12. DEFROST
The defrost timer (integrating the operation time of compressor)counts time by microprocessor
during HEATING operation.
When the unit has run in heating mode for
50
minutes and when the outdoor pipe temperature
falls to
–8
℃
, the defrosting is started. When the outdoor pipe temperature exceeds
8
℃
or the
defrosting time reaches
10
minutes, the defrosting is ended.
During the defrosting operation, the RUN LED indicator on the indoor unit of the appliance
flickers.
In the defrost operation, firstly the compressor and the outdoor fan motor are turned
OFF
.
59
seconds
later the reversing valve is turned
OFF
.
60 seconds
later the compressor is turned
ON
.
The maximum defrost time is 10 minutes.
In the end of defrosting, the compressor is turned
OFF
,
59
seconds
later the reversing valve is
turned
ON
.
60 seconds
later the compressor and outdoor fan motor are turned
ON
and starting
HEATING operation.
During the defrost operation, the indoor fan motor is controlled by
Cold Air Preventive
System.
The HEATING and defrosting operation is alternated as following.
Switch ON
Heating
Min 50 mins
Heating
Min 50 mins
Heating
Min 50 mins
Defrosting
Max 10 mins
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание AC-S10HKX2
Страница 27: ...27 Model No AC S10HKX2 Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...
Страница 45: ...45 Model No AC S10HKX2 Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...
Страница 48: ...48 Model No AC S10HKX2 Version 1 0 OUTDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...
Страница 51: ...51 Model No AC S10HKX2 Version 1 0 Outdoor Unit Все каталоги и инструкции здесь http splitoff ru tehn doc html ...