Akytec MV210-101 Скачать руководство пользователя страница 13

 

Configuration and operation 

 

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de  

12

 

4.3  Battery 

The RTC is powered by the supply voltage. When the device is powered off, RTC is powered by a replacea-

ble battery of type CR2032. 
A fully charged battery can power the RTC for 5 years. At the temperatures near the permissible limits (Tab. 

3.2), the battery life time is reduced. 
The parameter 

Voltage

 

in the group 

Battery

 shows the battery voltage in mV. 

This parameter is queried each time after powering on and then every 12 hours. 
The battery should be replaced if at least one of the following events has occurred: 

–  LED indicator   lights up for 0.2 s with a period of 2 s, which means that U

B

 

 2 V and the battery 

has to be replaced as soon as possible, but the RTC can still work for about 2 weeks without power 

supply. 

–  The battery was last time replaced 6 years ago. 

For battery replacement, see App. C. 

 

NOTE

 

If the battery voltage is less than 1.6 V, the configuration parameters are written to the 

battery-backed RAM and then transferred to the flash memory. The recording interval 

depends on the load of the module processor (at least 2 minutes). 

Since the number of erase cycles of the flash memory is limited, it is not recommended to 

record the configuration parameters cyclically when the battery is low. 

4.4  Ethernet 

To configure the Ethernet interface, open the node 

Network > Ethernet

 in the parameter tree. 

Table 4.1.   Ethernet parameters 

Parameter 

Description 

Default value 

Access 

IP address 

IPv4 Internet Protocol address 

192.168.1.99 

Subnet mask 

IP address recognition area in the subnet 

255.255.255.0 

Gateway 

IP address of the gateway 

192.168.1.1 

DNS server 1 

Primary DNS server 

77.88.8.8 

RW 

DNS server 2 

Secondary DNS server 

8.88.8.8 

RW 

New IP address 

Enter new value 

 

RW 

New subnet mask 

Enter new value 

 

RW 

New gateway 

Enter new value 

 

RW 

DHCP 

On

 / 

Off

 / 

Service button

 

Service button

 

RW 

The Ethernet parameters can be set using: 

  only main toolbar 

  service button on the device (recommended if you need to configure several devices at once) (Sect. 

4.4.1.) 

To change Ethernet parameters using the main toolbar: 

1.  Enter new values for the parameters 

New IP address

New subnet mask

 and 

New gateway

 

2.  Set the parameter 

DHCP

 to 

Off

 

3.  Click the toolbar item 

Write parameters 

 

4.  Click the toolbar item 

Restart device

   

5.  If you want to check the new parameters or continue configuring the device, you must add it again to the 

project with the new network parameters. 

Содержание MV210-101

Страница 1: ...alder Str 269 A 30179 Hannover Germany Tel 49 0 511 16 59 672 0 www akytec de MV210 101 Analog Input Module 8 AI User guide MV210 101_2022_05_34798 1 15_EN All rights reserved Subject to technical cha...

Страница 2: ...Connection with akYtecToolPro 10 4 1 1 Connection over USB 10 4 1 2 Connection over Ethernet 10 4 2 Real time clock 11 4 3 Battery 12 4 4 Ethernet 12 4 4 1 Network parameters setting using service but...

Страница 3: ...stallation 21 5 1 Mounting 21 5 2 Wiring 21 5 2 1 General information 22 5 2 2 Analog inputs 22 5 2 3 Ethernet 25 6 Factory settings restoration 26 7 Maintenance 27 8 Transportation and storage 28 9 S...

Страница 4: ...ks and for modifying that infor mation to change device behavior PWM pulse width modulation RTC real time clock RTD resistance temperature detectors TC thermocouple UTC Coordinated Universal Time worl...

Страница 5: ...current regulations and tech nical standards 1 5 Safety WARNING Ensure the mains voltage matches the voltage marked on the nameplate Ensure the device is provided with its own power supply line and e...

Страница 6: ...ur homepage akYtec de 2 1 Basic features 8 analog inputs Sect 4 8 RTD TC active linear sensors U I passive linear sensors R switch contacts supported Tab 3 2 Device and input status indicators Sect 2...

Страница 7: ...cription green Off Power off On Power on Eth 1 green Off Not connected Flashing Data transfer over Ethernet 1 interface Eth 2 green Off Not connected Flashing Data transfer over Ethernet 2 interface r...

Страница 8: ...6 s Linear signals 0 6 s Basic error RTD 0 25 FS TC 0 5 FS Linear signals 0 25 FS Additional error due to electromagnetic interference max 0 25 FS Temperature influence 20 of basic error 10 C Integrat...

Страница 9: ...T 6651 2009 100M 0 00428 180 200 0 25 0 1 C GOST 6651 2009 500M 0 00428 180 200 0 25 0 1 C GOST 6651 2009 1000M 0 00428 180 200 0 25 0 1 C GOST 6651 2009 Ni100 0 00617 60 180 0 25 0 1 C GOST 6651 2009...

Страница 10: ...g environment conditions must be observed clean dry and controlled environment low dust level closed non hazardous areas free of corrosive or flammable gases Table 3 3 Operating conditions Condition P...

Страница 11: ...the device is powered over USB the inputs outputs and the Ethernet interfaces are disabled If you need full control over the device you have to connect the main power but you must observe the followin...

Страница 12: ...00 To set the time click the toolbar icon Real time clock Fig 4 1 Use the button Synchronize with PC to synchronize the RTC with the PC clock Select your time zone from the drop down list below You ca...

Страница 13: ...ule processor at least 2 minutes Since the number of erase cycles of the flash memory is limited it is not recommended to record the configuration parameters cyclically when the battery is low 4 4 Eth...

