5
1. GENERAL INFORMATION
Thank you for choosing ALARKO brand.
This booklet covers ALARKO branded premix condensing Super Fit 24/28/35
model gas fired combi boilers in, suitable for natural gas or LPG use. Keep this
booklet on hand to consult to whenever you may need.
You will be informed about combi boiler use by authorized dealers after they
mount the boiler on its position and set the connections, and by authorized
service people after they take the boiler into operation. You can ask any unclear
points again. Our experts will be glad to answer your questions.
For long-term, safe and economical use of the boiler, please read this booklet
carefully before using the boiler, obey the safety rules and warnings carefully.
Start-up of the boiler by authorized service is free of charge and it is required for
the product guarantee to be valid.
1.1 General Notifications
Professionally qualified personnel in accordance with current laws
and standards and in line with the manufacturer’s instructions must
install the appliance.
With ‘Professionally qualified personnel’ is intended a personnel with
technical knowledge in the field of installation and maintenance of
components for central heating and domestic hot water production
systems for domestic and industrial use.
The appliance must be used solely for the purpose for which it has
been designed and manufactured: central heating and domestic
hot water production. Any other use is deemed as improper and as
such dangerous. Under no circumstances will the manufacturer be
held responsible for damage or injury to persons or animals caused
by errors in the installation and/or use of the appliance, or through
non-compliance with current local and national standards and/or the
manufacturer’s instructions.
The installation, operation and maintenance manual form an integral
and essential part of the product and must be kept near the appliance
always.
This manual must be kept in a safe place and made available for any
future reference. If the appliance is sold or transferred to a different
owner, this must follow the appliance to be read by the new owner
and/or installer.
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
Содержание SUPER FIT 24
Страница 2: ...Code No A 1 5 1i Publishing Date 020321 Revision Date 020321...
Страница 8: ...8 1 2 Declaration of Conformity...
Страница 23: ...23 3 TECHNICAL CHARACTERISTICS 3 1 Technical Data...
Страница 26: ...26 3 4 Dimensions 3 4 Dimensions Figure 7 Dimensions Figure 7 Dimensions Gas Inlet...
Страница 35: ...35 Opening the Package Opening the Package Figure 13 Opening the package...
Страница 46: ...46 Figure 24 Flue applications...
Страница 52: ...52...
Страница 53: ...53...
Страница 54: ...54...
Страница 55: ...55...