![Akytec MV210-101 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/akytec/mv210-101/mv210-101_user-manual_2887631023.webp)
Installation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
22
5.2.1 General information
Power supply terminals and Ethernet interfaces are placed on the top of the device (Fig. 2.3. Pos.1). Mating
plug for the power supply is included.
Terminal assignments are given in Fig. 5.3 and Tab. 5.1.
Electrical connections for inputs and outputs are given in Fig. 5.4…5.10.
Maximum conductor cross-section is 1.0 mm².
Plug-in terminal block for power supply and removable terminal block for I/O connections enable quick and
easy replacement of the device (see Fig. 5.2).
When wiring is completed, the wires should be placed in a special recess under the cover so that adjacent
devices can be placed on the DIN rail close to each other.
Fig. 5.3 Front view (open cover)
Table 5.1 Terminal assignments
Marking
Description
AI1-1…AI8-1
Input terminals 1 (-)
AI1-2…AI8-2
Input terminals 2 (+)
AI-R
Common terminals R (internally connected)
5.2.2 Analog inputs
Table 5.2 Sensor line requirements
Sensor type
Line length
m
Line resistance, max.
Ω
Line design
RTD
100
15
Three-wire cable, wires of equal length and
cross-section
TC
20
100
Thermocouple (compensating) cable
Current signal
100
100
Two-wire cable
Voltage signal
100
50
Two-wire cable
Resistance signal
10
5
Two-wire cable