terminal is shorted out, [device
name] in [room name]
power supply output is shorted
connection of the wired fire
detector for short circuit.
After the normal state of the
terminals is resumed, you will
receive respective notification
Battery is charging too long
Displayed in integration module
statuses
MultiTransmitter battery
charges for over 40 hours
The battery is most likely
defective. Install another
backup battery
Fire alarms reset
In case of alarms of the fire detectors connected to MultiTransmitter, the window
prompting of the need to reset the alarms is displayed in the Ajax app. This will
make the detectors return to their normal state and continue to respond to a fire.
If the detectors are not reset after the fire alarm, they will not respond to the next fire, as they
will remain in alarm mode.
There are two ways to reset fire detectors:
Technical specifications
Number of alarm/tamper zones
18
Supported detector contact types
NO, NC (without R), EOL (NC with R), EOL (NO
with R)
Resistance of the EOL Resistor
From 1 kΩ to 7.5 kΩ
1. By clicking the button in the notification in the app.
2. Via MultiTransmitter menu: click on the red button opposite the integration
module.