8.- Operation
8.1.- Compressor control
NORMAL OPERATION
CONTROL BY THERMOSTAT
Temperature is controlled by an external thermostat instead of probe 1, and to do so one of the digital inputs must be
configured as "Thermostat control".
This configuration cancels the probe inputs, and therefore temperatures will not be displayed nor will the functions
associated with them be carried out (temperature, alarms, HACCP logging, etc.).
CONTINUOUS CYCLE MODE
Use this function to cool the cold rooms before loading products.
It is activate pressing the
O
key for 5 seconds, the display shows the
%
icon while this mode is active.
ENERGY SAVING MODE
It allows energy saving in the periods of low activity of the cold room, and in this way reduces the installation's
electricity consumption. The display will show the
Z
icon when this mode is active.
It is activated using time programming, using the
Energy saving start
parameter on the
u
menu with the options:
Ÿ
Day:
Defines the days this mode will be activated on;
ž
Deact.: It will never be activated.
ž
Monday/Tuesday/Wednesday/Thurdsay/Friday/Saturday/Sunday: It will only activate on the chosen day.
ž
Mon-Sun: It will activate everyday (from Monday to Sunday).
ž
Mon-Sat: It will activate everyday except Sunday.
ž
Mon-Fri: It will activate everyday except Saturday and Sunday.
ž
Sat-Sun: It will only activate on Saturday and Sunday.
Ÿ
Hour:
It times the energy saving mode start hour.
Ÿ
Minute:
It times the energy saving mode start minute.
ON
SP
SP+Dif.
OFF
COMP.
ºC
When the temperature in probe 1 reaches the set
point value (SP) plus the probe's differential, the
compressor activates and makes the temperature
drop. When the set point value (SP) is reached, the
compressor stops.
When this mode is activated, the compressor starts
to operate continuously and without taking the set
point into account, until the time configured in the
Continuous cycle duration
parameter passes, or
until the
O
key is pressed again for 5 seconds.
The unit will immediately return to normal operation.
ON
SP
Continuous
Cycle Duration
SP+C1
OFF
COMP.
ºC
8.- Operation
8.1.- Compressor control
NORMAL OPERATION
CONTROL BY THERMOSTAT
Temperature is controlled by an external thermostat instead of probe 1, and to do so one of the digital inputs must be
configured as "Thermostat control".
This configuration cancels the probe inputs, and therefore temperatures will not be displayed nor will the functions
associated with them be carried out (temperature, alarms, HACCP logging, etc.).
CONTINUOUS CYCLE MODE
Use this function to cool the cold rooms before loading products.
It is activate pressing the
O
key for 5 seconds, the display shows the
%
icon while this mode is active.
ENERGY SAVING MODE
It allows energy saving in the periods of low activity of the cold room, and in this way reduces the installation's
electricity consumption. The display will show the
Z
icon when this mode is active.
It is activated using time programming, using the
Energy saving start
parameter on the
u
menu with the options:
Ÿ
Day:
Defines the days this mode will be activated on;
ž
Deact.: It will never be activated.
ž
Monday/Tuesday/Wednesday/Thurdsay/Friday/Saturday/Sunday: It will only activate on the chosen day.
ž
Mon-Sun: It will activate everyday (from Monday to Sunday).
ž
Mon-Sat: It will activate everyday except Sunday.
ž
Mon-Fri: It will activate everyday except Saturday and Sunday.
ž
Sat-Sun: It will only activate on Saturday and Sunday.
Ÿ
Hour:
It times the energy saving mode start hour.
Ÿ
Minute:
It times the energy saving mode start minute.
When the temperature in probe 1 reaches the set
point value (SP) plus the probe's differential, the
compressor activates and makes the temperature
drop. When the set point value (SP) is reached, the
compressor stops.
8.- Operation
8.1.- Compressor control
NORMAL OPERATION
CONTROL BY THERMOSTAT
Temperature is controlled by an external thermostat instead of probe 1, and to do so one of the digital inputs must be
configured as "Thermostat control".
This configuration cancels the probe inputs, and therefore temperatures will not be displayed nor will the functions
associated with them be carried out (temperature, alarms, HACCP logging, etc.).
CONTINUOUS CYCLE MODE
Use this function to cool the cold rooms before loading products.
It is activate pressing the
O
key for 5 seconds, the display shows the
%
icon while this mode is active.
ENERGY SAVING MODE
It allows energy saving in the periods of low activity of the cold room, and in this way reduces the installation's
electricity consumption. The display will show the
Z
icon when this mode is active.
It is activated using time programming, using the
Energy saving start
parameter on the
u
menu with the options:
Ÿ
Day:
Defines the days this mode will be activated on;
ž
Deact.: It will never be activated.
ž
Monday/Tuesday/Wednesday/Thurdsay/Friday/Saturday/Sunday: It will only activate on the chosen day.
ž
Mon-Sun: It will activate everyday (from Monday to Sunday).
ž
Mon-Sat: It will activate everyday except Sunday.
ž
Mon-Fri: It will activate everyday except Saturday and Sunday.
ž
Sat-Sun: It will only activate on Saturday and Sunday.
Ÿ
Hour:
It times the energy saving mode start hour.
Ÿ
Minute:
It times the energy saving mode start minute.
When this mode is activated, the compressor starts
to operate continuously and without taking the set
point into account, until the time configured in the
Continuous cycle duration
parameter passes, or
until the
O
key is pressed again for 5 seconds.
The unit will immediately return to normal operation.
ON
SP2
(SP2)+Dif.
OFF
COOL
ºC
Operation is the same as in the normal ode, but
increasing the set point the amount of degrees
defined in the
Set point energy saving
parameter.
(SP2= Set point during energy saving)
8.- Operation
8.1.- Compressor control
NORMAL OPERATION
CONTROL BY THERMOSTAT
Temperature is controlled by an external thermostat instead of probe 1, and to do so one of the digital inputs must be
configured as "Thermostat control".
This configuration cancels the probe inputs, and therefore temperatures will not be displayed nor will the functions
associated with them be carried out (temperature, alarms, HACCP logging, etc.).
CONTINUOUS CYCLE MODE
Use this function to cool the cold rooms before loading products.
It is activate pressing the
O
key for 5 seconds, the display shows the
%
icon while this mode is active.
ENERGY SAVING MODE
It allows energy saving in the periods of low activity of the cold room, and in this way reduces the installation's
electricity consumption. The display will show the
Z
icon when this mode is active.
It is activated using time programming, using the
Energy saving start
parameter on the
u
menu with the options:
Ÿ
Day:
Defines the days this mode will be activated on;
ž
Deact.: It will never be activated.
ž
Monday/Tuesday/Wednesday/Thurdsay/Friday/Saturday/Sunday: It will only activate on the chosen day.
ž
Mon-Sun: It will activate everyday (from Monday to Sunday).
ž
Mon-Sat: It will activate everyday except Sunday.
ž
Mon-Fri: It will activate everyday except Saturday and Sunday.
ž
Sat-Sun: It will only activate on Saturday and Sunday.
Ÿ
Hour:
It times the energy saving mode start hour.
Ÿ
Minute:
It times the energy saving mode start minute.
Operation is the same as in the normal ode, but
increasing the set point the amount of degrees
defined in the
Set point energy saving
parameter.