![AL-KO EASYAIR flat EF-01 Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/al-ko/easyair-flat-ef-01/easyair-flat-ef-01_operating-and-assembly-instruction-manual_2887691035.webp)
Subject to changes in line with technical progress.
35
3059570
Assembly
WARNING
Risk of injury from falling from ladders, scaffolding or work platforms.
Only use suitable and tested ladders, steps, scaffolding and work platforms.
Only allow assembly, installation, commissioning, repair, maintenance and servicing
work to be carried out by qualified staff.
Work with care.
If necessary, connect the switch cabinet to the field devices of the EASYAIR
®
flat unit in accordance with the circuit dia
-
gram included with the unit documentation (option with control).
5.6.1
Cable lists
NOTE
The cable cross-sections are provided with no liability.
The installation type, installation length and any accumulations have not been taken into ac-
count.
NOTE
More information on the cable list for the EASYAIR
®
flat unit can be found in the circuit dia
-
gram supplied.
5.6.2
Cable from the switch cabinet to the field devices
Field device
Cable
Actuator for damper and bypass damper
3 x 1.0 mm
2
Room unit
6-wire flat-band phone cable for RJ12 connector
Temperature sensor
2 x 1.0 mm
2
Frost protection thermostat
2 x 1.0 mm
2
Valves (heating valve, cooling valve)
3 x 1.0 mm
2
Pumps (heating pump, cooling pump)
3 x 1.5 mm
2