Installation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
24
Fig. 5.7 Current sensor wiring (2-wire)
Fig. 5.8 Current sensor wiring (3-wire)
5.2.2.4 Linear resistance signals
For supported signals see Tab. 3.2.
Fig. 5.9 Resistance sensor wiring (3-wire)
5.2.2.5 Switch contact
Two discrete "dry contact" signals can be connected to each analog input (switches, buttons, relay contacts,
etc.).
Any resistors in the range 200…3000
Ω
can be used as shunt resistors. Both resistors on the input must
have the same nominal value.
Fig. 5.10 Switch contact wiring
The status of the input connected with two switch contacts is represented as an integer in the range 0…3
(Tab. 5.3).
Table 5.3 Digital input status
Status
K1
K2
0
open
open
1
open
closed
2
closed
open
3
closed
closed