Страница 14: ...if any have been changed are assigned to this module The address is automatically incremented by 1 for each subsequent device Only Ethernet parameters will be changed other parameters will not be aff...

Страница 15: ...described in Tab 4 5 To view all logged parameters use the toolbar item Device information in akYtecToolPro The archive can be read with via Modbus TCP using function 20 Tab D 3 This function allows r...

Страница 16: ...2 R AIn timestamp Timestamp of input AIn as INT16 Sect 4 8 5 0 65535 s 100 R AIn INT Measured value of input AIn as INT16 Sect 4 8 5 32768 32767 R 4 8 1 Input sampling As long as the Input signal para...

Страница 17: ...n working in conditions of strong interferences it is recommended to decrease the bandwidth to eliminate their influence on the operation of the module 2 At the second stage of filtering the signal is...

Страница 18: ...ond the permissible range RTD or TC sensor break RTD short circuit Cold junction temperature is beyond the range 40 90 Some transmitter errors cannot be detected Current and voltage sensor breaks The...

Страница 19: ...age broker and a number of clients Broker is a server that receives all messages from the clients and then routes the messages to the appropriate des tination clients Client can be publisher or and su...

Страница 20: ...for broker 0 65535 1883 RW Store last message If On other clients subscribed to the module s topics will receive the latest messages from these topics On Off Off RW Publishing interval Publishing inte...

Страница 21: ...rotocol without GET requests it is recommended to set the pa rameter Safe state timeout Modbus Slave group to 0 since writing is usually event driven and not cyclic in this case Table 4 11 SNMP parame...

Страница 22: ...the power supply of the module and all connect ed devices open the front cover 1 loosen the two screws 3 remove the terminal block 2 Now you can replace the device Reverse this procedure after replac...

Страница 23: ...ble quick and easy replacement of the device see Fig 5 2 When wiring is completed the wires should be placed in a special recess under the cover so that adjacent devices can be placed on the DIN rail...

Страница 24: ...als AIn 1 of all inputs have the same electric potential Fig 5 5 TC wiring To connect a remote thermocouple to the input use thermocouple compensating cable About using of cold junction compensation C...

Страница 25: ...2 5 Switch contact Two discrete dry contact signals can be connected to each analog input switches buttons relay contacts etc Any resistors in the range 200 3000 can be used as shunt resistors Both r...

Страница 26: ...o seal the unused connector with a rubber plug included Star topology The maximum length of the network lines between modules is 100 m Both Ethernet connectors can be used Fig 5 11 Star topology Chain...

Страница 27: ...the factory settings all parameters but Ethernet will be reset to default values and the password deleted The Ethernet parameters will not be affected To restore the factory settings Power on the devi...

Страница 28: ...power before maintenance The maintenance includes cleaning the case and terminal blocks from dust dirt and debris checking the device fastening checking the wiring connecting wires terminal connection...

Страница 29: ...otection If the device is not taken immediately after delivery into operation it must be carefully stored at a protected location The device should not be stored in an atmosphere with chemically activ...

Страница 30: ...kYtec GmbH Vahrenwalder Str 269 A 30179 Hannover Germany Tel 49 0 511 16 59 672 0 www akytec de 29 9 Scope of delivery MV210 101 1 Ethernet connection cable 1 2 pole plug in terminal block 1 Rubber pl...

Страница 31: ...pendix A Dimensions akYtec GmbH Vahrenwalder Str 269 A 30179 Hannover Germany Tel 49 0 511 16 59 672 0 www akytec de 30 Appendix A Dimensions Fig A 1 External dimensions Fig A 2 Wall mounting dimensio...

Страница 32: ...69 A 30179 Hannover Germany Tel 49 0 511 16 59 672 0 www akytec de 31 Appendix B Galvanic isolation Fig B 1 Galvanic isolation The test voltages shown in Fig B 1 correspond to the tests carried out un...

Страница 33: ...he module and all connected devices remove the terminal blocks without disconnecting the connected wires Fig 5 2 remove the module from the DIN rail remove the front part of the case by opening the fo...

Страница 34: ...form name R 0xF020 61472 String32 Platform version R 0xF030 61488 String32 Hardware version R 0xF040 61504 String16 Additional text information R 0xF048 61512 String16 S N R 0xF084 61572 String32 MAC...

Страница 35: ...0x101A 4122 REAL32 AI2 Upper measuring limit 10000 10000 RW 0x101C 4124 REAL32 AI2 Lower measuring limit 10000 10000 RW 0x101E 4126 REAL32 AI2 Filter time constant 0 65535 s RW 0x1020 4128 UINT16 AI2...

Страница 36: ...RW 0x1068 4200 REAL32 AI7 Curve slope 1 10 RW 0x106A 4202 REAL32 AI7 Upper measuring limit 10000 10000 RW 0x106C 4204 REAL32 AI7 Lower measuring limit 10000 10000 RW 0x106E 4206 REAL32 AI7 Filter tim...

Страница 37: ...able 0 off 1 on RW 0x1600 5632 UINT16 NTP server pool RW 0x1601 5633 String32 NTP server 1 RW 0x1641 5697 UINT32 NTP server 2 RW 0x1643 5699 UINT32 Synchronization period 5 65535 s RW 0x1645 5701 UINT...

Страница 38: ...4 Modbus error codes Code Name Description 01 Illegal Function Function code received in the query is not recognized or allowed by slave 02 Illegal Data Address Data address of some or all the require...

Страница 39: ...nonexistent 03 Failed to move to the desired offset in the file 04 Error while deleting file on delete request Too much data requested more than 250 bytes Invalid record number greater than 0x270F Inv...

Отзывы: