Immediately set the 3-way valve to the closed position. 

 

Do this quickly so that the gauge ends up indicating 3 to 5kg/cm

2

.g. 

 

Disconnect the charge set, and amount the 2-way and 3-way valve’s caps and the service port cap. 

 

Use torque wrench to tighten the service port cap to a torque of 1.8 kg.m. 

 

Be sure to check for gas leakage. 

 

3.  RE-AIR PURGING FOR RE-INSTALLATION 

 

Confirm that both the 2-way valve and the 3-way valve are set to the closed position. 

 

Connect the charge set and a gas cylinder to the service port of the 3-way valve. 

 

Leave the valve on the gas cylinder closed. 

 

Air purging 

 

Open the valves on the gas cylinder and the charge set. Purge the air by loosening the flare 

nut  on  the  2-way  valve  approximately 

45

°

for 

3  seconds

,  then  closing  it  for 

1  minute

Repeat

 3 

times. 

 

After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve. 

 

 

Все каталоги и инструкции здесь:

 http

:

//splitoff.ru/tehn-doc.html

Содержание AC-S10HKX2

Страница 1: ...Air Conditional Service Manual Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...

Страница 2: ...2 Model No AC S10HKX2 Version 1 0 2 Model AC S10HKX2 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 3: ...IFICATIONS 4 FEATURES 5 OPERATING RANGE 7 PERFORMANCE CURVES 8 REMOTE CONTROLLER 11 OPERATION DETAILS 14 INSTALLATION 25 2 WAY 3 WAY VALVE 37 EXPLODED VIEW PART LIST 46 WIRING DIAGRAM 50 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 4: ... Air circulation m3 h A B 420 420 High A B 33 33 Indoor unit Low A B 27 27 Noise level dB A Outdoor unit 61 Unit A Rotary PH160X1C Compressor type Unit B Rotary PH160X1C Other 24 Hours timer Yes Smart function Yes Jet function Yes Auto restart Yes 3 Speed control Yes Horizon Yes Auto swing louver Vertical No Suitable area m2 14 20 14 20 Outdoor IP class IP 4 Gas 3 8 A B Connect diameter inch liqui...

Страница 5: ... hours in HEATING AUTO FAN The appliance automatically selects the indoor fan speed in accordance to the room temperature At the start the appliance operates at high fan speed As the room temperature gets closer to the set temperature the fan switches to a lower speed for quieter operation FAN SPEED HIGH MEDIUM LOW 1 The appliance can set at different indoor fan motor speed by pressing the FAN SPE...

Страница 6: ... supply restores after its failure the machine will start to work automatically with the previous setting parameters SUPER Strong cooling when you just come into your room and want to cool the room as soon as possible Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 7: ... the heat pump ranges from 7 to 43 The rated cooling operation test condition is as following Indoor DB WB temperature 27 19 Outdoor DB WB temperature 35 24 The rated heating operation test condition is as following Indoor DB WB temperature 20 Max 15 Outdoor DB WB temperature 7 6 2 REFRIGERANT PIPING The maximum length of the connecting refrigerant piping between indoor unit and outdoor unit is 15...

Страница 8: ...TION PRESSURE VS TEMPERATURE CHART COOLING OPERATION OUTDOOR INTAKE AIR TEMP 75 2 24 66 2 19 INDOOR WB F PSI INDOOR DB 80 6 60 65 70 75 80 85 90 95 100 105 110 115 F DB SUCTION PRESSURE 95 90 F æ æ Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 9: ...9 Model No AC S10HKX2 Version 1 0 COOLING UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 10: ...et air temp of indoor unit æ 30 31 32 33 34 35 36 37 38 39 40 11 12 13 14 80 90 100 110 100 110 90 Outdoor air temp æ Cooling capacity Power input Outlet air temp of indoor unit æ Indoor air temp 27 æ Indoor humidity 47 RH Indoor fan speed Hi COOLING OPERATION Indoor air temp 2 æ Indoor fan speed Hi HEATING OPERATION Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 11: ...11 Model No AC S10HKX2 Version 1 0 REMOTE CONTROLLER The remote controller transmits signals to the system 9 5 3 8 4 2 7 6 1 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 12: ...mode HEATING mode 3 FAN SPEED BUTTON Used to select the indoor fan motor speed Automatic fan speed High fan speed Medium fan speed Low fan speed 4 TEMPERATURE SETTING BUTTON Used to adjust the preset room temperature Used to adjust time in TIMER mode 5 SWING BUTTON Press to adjust airflow direction 6 SMART BUTTON Used to enter fuzzy logic operation directly regardless of the unit is on or off Все ...

Страница 13: ...SUPER BUTTON Used to start or stop the fast cooling Fast cooling operates at high fan speed with 18 setting temperature automatically Indication symbols on LCD Signal transmit Smart indicator Dry indicator Fan only indicator Sleep indicator Heating indicator Cooling indicator Super indicator High fan speed Medium fan speed Low fan speed Auto fan speed Все каталоги и инструкции здесь http splitoff ...

Страница 14: ...w 1 during COOLING or DRY operation for 3 minutes the compressor and outdoor fan motor turn OFF with buzzer 3 beeps When the indoor pipe temperature recovers to 5 and the compressor has been off for 3 minutes the compressor and outdoor fan motor will be turned ON Overheating protection system When overloading occurs during the heating operation this system controls the outdoor fan motor and compre...

Страница 15: ...es at 0 The louver swings from 25 to 65 with an automatic setting point of 45 during COOLING operation The louver swings from 10 to 30 with an automatic setting point of 30 during DRY operation The louver swings from 45 to 98 with an automatic setting point of 85 during HEATING operation The louver swings from 45 to 98 with an automatic setting point of 85 during FAN only operation 3 COOLING MODE ...

Страница 16: ...ure plus 1 The compressor OFF when temperature is the setting temperature minus 1 The setting temperature can only be adjusted by 2 up and down When the appliance operates at DRY mode the indoor motor speed is LOW ROOM TEMP SET TEMP 1 æ COMP ON SET TEMP 1 æ COMP OFF Indoor fan motor speed Compressor Outdoor fan motor set speed low speed set speed low speed set speed ON OFF ON OFF ON ON OFF ON OFF ...

Страница 17: ...D AIR PREVENTIVE SYSTEM ONLY AVAILABLE FOR HEAT PUMP This system is intended to prevent cold air from being discharged during HEATING operation The indoor fan motor speed will be controlled as following Set Temp 1C COMP ON The indoor fan motor is controlled by Cold Air Preventive System Set Temp 1C COMP OFF Room Temp Compressor Indoor fan motor speed ON OFF set speed OFF ON set speed More than 3 m...

Страница 18: ...rt Over 26 21 26 Below 21 Preset temperature 26 Intake air temperature at operation start 22 Operation mode COOLING DRY HEATING The initial mode will be continued and independent upon the room temperature changing If initial mode is selected that mode is continued independent upon the temperature changing The indoor fan motor speed is automatically determined by Auto Fan Speed If you are not satis...

Страница 19: ...re falls Set temp 1 æ Intake air temp Set temp Set temp 2 æ High Medium Indoor fan motor speed Set temp 1 æ Medium Low Indoor pipe temperature rises Indoor pipe temperature rises Indoor pipe temperature falls Medium Low Indoor fan motor speed Intake air temp Set temp 2 æ Set temp Intake air temp Set temp 1 æ Set temp 3 æ Low High High Medium Indoor fan motor speed Все каталоги и инструкции здесь h...

Страница 20: ...tic OK OK OK N A Cold Air Preventive OK OK OK OK DRY N A N A OK N A FAN ONLY OK OK OK N A 10 EMERGENT START If you lose the remote controller or the remote controller defected you can also operate the appliance by pressing the EMERGENT BUTTON on the indoor unit for an emergent start The operation mode is SMART if an emergent start is presented when the appliance is connected to the power at first ...

Страница 21: ...ation firstly the compressor and the outdoor fan motor are turned OFF 59 seconds later the reversing valve is turned OFF 60 seconds later the compressor is turned ON The maximum defrost time is 10 minutes In the end of defrosting the compressor is turned OFF 59 seconds later the reversing valve is turned ON 60 seconds later the compressor and outdoor fan motor are turned ON and starting HEATING op...

Страница 22: ...e is in STANDBY and it will be switched ON when the preset time is achieved Pressing TIMER button once the last setting time display on the LCD of remote controller You can adjust the setting time by pressing the TEMPERATURE SETTING BUTTON Pressing the TIMER button again the timer mode is selected and the yellow LED indicator on the indoor unit lights up The TIMER mode can be cancelled by pressing...

Страница 23: ...n with SLEEP mode the operation diagram is as following The setting temperature will be raised by 0 5 per hour in the first two hours after the starting The operation will stop after 8 hours When selecting HEATING operation with SLEEP mode the setting temperature will be decreased by 3 during successive 3 hours later The operation will stop in 8 hours The operation diagram is as following Set temp...

