26
12.- Parameters
The programming menu allows adjusting the unit's parameters to the installation's
needs.
Press the
SET
key for 5 seconds to access the programming menu. If the access
code is activated, a 2 digit code is requested (See page 24), if it is not correct the unit
will not enter programming.
The parameters are grouped by functions in 12 separate menus, to access a given menu, select it using the browser and
press
SET
.
The
Def.
column indicates the default parameters.
Temperature values are expressed in
ºC
(equivalent temperature in ºF).
12.- Parameters
The programming menu allows adjusting the unit's parameters to the installation's
needs.
Press the
SET
key for 5 seconds to access the programming menu. If the access
code is activated, a 2 digit code is requested (See page 24), if it is not correct the unit
will not enter programming.
The parameters are grouped by functions in 12 separate menus, to access a given menu, select it using the browser and
press
SET
.
The
Def.
column indicates the default parameters.
Temperature values are expressed in
ºC
(equivalent temperature in ºF).
Description
Page
Units
Min
Def
Max.
Set Point
10
(ºC/ºF)
–40
0.0
320
Sensor 1 differential
13
(ºC/ºF)
0.1
1.0
20.0
Calibration of probe 1
10
(ºC/ºF)
–20.0
0.0
20.0
Set point upper limit (it cannot be set above this value)
14
(ºC/ºF)
B.I.
99.9
320
Set point lower limit (it cannot be set below this value)
14
(ºC/ºF)
–40.0
–40.0
B.S.
Compressor protection
OFF/ON
(From the last disconnection)
ON
(to the connection)
14
OFF/ON
Protection delay time
14
(min.)
0
0
255
Compressor ON fault s1
(If it is 0, it will always be stopped)
14
(min.)
0
10
255
Compressor OFF fault s1
(If it is 0, it will always be running)
14
(min.)
0
5
255
Stop when opening door?
(It requires a digital input configured as door contact)
14
No
Description
Page
Units
Min
Def
Max.
Defrost type:
Electrical heater
Reverse cycle
15
Res
Defrost count:
Frequency
Compressor sum
Real time clock
16
Fre.
Defrost frequency (Time between two starts)
16
(h.)
0
6
120
Defrost duration
16
(min.)
0
30
255
Defrost message:
Current temperature
Defrost Start temperat
DEFROST message
16
DEF
Message duration (Time added at the end of the defrost)
16
(min.)
0
5
255
Defrost final temperature
16
(ºC/ºF)
–40.0
8.0
99.9
REFRIGERATION control (Compressor)
DEFROST control