14
The
Set point energy saving
parameter defines what the set point will be when this mode is active and
the
Energy saving duration
parameter defines the duration of this mode in hours. It never activates if it is configured
at 0.
This mode may optionally be activated and deactivated whenever you want using the external button connected to one
of the digital inputs, and to do so the corresponding input should be configured as "Remote energy saving”.
COMPRESSOR PROTECTION DELAY
This protects the compressor, preventing continuous stops and start-ups in certain exceptional cases.
The
Comrpessor Protection
parameter allows choosing between 2 types of delay:
OFF-ON:
Minimum time the compressor should stay stopped before each start-up.
ON:
Minimum time the compressor should stay operating before each start-up.
The
Protection delay time
parameter defines the time of the previous parameter.
OPERATION IN THE EVENT OF A FAULT IN PROBE 1
If probe 1 fails (failure, disconnection, etc. ), the compressor operates according to times programmed in the following
parameters:
Compressor ON fault s1:
Time of the compressor operating in the event of a fault in probe 1.
Compressor OFF fault s1:
Time of the compressor stopped in the event of a fault in probe 1.
SET POINT LOCKINGS
Using the
Set Point upper limit
and
Set Point lower limit
parameters, it is possible to set a top and bottom limit for
the
Set point (SP)
parameter, which prevents being able to set a set point that is too low or too high that might
damage the installation or the stored product.
STOP COMPRESSOR WHEN THE DOOR IS OPENED
This defines if the compressor will be stopped whenever the cold room's door is opened. To do so, one of the digital
inputs should be configured as "door contact" (See page 22).
If the door stays open longer than the value programmed in the
Inact. with door open
parameter, the compressor will
return to normal operation (See page 22).
ON
Fault in Probe 1
COMP.
OFF
COMP.
OFF
COMP.
ON
COMP.
ON
OFF
COMP.
Time
ON
ON
ON
OFF-ON
SP
SP
SP+Dif.
SP+Dif.
Delay time
Delay time
OFF
OFF
COMP.
COMP.
Time
Time