Страница 24: ...fan motor Principal and subordinate Defrost mode If two units A and B are all in heating mode when one unit comes into defrost then the other unit is forced to come into cooling mode with the reverse valve OFF That is to say when one unit comes into defrost mode the outdoor fan motor will stop and the two reverse valves will be in OFF mode From the time the outdoor unit begin to operate the outdoo...

Страница 25: ...paces from the wall ceiling fence or other obstacles Outdoor unit If an awning is built over the unit to prevent direct sunlight or rain exposure be careful that heat radiation from the condenser is not restricted There should not be any animals or plants which could be affected by air discharged Ensure the spaces from the wall ceiling fence or other obstacles A place where noise does not annoy yo...

Страница 26: ...pipes and the cable Use the accessory piping kit or the pipes purchased locally Measure the distance between the indoor and the outdoor units Cut the pipes a little longer than measured distance Cut the cable a 1 5m longer than the pipe length Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 27: ...27 Model No AC S10HKX2 Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 28: ...emoved from the indoor unit as some gas is charged to prevent the inside of the pipe from rusting Fit the copper pipe end into the bar of flare tool about 0 0 5mm higher Flare the pipe ends 4 Tape the flaring portion to protect it from the dust or damages Indoor unit installation Hook the indoor unit onto the upper portion of installation plate Engage the two hooks of the rear top of the indoor un...

Страница 29: ...que wrench ensure the direction for tightening follows the arrows on the wrench Pipe Size Torque Liquid Side φ6 or 1 4 inch 1 8 kg m Liquid Side φ10 or 3 8 inch 3 5 kg m Liquid Side φ12 or 1 2 inch 5 5 kg m Gas Side φ10 or 3 8 inch 3 5 kg m Gas Side φ12 or 1 2 inch 5 5 kg m Gas Side φ16 or 5 8 inch 7 5 kg m Gas Side φ19 or 3 4 inch 10 0 kg m Wrap the insulation material around the connecting porti...

Страница 30: ... the center of the piping and sufficiently tighten the flare nut with fingers Finally tighten the flare nut with torque wrench until the wrench clicks When tightening the flare nut with torque wrench ensure the direction for tightening follows the arrows on the wrench Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 31: ...TING AND INSTALLATION INSTRUCTIONS MANUAL 5 CHECKING THE DRAINAGE AND CONNECTING THE CABLE TO INDOOR UNIT Checking the drainage 1 Remove the grille from the cabinet Set the up and down air direction louver to open position horizontally by finger pressure Remove the screw caps and the securing screws To remove the grille pull the lower left and right side of the grille toward you slightly titled an...

Страница 32: ...ou may connect an additional drainage hose the end of the drainage outlet should keep distance from the ground Do not dip it into water and fix it on the wall to avoid swinging in the wind In case of the outdoor unit is installed below position of the indoor unit Tape the piping drainage hose and connecting cable from down to up Form the piping gathered by taping along the exterior wall and fix it...

Страница 33: ... equivalent Connecting the cable to the indoor unit as shown in the OPERATING AND INSTALLATION INSTRUCTIONS MANUAL 6 AIR PURING OF THE PIPINGS AND INDOOR UNIT Air purging preparation Remove the caps from the 2 way and 3 way valves Remove the service port cap from the 3 way valve To open the valve turn the valve spindle of 2 way valve counter clockwise approximate 90 and hold it there for 5 seconds...

Страница 34: ... If there is no leakage found open 2 way again turn the valve spindle counter clockwise until it stops If there is leakage found re tighten the connecting portion with wrench If the leakage persists locate a leakage and repair it until leakage ceases Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 35: ...ort of 3 way valve Measure the pressure Keep it for 5 10 minutes Ensure if the pressure indicated on the gauge is as same as that of measured at the first time No leakage found Leakage found Open 2 way valve again turn the valve spindle counter clockwise until it stops Re tighten the connecting portion with wrench Leakage ceases Leakage persists Locate a repair leak Purge the air push the pin on t...

Страница 36: ... piping The additional gas for air purging has been charged in the outdoor unit However if the flare connections have not been done correctly and gas leaks a gas cylinder and the charge set will be needed Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 37: ...e Open push pin Operation Open with valve cap Open with valve cap Closed with cap Pumping down Transferring Closed clockwise Open counter clockwise Open connected manifold gauge Evacuation Servicing Open Open Open with charging cylinder Gas charging Servicing Open Open Open with charging cylinder Pressure check Servicing Open Open Open with charging cylinder Gas releasing Servicing Open Open Open ...

