Technical Data Sheet: FireProtect 2 Jeweller
Detection of
dangerous
temperature
Sensitive element
thermistor
High temperature Alarm
at temperatures above
64°C
Rapid temperature rise
Alarm
when the temperature
rises more than 10°C in 1
minute or less
According to the
requirements for
temperature detectors of
A1 class of EN 54-5 and
BS 5446-2 standards.
Additional features
In-built siren
volume 85 dB (at a
distance of 3 meters)
Interconnected fire
detectors alarms
All fire detectors in the
system turn on built-in
sirens if at least one of the
detectors registers an
alarm.
LED indication
green is a power indication
yellow is an indication of
malfunctions
red is an indication of fire
alarms
Button on the front panel of
the detector
In normal mode, when
pressed, it starts the
smoke chamber test.
In the event of an alarm or
malfunction, the pressing
turns off the detector
sound notification.
The interconnected alarm
is activated after no more
than 20 seconds.
Lights up once every 56
seconds.
Lights up when
malfunctions are detected.
For example, in the case of
discharged batteries or
contamination of the
smoke chamber.
Lights up when the
detector detects a fire
alarm.