Model No: AC-S10HKX2
Version 1.0
Connecting the piping to the indoor unit
Align the center of the piping and sufficiently tighten flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Wrench tightening the flare nut torque wrench, ensure the direction for tightening follows
the arrows on the wrench.
Pipe Size
Torque
Liquid Side(
φ
6 or 1/4 inch)
1.8 kg.m
Liquid Side (
φ
10 or 3/8 inch)
3.5 kg.m
Liquid Side(
φ
12 or 1/2 inch)
5.5 kg.m
Gas Side (
φ
10 or 3/8 inch)
3.5 kg.m
Gas Side(
φ
12 or 1/2 inch)
5.5 kg.m
Gas Side(
φ
16 or 5/8 inch)
7.5 kg.m
Gas Side(
φ
19 or 3/4 inch)
10.0 kg.m
Wrap the insulation material around the connecting portion.