![Alarko SRS 20 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/alarko/srs-20/srs-20_installation-and-operating-instructions-manual_2888488026.webp)
26
3. TECHNICAL CHARACTERISTICS
3.1 Technical Data
Model
SRS 20
SRS 28
SRS 36
CE Certification
no
1312CR6123
1312CR6123
1312CR6123
Appliance Type
B23-B33-C13-C13(x)-C33-
C33(x)-C43-C43(x)-C53-C53(x)-
C63-C63(x)-C83-C83(x)-C93-
C93(x)
B23-B33-C13-C13(x)-C33-
C33(x)-C43-C43(x)-C53-
C53(x)-C63-C63(x)-C83-
C83(x)-C93-C93(x)
B23-B33-C13-C13(x)-C33-
C33(x)-C43-C43(x)-C53-
C53(x)-C63-C63(x)-C83-
C83(x)-C93-C93(x)
Appliance Category
II2H3B/P
II2H3B/P
II2H3B/P
Domestic hot Water (DHW) Input Max.
kW
21
29.3
37.7
Heat Input Min. (50/30
°
C)
kW
3.9 (G20) - 5.5 (G30)
5.5 (G20) - 8.15 (G30)
5.7 (G20) - 8.89 (G30)
Heat Output Min. (50/30
°
C)
kW
4.0 (G20) - 3.74 (G30)
5.7 (G20) - 5.19 (G30)
6.0 (G20)
–
6.78 (G30)
Heat Input Max. (50/30
°
C)
kW
18.5
26.0
32.8
Heat Output Max. (50/30
°
C)
kW
20.1
27.9
35.3
Efficiency at %100 load (50/30
°
C)
%
109.2
107.3
107.6
Efficiency at %30 load (50/30
°
C)
%
106.8
106.3
105,9
Heat Output Max. (80/60
°
C)
kW
18.1
25.5
32.2
Heat Output Min. (80/60
°
C)
kW
3.7 (G20)
–
2.92 (G30)
5.3 (G20)
–
5.19 (G30)
5.5 (G20)
–
5.98 (G30)
Efficiency at %100 load (80/60
°
C)
%
97.9
97.9
98.03
Heating (Central Heating) Circuit
Central Heating Water Temperature Setting (Min-Max)
°
C
30-85 / 30-45
30-85 / 30-45
30-85 / 30-45
Max. Heating Operating Temperature
°
C
95
±4
95±4
95±4
Expansion Vessel Capacity
liters
8
8
10
Max. Operating Pressure (Heating)
bar
2.8
2.8
2.8
Min. Operating Pressure (Heating)
bar
0.5
0.5
0.5
Domestic hot Water (DHW) Circuit
(Automatic Bypass Feature)
DHW Temperature Setting (Min-Max)
°
C
30-60
30-60
30-60
Max. Hot Water Operating Pressure
bar
10
10
10
Min. Hot Water Operating Pressure
bar
0.5
0.5
0.5
DHW Flow Rate at
Δ
T 30 K
liters/min
10
14
18
Dimensions
Width
mm
437
437
437
Height
mm
640
640
640
Depth
mm
296
296
296
Weight (net)
kg
29
30
32
Hydraulic Connections
Central Heating Flow Connection
Ø
3/4
”
3/4
”
3/4
”
Central Heating Return Connection
Ø
3/4
”
3/4
”
3/4
”
DHW Input (Cold Water)
Ø
1/2
”
1/2
”
1/2
”
DHW Output (Hot Water)
Ø
1/2
”
1/2
”
1/2
”
Gas Connection
Ø
1/2
”
1/2
”
1/2
”
Flue Systems
Horizontal
–
Concentric Flue System
Ø
mm
60/100
60/100
80/125
Max. Flue Length
m
6
5
8
Twin Pipe Flue System
Ø
mm
80/80
80/80
80/80
Max. Flue Length (From Terminal to Terminal)
m
50
50
50
Vertical
–
Concentric Flue System
Ø
mm
60/100
60/100
80/125
Max. Flue Length
m
6
5
8
Gas Supply
Natural Gas G20
Inlet Pressure
mbar
20
20
20
Gas Consumption
m
³
/h
2
2.8
3.57
LPG G30
Inlet Pressure
mbar
30
30
30
Gas Consumption
kg/h
1.28
1.85
2.36
Electrical Specifications
Power Supply
V/Hz
230/50
230/50
230/50
Electrical Power Consumption
W
113
121
123
Electrical Protection
IP
X4D
X4D
X4D
Noise Level
db(A)
39-42
39-42
39-42
Содержание SRS 20
Страница 1: ...SERADENS SUPER SRS 20 28 36 PREMIX CONDENSING BOILER INSTALLATION AND OPERATING INSTRUCTIONS ...
Страница 2: ...Code No A 1 4 8i Publishing Date 100616 Revision Date 100616 ...
Страница 27: ...27 3 2 Dimensions SRS 20 28 36 Figure 5 Dimensions ...
Страница 37: ...37 Figure 13 Opening the Package Opening the Package ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 59: ...59 ...