Страница 38: ... gas cylinder and the charge set will be needed The air in the indoor unit and in the piping must be purged If air remains in the refrigerant pipes it will affect the compressor reduce the cooling and heating capacity and could lead to a malfunction Be sure to use a torque wrench to tighten the service port cap after using the service port so that it prevents the gas leakage from the refrigeration...

Страница 39: ...eat this three times Use torque wrench to tighten the service port cap to a torque of 1 8kg cm Set the 3 way valve to the back seat Mount the valve caps to the 2 way and 3 way valves Check for gas leakage At this time especially check for gas leakage from the 2 way and 3 way valve s caps and from the service port cap Caution If gas leakage is discovered take the following measures If the gas leaka...

Страница 40: ...it for 10 15 minutes Stop operation and wait for 3 minutes then connect the charge set to the service port of the3 way valve Connect the charge hose with the push pin to the service port Air purging of the charge hose Open the low pressure valve on the charge set slightly to purge air from the charge hose Set the 2 way valve to the closed position Operate the air conditioner at the cooling cycle a...

Страница 41: ...FOR RE INSTALLATION Confirm that both the 2 way valve and the 3 way valve are set to the closed position Connect the charge set and a gas cylinder to the service port of the 3 way valve Leave the valve on the gas cylinder closed Air purging Open the valves on the gas cylinder and the charge set Purge the air by loosening the flare nut on the 2 way valve approximately 45 for 3 seconds then closing ...

Страница 42: ...wrench to tighten the service port cap to a torque of 1 8kg m Be sure to check for gas leakage Caution Do not leak the gas in the air during air purging 4 BALANCE REFRIGERANT OF THE 2 WAY 3 WAY VALVES GAS LEAKED Confirm that both the 2 way and 3 way valves are set to the back seat Connect the charge set to the 3 way valve s service port Leave the valve on the charge set closed Connect the charge h...

Страница 43: ...t is discharged too suddenly the refrigeration oil will also be discharged 5 EVACUATION ALL AMOUNT OF REFRIGERANT LEAKED Connect the vacuum pump to the charge set s center hose Evacuating for approximately one hour Confirm that the gauge needle has moved toward 76cmHg vacuum of 4 mmHg or less Close the valve Low side on the charge set turn off the vacuum pump and confirm that the gauge needle does...

Страница 44: ...igerant it can be charged with a little at a time approximately 150g each time while operating the air conditioner in the cooling cycle However one time is not sufficient wait approximately 1 minute and then repeat the procedure pumping down pin This is different from previous procedures Because you are charging with liquid refrigerant from the gas side absolutely do not attempt to charge with lar...

Страница 45: ...45 Model No AC S10HKX2 Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 46: ...46 Model No AC S10HKX2 Version 1 0 EXPLODED VIEW AND PART LIST INDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 47: ...flector A 1201133 9 15 Vertical Deflector B 1201134 3 16 Louver Link 1201127 3 17 Louver Motor 1402136 1 18 Draining Pan 210657 1 19 Power Supply Cord N A 20 Cable Clamp N A 21 Receiver PCB Support 1102109 1 22 Display PCB Fixing Panel 1109133 1 23 Terminal Board 3PU 150264 1 24 Ring B 1203179 1 25 Pipe Assembly 13032974 1 26 Ring A 1203178 1 27 Bearing N A 28 Indoor Fan Motor 1402153 1 29 Electri...

Страница 48: ...48 Model No AC S10HKX2 Version 1 0 OUTDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 49: ...r 21093054 1 14 Terminal Board 4P2 15023004 A 1 15 Right Side Cover 8100342 1 16 Cable Fixed Plate 11093016 1 17 Terminal Board 3P 150298 1 18 Electrical Box 8210223 1 19 Outdoor Control PCB 81409132 1 20 Fan Capacitor 14113057 1 21 2 way Valve A 8130916 1 22 2 way Valve B 8130916 1 23 3 way Valve B 8130917 1 24 3 way Valve A 8130917 1 25 Capillary Assembly A 813031151 1 26 Chassis Assembly 810026...

Страница 50: ...50 Model No AC S10HKX2 Version 1 0 WIRING DIAGRAM Indoor Unit Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 51: ...51 Model No AC S10HKX2 Version 1 0 Outdoor Unit Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 52: ...Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...

Отзывы: