUTPUT THAT SWITCHES TO

GROUND, (-) FOR 10 SECONDS WITH EACH KEY PRESS.  THIS CAN BE USED TO 

TURN ON A  BUZZER, TURN ON LEDS OR OPERATE A  LOW CURRENT RELAY. 

THE RATING OF THIS OUTPUT IS LIMITED TO Ic MAX.  100 MA. SINK, Vc MAX. 24VDC. 

 

DU ACT 

(DURESS OUTPUT)

THIS IS AN NPN TRANSISTOR  OPEN COLLECTOR OUTPUT THAT SWITCHES TO      

GROUND, (-)  AFTER THE DURESS CODE HAS BEEN ENTERED.  THIS CAN BE USED

TO TRIGGER AN ALARM ZONE OR TURN ON A  BUZZER.  THE RATING OF THIS

OUTPUT IS LIMITED TO Ic  MAX. 100MA. SINK, Vc  MAX.  24VDC.

 

DOOR SENS

(DOOR POSITION SENSOR INPUT)

A NORMALLY-CLOSED MAGNETIC CONTACT CONNECTED TO THIS TERMINAL AND

GROUND, (-)  WILL  MONITOR THE POSITION OF THE DOOR.  

THIS TERMINAL MUST 

BE CONNECTED TO GROUND, (-) IF NOT USED. 

THE FACTORY INSTALLED JUMPER

MUST BE REMOVED WHEN USING THIS FEATURE  

THE DOOR POSITION SENSOR WILL PROVIDE THE FOLLOWING:

1. 

DOOR AUTO RE-LOCK

THE KEYPAD WILL IMMEDIATELY RE-LOCK AFTER THE DOOR CLOSES AND BEFORE

THE END OF TIME PERIOD THAT HAS BEEN PROGRAMMED FOR OUTPUT 1. 

THIS PREVENTS “TAILGATE” ENTRIES.

2. 

DOOR FORCED OPEN ALARM

THE KEYPAD WILL GENERATE A  DOOR FORCED OPEN ALARM INSTANTLY IF THE 

DOOR IS FORCED OPEN WITHOUT A VALID USER ENTRY CODE OR EGRESS

INPUT.  THE ALARM WILL LAST FOR 60 SECONDS AND CAN BE TURNED OFF WITH

ONE OF THE USER CODES IN GROUP 1 AT ANYTIME.  

3. 

DOOR PROPPED OPEN ALARM

IF THE DOOR IS LEFT OPEN LONGER THAN THE PRE-SET TIME THE KEYPAD WILL

GENERATE A DOOR PROPPED OPEN ALARM UNTIL THE DOOR IS CLOSED.  THE 

DOOR OPEN TIME IS PROGRAMMABLE FROM 1 TO 999 SECONDS.

4. 

INTER-LOCK CONTROL

THE INTER-LOCK CONTROL OUTPUT GOES TO GROUND, (-)  WHEN THE DOOR IS 

OPEN IN ORDER TO DISABLE THE SECOND KEYPAD IN THE INTER-LOCK SYSTEM.

 

O/P 1 INHIB. 

(OUTPUT 1 INHIBIT)

THIS IS A  NORMALLY-OPEN INPUT TERMINAL WHICH IS USED IN A CROSS WIRE

CONNECTION IN AN INTER-LOCK APPLICATION.

 

INT. LOCK 

( INTER-LOCK CONTROL OUTPUT)

THIS IS AN NPN TRANSISTOR OPEN COLLECTOR OUTPUT THAT SWITCHES TO

GROUND, (-)  FOR 5 SECONDS AFTER ENTERING A VALID USER CODE.  USE THIS

OUTPUT TO CONTROL THE SECOND KEYPAD IN A “MANTRAP” APPLICATION.

A “MANTRAP” SYSTEM IS A TWO DOOR SYSTEM THAT ALLOWS ONLY ONE DOOR

TO OPEN AT A TIME.  THIS PREVENTS ACCESS THRU DOOR 2 WHILE DOOR 1 IS  

OPEN.  ACCESS THRU DOOR 2 IS ALLOWED WHEN DOOR 1 IS CLOSED.

 

N.C TAMPER 

THIS CONTACT IS NORMALLY-CLOSED WHILE THE KEYPAD IS SECURE TO THE BACK 

BOX.  WHEN THE KEYPAD IS SEPARATED FROM THE BACK BOX THE CONTACTS

OPEN.  CONNECT THESE NORMALLY-CLOSED CONTACTS TO THE PANIC INPUT

OF AN ALARM PANEL IF REQUIRED.  

DURESS OUTPUT

OUTPUT 2 APPLICATIONS

The Duress Output will switch to ground, (-), when the Duress Code is entered.  This output can be

used to turn on a LED or piezo buzzer.  This output can be connected to a 24 hour zone of an alarm

system.  Only one connection option is recommended.  See page 7 for details.  

SHUNTING OF A N/C

PROTECTIVE ZONE

ARMING AND DISARMING

ALARM PANEL

TO ALARM PANEL

PROTECIVE ZONE

Use the n/o output contact of Output 2 to shunt a N/C protective zone.  Set the Keypad in Latching

Mode.  See page 6 for Keypad programming Latching Mode.

ALARM PANEL

REMOTE

ARM-DISARM

TERMINALS

Use the N/O or N/C output contact of Output 2 to arm or disarm a control panel.  Set the Keypad in

Momentary Mode.  See page 6 for Keypad programming Momentary Mode. 

CURRENT NOT TO

EXCEED 100 MA. 

Содержание KP-400

Страница 1: ...AS DIE CAST METAL KEYS WITH AUDIBLE AND VISUAL KEY PRESS TWO PROGRAMMABLE S P D T RELAY OUTPUTS DOOR PROP OPEN ALARM DOOR FORCED OPEN ALARM BUILT IN TAMPER SWITCH BUILT IN BUZZER REQUEST TO EXIT INPUT...

Страница 2: ...OCKS FOR 30 SECONDS RELAYS CAN BE SET FOR MOMENTARY OR LATCHING MODE ADJUSTABLE RELAY ON TIME FROM 1 TO 999 SECONDS KEYPAD BEEPER CAN BE SILENCED IF REQUIRED KEYPAD CAN BE PROGRAMMED FOR OUTPUT ANNUNC...

Страница 3: ...OLS CORPORATION 19 BRANDYWINE DRIVE P O BOX 280 DEER PARK NY 11729 WWW ALARMCONTROLS COM SELF CONTAINED DIGITAL VANDAL RESISTANT WEATHERPROOF ACCESS CONTROL KEYPAD MODEL KP 400 OPERATING INSTRUCTIONS...

Страница 4: ...S AC DC AUTO VOLTAGE SENSING ACTIVE CURRENT DRAW 100 MA MAX 12 V 120 MA MAX 24 V IDLE CURRENT DRAW 10 MA MAX 12 V 22 MA MAX 24 V OUTPUT 1 CONTACT RATING 5A 28 VDC OUTPUT 2 CONTACT RATING 1A 28 VDC REL...

Страница 5: ...ER CODE MULTIPLE REQUEST TO EXIT STATIONS CAN BE CONNECTED IN PARALLEL TO THESE TERMINALS LED INDICATORS RED ON WHEN OUTPUT 2 IS ACTIVE GREEN ON WHEN OUTPUT 1 IS ACTIVE YELLOW MONITORS POWER DRY CONTA...

Страница 6: ...1 TO 999 SECONDS 4 INTER LOCK CONTROL THE INTER LOCK CONTROL OUTPUT GOES TO GROUND WHEN THE DOOR IS OPEN IN ORDER TO DISABLE THE SECOND KEYPAD IN THE INTER LOCK SYSTEM O P 1 INHIB OUTPUT 1 INHIBIT TH...

Страница 7: ...2 BEEPS SUCCESSFUL CODE ENTRY 5 FLASHES 5 BEEPS FAULTY CODE ENTRY CONTINUOUS FLASHING CONTINUOUS TONE DAP JUMPER NOT REPLACED CONTINUOUS FLASHING NONE 1 FLASH IN 2 SEC INTERVAL NONE 1 LONG BEEP OUTPU...

Страница 8: ...LOWED To activate Keypad Initiation Mode enter then press the key The Yellow Led will flash twice and you will hear two beeps You are now in Keypad Initiation Mode 8 9 0 1 STEP 3 ENTERING THE USER COD...

Страница 9: ...D SILENT MODE To exit the Program Mode press the key The Keypad returns to normal operation The Keypad can be programmed with additional features by using the following op tions You have only 10 secon...

Страница 10: ...need the same number of digits To program the Keypad for Manual Mode press the keys then press the then press the key The Keypad is now in the Manual Mode PAGE 8 PAGE 7 CODE ENTRY MODES AUTO OR MANUA...

Отзывы: