background image

5

1. GENERAL INFORMATION

Thank you for choosing ALARKO brand.
This booklet covers ALARKO branded premix condensing SRS 20/28/36 model 

combi boilers in SERADENS SUPER Product  range, suitable for natural gas 

or LPG use.   Keep this booklet on hand to consult to whenever you may need.
You will be informed about combi boiler use by authorized dealers after they 

mount  the  boiler  on  its  position  and  set  the  connections,  and  by  authorized 

service people after they take the boiler into operation. You can ask any unclear 

points again. Our experts will be glad to answer your questions.
For long-term, safe and economical use of the boiler, please read this booklet 

carefully before using the boiler, obey the safety rules and warnings carefully.
Start-up of the boiler by authorized service is free of charge and it is required for 

the Product  guarantee to be valid. 

1.1 General Notifications

    

Professionally  qualified  personnel  in  accordance  with  current  laws 

and standards and in line with the manufacturer’s instructions must 

install the appliance.

     With ‘Professionally qualified personnel’ is intended a personnel with 

technical knowledge in the field of installation and maintenance of 

components for central heating and domestic hot water Product ion 

systems for domestic and industrial use.

     The appliance must be used solely for the purpose for which it has 

been designed and manufactured: central heating and domestic hot 

water Product ion. Any other use is deemed as improper and as such 

dangerous.  Under  no  circumstances  will  the  manufacturer  be  held 

responsible for damage or injury to persons or animals caused by 

errors in the installation and/or use of the appliance, or through non-

compliance with current local and national standards and/or the man-

ufacturer’s instructions.

     The installation, operation and maintenance manual forms an integral 

and essential part of the Product  and must be kept near the appliance 

always.

      This manual must be kept in a safe place and made available for any 

future reference. If the appliance is sold or transferred to a different 

owner, this must follow the appliance to be read by the new owner 

and/or installer.

21

INSTALLATION INSTRUCTIONS

TA99A086.B0706

15

3.5 Gas connection 

  The connection to the gas supply must be carried out by professionally qualified personnel, registered 

in accordance with current legislation. 

  When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance 

with the Gas Safety and Use Regulations..  

Before installing the boiler, check the following: 

  The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and 

must be fitted with all the safety and control devices provided for by current standards. 

  The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to 

boiler and comply with current standards and regulations.  

Check the internal and external seals of the gas supply system. 

  A gas shut-off valve must be installed upstream of the appliance 

  Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has 

been set-up (see gas type label inside the boiler). 

  The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the 

boiler). 

  Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe. 

  Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel. 

3.6 Electrical connections 

  The connection to the mains power supply must be carried out by professionally qualified personnel, 

registered in accordance with current legislation and authorised by Radiant Bruciatori. 

  Always check to make sure that the appliance has an efficient earth system. This requirement is only 

satisfied if it has been properly connected to an efficient earth system installed in accordance with the 

requirements of current safety standards (Standard CEI 64-8 Electrical Installations).

 This basic safety 

measure must be checked and verified.  

In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be 

held liable for any damage or injury caused as a result of an inefficient or inexistent earth system. 

  The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180 

W. 

The appliance should be protected by a 3 A 

fuse. The connection to the mains electricity supply must be 

via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the 

appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram. 

  Ensure  the domestic power supply is checked by a qualified electrician to ensure that it can support the 

maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the 

cable sizes are adequate for the power absorbed by the appliance.

  The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the 

appliance and have the cable replaced by a suitably qualified electrician.

  When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with 

maximum external Ø 8 mm;

When using an electrical appliance, a few fundamental rules must be observed: 

  Do not touch the appliance with damp or wet parts of the body or when barefoot. 

  Do not pull on the electric wires. 

  Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been 

expressly provided for. 

  Do not allow the appliance to be used by children or anyone unfamiliar with its operation. 

Alarko Carrier.

3.3 Electrical Connection

110

3.2 Gas Connection

21

INSTALLATION INSTRUCTIONS

TA99A086.B0706

15

3.5 Gas connection 

  The connection to the gas supply must be carried out by professionally qualified personnel, registered 

in accordance with current legislation. 

  When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance 

with the Gas Safety and Use Regulations..  

Before installing the boiler, check the following: 

  The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and 

must be fitted with all the safety and control devices provided for by current standards. 

  The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to 

boiler and comply with current standards and regulations.  

Check the internal and external seals of the gas supply system. 

  A gas shut-off valve must be installed upstream of the appliance 

  Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has 

been set-up (see gas type label inside the boiler). 

  The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the 

boiler). 

  Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe. 

  Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel. 

3.6 Electrical connections 

  The connection to the mains power supply must be carried out by professionally qualified personnel, 

registered in accordance with current legislation and authorised by Radiant Bruciatori. 

  Always check to make sure that the appliance has an efficient earth system. This requirement is only 

satisfied if it has been properly connected to an efficient earth system installed in accordance with the 

requirements of current safety standards (Standard CEI 64-8 Electrical Installations).

 This basic safety 

measure must be checked and verified.  

In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be 

held liable for any damage or injury caused as a result of an inefficient or inexistent earth system. 

  The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180 

W. 

The appliance should be protected by a 3 A 

fuse. The connection to the mains electricity supply must be 

via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the 

appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram. 

  Ensure  the domestic power supply is checked by a qualified electrician to ensure that it can support the 

maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the 

cable sizes are adequate for the power absorbed by the appliance.

  The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the 

appliance and have the cable replaced by a suitably qualified electrician.

  When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with 

maximum external Ø 8 mm;

When using an electrical appliance, a few fundamental rules must be observed: 

  Do not touch the appliance with damp or wet parts of the body or when barefoot. 

  Do not pull on the electric wires. 

  Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been 

expressly provided for. 

  Do not allow the appliance to be used by children or anyone unfamiliar with its operation. 

Alarko Carrier.

3.3 Electrical Connection

110

3.2 Gas Connection

21

INSTALLATION INSTRUCTIONS

TA99A086.B0706

15

3.5 Gas connection 

  The connection to the gas supply must be carried out by professionally qualified personnel, registered 

in accordance with current legislation. 

  When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance 

with the Gas Safety and Use Regulations..  

Before installing the boiler, check the following: 

  The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and 

must be fitted with all the safety and control devices provided for by current standards. 

  The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to 

boiler and comply with current standards and regulations.  

Check the internal and external seals of the gas supply system. 

  A gas shut-off valve must be installed upstream of the appliance 

  Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has 

been set-up (see gas type label inside the boiler). 

  The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the 

boiler). 

  Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe. 

  Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel. 

3.6 Electrical connections 

  The connection to the mains power supply must be carried out by professionally qualified personnel, 

registered in accordance with current legislation and authorised by Radiant Bruciatori. 

  Always check to make sure that the appliance has an efficient earth system. This requirement is only 

satisfied if it has been properly connected to an efficient earth system installed in accordance with the 

requirements of current safety standards (Standard CEI 64-8 Electrical Installations).

 This basic safety 

measure must be checked and verified.  

In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be 

held liable for any damage or injury caused as a result of an inefficient or inexistent earth system. 

  The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180 

W. 

The appliance should be protected by a 3 A 

fuse. The connection to the mains electricity supply must be 

via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the 

appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram. 

  Ensure  the domestic power supply is checked by a qualified electrician to ensure that it can support the 

maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the 

cable sizes are adequate for the power absorbed by the appliance.

  The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the 

appliance and have the cable replaced by a suitably qualified electrician.

  When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with 

maximum external Ø 8 mm;

When using an electrical appliance, a few fundamental rules must be observed: 

  Do not touch the appliance with damp or wet parts of the body or when barefoot. 

  Do not pull on the electric wires. 

  Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been 

expressly provided for. 

  Do not allow the appliance to be used by children or anyone unfamiliar with its operation. 

Alarko Carrier.

3.3 Electrical Connection

110

3.2 Gas Connection

21

INSTALLATION INSTRUCTIONS

TA99A086.B0706

15

3.5 Gas connection 

  The connection to the gas supply must be carried out by professionally qualified personnel, registered 

in accordance with current legislation. 

  When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance 

with the Gas Safety and Use Regulations..  

Before installing the boiler, check the following: 

  The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and 

must be fitted with all the safety and control devices provided for by current standards. 

  The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to 

boiler and comply with current standards and regulations.  

Check the internal and external seals of the gas supply system. 

  A gas shut-off valve must be installed upstream of the appliance 

  Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has 

been set-up (see gas type label inside the boiler). 

  The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the 

boiler). 

  Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe. 

  Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel. 

3.6 Electrical connections 

  The connection to the mains power supply must be carried out by professionally qualified personnel, 

registered in accordance with current legislation and authorised by Radiant Bruciatori. 

  Always check to make sure that the appliance has an efficient earth system. This requirement is only 

satisfied if it has been properly connected to an efficient earth system installed in accordance with the 

requirements of current safety standards (Standard CEI 64-8 Electrical Installations).

 This basic safety 

measure must be checked and verified.  

In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be 

held liable for any damage or injury caused as a result of an inefficient or inexistent earth system. 

  The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180 

W. 

The appliance should be protected by a 3 A 

fuse. The connection to the mains electricity supply must be 

via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the 

appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram. 

  Ensure  the domestic power supply is checked by a qualified electrician to ensure that it can support the 

maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the 

cable sizes are adequate for the power absorbed by the appliance.

  The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the 

appliance and have the cable replaced by a suitably qualified electrician.

  When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with 

maximum external Ø 8 mm;

When using an electrical appliance, a few fundamental rules must be observed: 

  Do not touch the appliance with damp or wet parts of the body or when barefoot. 

  Do not pull on the electric wires. 

  Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been 

expressly provided for. 

  Do not allow the appliance to be used by children or anyone unfamiliar with its operation. 

Alarko Carrier.

3.3 Electrical Connection

110

3.2 Gas Connection

21

INSTALLATION INSTRUCTIONS

TA99A086.B0706

15

3.5 Gas connection 

  The connection to the gas supply must be carried out by professionally qualified personnel, registered 

in accordance with current legislation. 

  When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance 

with the Gas Safety and Use Regulations..  

Before installing the boiler, check the following: 

  The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and 

must be fitted with all the safety and control devices provided for by current standards. 

  The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to 

boiler and comply with current standards and regulations.  

Check the internal and external seals of the gas supply system. 

  A gas shut-off valve must be installed upstream of the appliance 

  Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has 

been set-up (see gas type label inside the boiler). 

  The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the 

boiler). 

  Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe. 

  Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel. 

3.6 Electrical connections 

  The connection to the mains power supply must be carried out by professionally qualified personnel, 

registered in accordance with current legislation and authorised by Radiant Bruciatori. 

  Always check to make sure that the appliance has an efficient earth system. This requirement is only 

satisfied if it has been properly connected to an efficient earth system installed in accordance with the 

requirements of current safety standards (Standard CEI 64-8 Electrical Installations).

 This basic safety 

measure must be checked and verified.  

In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be 

held liable for any damage or injury caused as a result of an inefficient or inexistent earth system. 

  The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180 

W. 

The appliance should be protected by a 3 A 

fuse. The connection to the mains electricity supply must be 

via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the 

appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram. 

  Ensure  the domestic power supply is checked by a qualified electrician to ensure that it can support the 

maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the 

cable sizes are adequate for the power absorbed by the appliance.

  The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the 

appliance and have the cable replaced by a suitably qualified electrician.

  When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with 

maximum external Ø 8 mm;

When using an electrical appliance, a few fundamental rules must be observed: 

  Do not touch the appliance with damp or wet parts of the body or when barefoot. 

  Do not pull on the electric wires. 

  Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been 

expressly provided for. 

  Do not allow the appliance to be used by children or anyone unfamiliar with its operation. 

Alarko Carrier.

3.3 Electrical Connection

110

3.2 Gas Connection

Содержание SRS 20

Страница 1: ...SERADENS SUPER SRS 20 28 36 PREMIX CONDENSING BOILER INSTALLATION AND OPERATING INSTRUCTIONS ...

Страница 2: ...Code No A 1 4 8i Publishing Date 100616 Revision Date 100616 ...

Страница 3: ...14 2 7 Filling the System 14 2 8 Operating Modes and Start Up 16 2 9 Diagnostics Error Codes 18 2 10 Automatic Control Devices Optional 20 2 11 Automatic Operation of the Boiler In Accordance With Weather Temperature Optional 21 2 12 Domestic Hot Water DHW Pre heating Function 22 2 13 Solar Connection Set 23 2 14 Use with LPG 25 3 TECHNICAL CHARACTERISTICS 26 3 1 Technical Data 26 3 2 Dimensions S...

Страница 4: ...ion of the Boiler 38 4 5 Water Connections 39 4 6 Appropriate Central Heating Pipes 41 4 7 Gas Connection 42 4 8 Electrical Connections 43 4 9 Flue Connections 46 5 COMMISSIONING THE APPLIANCE 54 6 PERIODIC MAINTENANCE AND CLEANING 54 6 1 Periodic Maintenance of the Combi Boiler 54 6 2 Maintenance Content 54 6 3 Cleaning of the Combi Boiler User 55 ...

Страница 5: ...The power supply cable must not be replaced by the user if the cable is damaged in any way sw appliance and have the cable replaced by a suitably qualified electrician When replacing the power supply cable only use cables of the same characteristics HO5 VV maximum external Ø 8 mm When using an electrical appliance a few fundamental rules must be observed Do not touch the appliance with damp or wet...

Страница 6: ...uitably qualified electrician When replacing the power supply cable only use cables of the same characteristics HO5 VV maximum external Ø 8 mm When using an electrical appliance a few fundamental rules must be observed Do not touch the appliance with damp or wet parts of the body or when barefoot Do not pull on the electric wires Do not leave the appliance exposed to atmospheric elements rain sun ...

Страница 7: ...to an efficient earth system installed in accordance with the re quirements of current safety standards This fundamental safety require ment must be checked and verified In case of doubt have the electrical system checked by a qualified electrician The manufacturer will not be held liable for any damage or injury caused as a result of an ineffective or non existent earth system The domestic power ...

Страница 8: ...T 2 1 SPECIFIC STANDARD FOR TYPE C APPLIANCES AND TYPE B2 B3 AND B5 APPLIANCES OF A NOMINAL HEAT INPUT NOT EXCEEDING 1 000 kW EN 60335 1 HOUSEHOLD AND SIMILAR ELECTRICAL APPLIANCES SAFETY PART 1 GENERAL REQUIREMENTS EN 60335 2 102 HOUSEHOLD AND SIMILAR ELECTRICAL APPLIANCES SAFETY PART 2 102 PARTICULAR REQUIREMENTS FOR GAS OIL AND SOLID FUEL BURNING APPLIANCES HAVING ELECTRICAL CONNEC TIONS EN 132...

Страница 9: ...ollowing substances in the manufac ture of ALARKO heating Product s Asbestos Mercury CFC s 1 3 Gas Safety Gas appliances must be installed only by informed and authorized people in accordance with rules of local gas distribution institutions Gas conversion pro cesses must also be performed by authorized people This appliance is produced and certified to operate with natural gas or mix LPG under ga...

Страница 10: ...rmed ideally with the premix system i e premixing of gas and air at the ideal ratio of 1 10 before combustion This is ensured by the modulating fan which adjusts its speed as per the capacity requirement and the venturi which mixes the gas taken by the drawing of the fan from the modulating gas valve and air in the ideal ratio 2 USER INSTRUCTIONS 2 1 Introduction Following the installation and com...

Страница 11: ...installer For your own safety do not ask the installer to install your boiler to prohibited spaces Before gas installation a suitable gas installation project has to be pre pared and approved according to the requirements of local gas distribu tion organization After approval of local gas distribution organization and precise application of installation have your boiler commissioned by an Authoriz...

Страница 12: ...e of doubt a pres sure regulator should be fitted Consult your installer on this issue 2 4 Terms and Conditions of Guarantee and Service Your boiler is 2 two years guaranteed by Alarko Carrier for material and Prod uct ion defects provided that the principles warnings and standards mentioned in installation and operating instructions are obeyed Guarantee is not valid under below conditions Install...

Страница 13: ...ncrease button 4 Domestic hot water DHW temperature decrease button 5 Heating water temperature increase button 6 Heating water temperature decrease button 7 LCD display for temperature error codes and operating mode 8 Terminal board for external wiring of room thermostat and outside tempera ture sensor Room thermostat and outside temperature sensor is optional 1 2 3 4 5 6 7 8 Figure 1 Control Pan...

Страница 14: ...s displayed The system comes back to the default menu if no key is pressed within a time out period corresponding to 30 sec Alternatively you can close user info menu by pressing Info key 2 for time period of 2 seconds 2 7 Filling the System Pressure sensor is included in Seradens Super combi boilers After all connec tions electric fittings and flue are completed system could be filled by means of...

Страница 15: ...e value open the filling tap F in Figure 2 Check the pressure value from the screen to avoid filling the system exces sively Keep filling the system until the pressure reaches 1 2 bars then close the filling tap Figure 2 Bottom view of Seradens Super combi boiler Excessive filling of the heating system leads to E47 error this is a precaution to avoid uncontrolled discharge of excess water from 3 b...

Страница 16: ...de press key 1 Figure 1 and see tap symbol and radiator symbol continuously shown on the display At this mode combi boiler operates for the domestic hot DHW and heating CH systems The automatic ignition system lights the burner every time there is a demand for both The existence of the flame is shown with flame symbol on the display In this case the tap symbol on the display blinks when system ope...

Страница 17: ... in Section 2 7 Setting Heating CH Temperature The heating temperature is regulated by using keys 5 and 6 Figure 1 Pushing key 5 will increase the CH set point temperature Pushing key 6 will decrease the CH set point temperature The range of set temperature for the CH varies from a minimum of 30 C to a maximum of 85 C in case of reduced range operation temperature range is from a minimum of 30 C t...

Страница 18: ...ate see gas type l boiler Prior to installation it is good practice to ensure that there are no machining residues on the gas s Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified 3 6 Electrical connections The connection to the mains power supply must be carried out by professionally qualifi registered in accordance with current legislation and autho...

Страница 19: ...ter tap close filling tap on the appliance and open main DHW inlet tap under the appliance If E46 Pressure Sensor Error code lights on the display continuously Reset the system by pressing key 1 for 2 seconds if the error persists call the Service Centre E05 Heating Sensor Error E05 code lights on the display continuously Call the Service Centre E06 Domestic Hot Water DHW Temperature Sensor Error ...

Страница 20: ...ces Optional Using one of the following automatic control devices is recommended on the purpose of comfort and fuel economy Room Thermostat You can use room thermostat with your boiler to maintain desired room temperature Analog and digital models are available These models are nonprogrammable Weekly Programmable Room Thermostat These device is used to set your boiler to run at desired time interv...

Страница 21: ... safety of your boiler contact the authorized installers or services to buy any of these options Do not forget to ask for user manual of the device You can get more detailed informa tion from our web site www alarko carrier com tr 2 11 Automatic Operation of the Boiler In Accordance With Weather Temperature Optional If you use outside sensor with your boiler you can manage the appliance with one o...

Страница 22: ...W temperature reaches 5 C below set value This is enough for DHW tem perature to reach set value It is obligatory to use room thermostat for pre heating function s turn to come in winter and only heating modes Otherwise pre heating function is never active because software always thinks as though there is always demand for heating In summer mode water in DHW heat exchanger is pre heated for the ne...

Страница 23: ...he solar collector and hot water tank to the Solar Con nection Set which can be supplied as accessory with Seradens Super There is no need for any electronic control system Schematics of a working system is shown in Figure 3 Solar Connection Set is shown in Figure 4 Heating DHW Production with a combi boiler Solar Collector Cold Water Inlet Hot water tank Figure 3 Solar Connection Set Solar Connec...

Страница 24: ...prevents people from boiling If water temperature in the hot water tank is below 48 C diverting valve sends domestic hot water to the combi boiler to be heated to demanded temperature Temperature of domestic hot water coming from combi boiler is also set before being sent to the taps Setting temperature of thermostatic valve can be set be tween 30 56 C Solar Connection Set is composed of a Solar C...

Страница 25: ...n case thermostatic hot water buckets are used to heat up the LPG bottles water temperature should not exceed 22 C Do not place the boiler and the LPG bottles in the same cabinet Use certified bottles only Do not shake or lay the bottles Only use a certified 30 mbar regulator at every bottle exits If you smell gas turn the bottles off and follow the instructions in Gas Safety section WARNING The b...

Страница 26: ... C 95 4 95 4 95 4 Expansion Vessel Capacity liters 8 8 10 Max Operating Pressure Heating bar 2 8 2 8 2 8 Min Operating Pressure Heating bar 0 5 0 5 0 5 Domestic hot Water DHW Circuit Automatic Bypass Feature DHW Temperature Setting Min Max C 30 60 30 60 30 60 Max Hot Water Operating Pressure bar 10 10 10 Min Hot Water Operating Pressure bar 0 5 0 5 0 5 DHW Flow Rate at ΔT 30 K liters min 10 14 18 ...

Страница 27: ...27 3 2 Dimensions SRS 20 28 36 Figure 5 Dimensions ...

Страница 28: ...8 3 BAR PRESSURE SAFETY VALVE 9 LIMIT THERMOSTAT 10 AUTOMATIC AIR VENT 11 HEATİNG WATER FLOW TEMPER ATURE SENSOR 12 PUMP 13 PRESSURE SENSOR 14 FLUE FUSE 15 EXPANSION TANK 16 DOMESTIC HOT WATER DHW TEMPERATURE SENSOR 17 SIPHON 18 DRAINAGE TAP 19 CONDENSATE DRAIN PIPE 20 3 WAY VALVE MOTOR 21 WATER FILLING TAP 22 ELECTRONIC FLOW SENSOR 23 DOMESTIC HOT WATER DHW PLATE EXCHANGER 24 HEATING RETURN PIPE ...

Страница 29: ...RE SAFETY VALVE 9 AUTOMATIC AIR VENT 10 LIMIT THERMOSTAT 11 HEATING WATER FLOW TEMPERATURE SENSOR 12 PUMP 13 PRESSURE SENSOR 14 FLUE FUSE 15 EXPANSION TANK 16 DOMESTIC HOT WATER DHW TEMPERATURE SENSOR 17 SIPHON 18 DRAINAGE TAP 19 FLOW LIMITER 20 ELECTRONIC FLOW SEN SOR 21 DOMESTIC HOT WATER DHW PLATE EXCHANGER 22 3 WAY VALVE MOTOR 23 WATER FILLING TAP HR HEATING RETURN HF HEATING FLOW G GAS CWI CO...

Страница 30: ...30 3 5 Circulation Pump Performance Chart SRS 20 Head m Flow Rate m h III Pump head at maximum speed II Pump head at second speed I Pump head at minimum speed Figure 8 SRS 20 Pump Performance Chart ...

Страница 31: ...31 SRS 28 III Pump head at maximum speed II Pump head at second speed I Pump head at minimum speed Figure 9 SRS 28 Pump Performance Chart Flow Rate m h ...

Страница 32: ...32 SRS 36 III Pump head at maximum speed II Pump head at second speed I Pump head at minimum speed Figure 10 SRS 36 Pump Performance Chart Flow Rate m h ...

Страница 33: ...HW cycles CH CH antifreeze DHW DHW antifreeze chimney sweeper cycles Parameters programming function External temperature compensation function if outside sensor is used Circulation pump anti locking function 3 way diverting valve anti locking function Remote controller communication channel Opentherm protocol Automatic flame control system Domestic hot water pre heating function Gas type selectio...

Страница 34: ...heless remain enabled If the boiler was previously on it is switched off and the post ventilation pump overrun circulation pump and three way valve inactivity protection functions are enabled The remote control where fitted remains active and illuminated 4 INSTALLATION 4 1 Reference Standards This appliance meets the requirements of EN 15502 1 2012 A1 2015 GAS FIRED HEATING BOILERS PART 1 GENERAL ...

Страница 35: ...00 3 2 2014 EN 61000 3 3 2013 Current gas safety regulations state that all gas appliances must be installed by a competent person in accordance with the regulations and rules in force in the countries of destination These appliances must be installed in accordance with relevant national and local rules and regulations in force The manufacturer s instructions must not be taken in any way as overri...

Страница 36: ...can be carried by two people by uplifting it through the two holes on both sides The boiler should be stored in a place free of dust and moisture and should not be taken out of its package until it is to be installed When stored maximum four boxes can be placed on top of each other Boilers can be installed following the completion of water and electric sys tems ...

Страница 37: ...37 Figure 13 Opening the Package Opening the Package ...

Страница 38: ...nstallation clea rances If the boiler is installed in a room containing a bath or shower reference must be made to the national standards and local requirements In order to allow access to the interior of the boiler for maintenance pur poses it is important that the necessary clearances indicated in Figure 14 are respected For mounting the appliance it is required to follow the below instructions ...

Страница 39: ...icient earth system This requirem satisfied if it has been properly connected to an efficient earth system installed in accordan requirements of current safety standards Standard CEI 64 8 Electrical Installations This b measure must be checked and verified In case of doubt have the electrical system checked by a qualified electrician The manufacturer held liable for any damage or injury caused as ...

Страница 40: ...ave a hardness rating of more than 17 5 French hardness It is nevertheless advisable to check the properties of the water supply and install the appropriate treatment devices where nec essary The cold water supply pressure at the inlet to the boiler must be between 0 5 and 10 bars In areas with higher water inlet pressure a pressure reducing valve must be fitted before the boiler The frequency of ...

Страница 41: ...fety valve in the case of system overpressure Condensate Drain The condensate drain flexible pipe supplied with the boiler is connected to the siphon The condensate discharge into the drainage system is allowed by means of siphon Condensate drain pipe must be connected to sewage drain as open connection at boiler side to prevent interruption in flow and as including U form in pipe to prevent smell...

Страница 42: ...ony at low water temperature This condition causes change in water characteristics and increase its viscosity and finally heat exchanger and pump obstructions may occur To prohibit above consequences biocide and electro cell preventive inhibi tors additives must be added to piping water Sentinel X700 X100 etc Piping System Obstructions Piping system obstructions are generally encountered just afte...

Страница 43: ...a a single pole switch with at least 3 millimetres gap between open contacts mounted upstr appliance Make sure that the positions of the live and neutral wires correspond to the wiring diagram Ensure the domestic power supply is checked by a qualified electrician to ensure that it can maximum power absorption of the appliance as indicated on the rating plate In particular make s cable sizes are ad...

Страница 44: ...c wires Do not leave the appliance exposed to atmospheric elements rain sun etc unless these conditions have been expressly provided for Do not allow the appliance to be used by children or anyone unfamiliar with its operation Outside Sensor Remote Control Room Thermostat Connections Outside sensor remote control and room thermostat cables must be connected to terminal board These cables must be t...

Страница 45: ...ned right bot tom part of the plastic panel see A detail in Figure 19 d With the cover removed connect remote control room thermostat and outside sensor wires as shown in Figure 19 A detail Note Room thermostat is in bridged condition as factory setting If room thermostat will not be used certainly it must be left as bridged e When the wires have been connected place the protective cover and then ...

Страница 46: ...sing an electrical appliance a few fundamental rules must be observed Do not touch the appliance with damp or wet parts of the body or when barefoot Do not pull on the electric wires Do not leave the appliance exposed to atmospheric elements rain sun etc unless these conditions expressly provided for Do not allow the appliance to be used by children or anyone unfamiliar with its operation Alarko C...

Страница 47: ...ification Do not allow the flue gas to pro trude inside the chimney instead terminate it before it reaches the flue pipe The flue gas must be perpen dicular to the opposite wall of the flue pipe see Figure 23 Flue Application Options Flue application options are C13 C33 C33 x C43 C43 x C53 C53 x C63 C63 x C83 C83 x C93 C93 x B23 and B33 You can find ex planations in Table 4 1 and visual ap plicati...

Страница 48: ...ressure area C43 x Combustion air and flue gas connections connected to multiple air flue gas chimney system C53 x Combustion air intake and flue gas discharge with different lines Outlets are at different pressure areas C63 x Connection design as per appliances where combustion air intake and flue gas discharge cannot be measured C83 x Flue gas installation is independent or with multiple connect...

Страница 49: ...exhaust fumes The flue gas pipe can be connected directly to the outside or can be connected to a suitable combined flue system MAXIMUM FLUE LENGTH SRS 20 6 m SRS 28 5 m The maximum flue length linear equivalent is obtained by summing the length of linear pipe and the equivalent lengths of each elbow fitted The linear equivalent is intended as being the total length of the pipe from the connection...

Страница 50: ...the exhaust fumes The flue gas pipe can be connected directly to the outside or can be connected to a suitable combined flue system MAXIMUM FLUE LENGTH SRS 36 8 m The maximum flue length linear equivalent is obtained by summing the length of linear pipe and the equivalent lengths of each elbow fitted The linear equivalent is intended as being the total length of the pipe from the connection with t...

Страница 51: ...d draws combustion air through two separate pipes Figure 29 Twin flue set MAXIMUM FLUE LENGTH Ø 80 80 50 m The maximum flue length linear equivalent is obtained by summing the length of linear pipe and the equivalent lengths of each elbow fitted The linear equivalent is intended as being the total length of the pipe from the connection with the combustion chamber of the appliance excluding the fir...

Страница 52: ...the Ø60 mm plastic inner pipe discharges the exhaust fumes MAXIMUM FLUE LENGTH SRS 20 6 m SRS 28 5 m The maximum flue length linear equivalent is obtained by summing the length of linear pipe and the equiv alent lengths of each elbow fitted The linear equivalent is intended as being the total length of the pipe from the connection with the combustion chamber of the appliance excluding the first el...

Страница 53: ...5 mm pipe draws the combustion air while the Ø80 mm plastic inner pipe discharges the exhaust fumes MAXIMUM FLUE LENGTH SRS 36 8 m The maximum flue length linear equivalent is obtained by summing the length of linear pipe and the equiv alent lengths of each elbow fitted The linear equivalent is intended as being the total length of the pipe from the connection with the combustion chamber of the ap...

Страница 54: ... etc unless these condition expressly provided for Do not allow the appliance to be used by children or anyone unfamiliar with its operation Alarko Carrier 3 3 Electrical Connection 3 5 Gas connection The connection to the gas supply must be carried out by professionally qualified personnel in accordance with current legislation When connecting the boiler to the gas supply pipe only use appropriat...

Страница 55: ... with detector or detergent foam Cleaning of dirt separator Cleaning of filters Control of accurate operating of the appliance Filling the authorized service form 6 3 Cleaning of the Combi Boiler User Wipe the outer case of the appliance with soft humid fabric Don t use hard abrasive cleaning materials ...

Страница 56: ...56 ...

Страница 57: ...57 ...

Страница 58: ...58 ...

Страница 59: ...59 ...

Страница 60: ...0 Şehit Fethibey Cad No 55 Kat 13 35210 Pasaport İZMİR Tel 0232 483 25 60 Fax 0232 441 55 13 Ziyapaşa Bulvarı Çelik Ap No 25 5 6 01130 ADANA Tel 0322 457 62 23 Fax 0322 453 05 84 Mehmetçik Mahallesi Aspendos Bulvarı No 79 5 ANTALYA Tel 0242 322 00 29 Fax 0242 322 87 66 444 0 128 İSTANBUL ANKARA İZMİR ADANA ANTALYA MDH web www alarko carrier com tr e posta info alarko carrier com tr ...

Отзывы: