Fan Delay (s).
Defines the delay time (in seconds) to turn on/off
the fan when there is no demand from the Auxiliary Heater.
Possible values are 0, 45, 60 and 120 seconds.
First Stage Menu
-
First Stage Differential.
Temperature that the system has to
surpass to activate the first stage of auxiliary heat. Values: 1 to 5˚C /
2 to 10˚F in increments of 0.5˚C / 1˚F. By default, 1˚C / 2˚F.
-
First Stage Hysteresis.
Defines the hysteresis for the operation of
the first stage. Values: 1 to 5˚C / 2 to 10˚F in increments of 0.5˚C / 1˚F.
By default, 1˚C / 2˚F.
-
Min. Time Exhausted.
Minimum time that the Heat Pump must be
active before the first stage of auxiliary heat can be activated.
Possible values are 0, 45, 60 and 120 minutes. By default, 45 minutes.
Second Stage Menu
-
Second Stage differential.
Temperature that the system must
surpass to activate the second stage of auxiliary heat. Values: 1 to
5˚C/2 to 10˚F in increments of 0.5˚C/1˚F. By default, 1˚C / 2˚F.
-
Second Stage Hysteresis.
Defines the hysteresis for the operation
of the second stage. Values: 1 to 5˚C / 2 to 10˚F in increments of 0.5˚C
/ 1˚F. By default, 1˚C / 2˚F.
-
Min. Time Exhausted.
Minimum time that the first stage must be
active before the second stage of auxiliary heat can be activated.
Possible values are 0, 45, 60 and 120 minutes. By default, 45 minutes.
−
Away mode settings.
This option configures the following parameters of the
unoccupied user mode and the vacation user mode.
o
Hysteresis.
If the set point temperature is surpassed by the differential
defined, the zone will cease demand. Range: 1 to 3.5˚C / 2 to 7˚F in steps
of 0.5˚C / 1˚F. By default, 3˚C / 6˚F.
o
Override Time.
Sets time that the zone will resume the selected away
mode when the user touches the controller screen during an away period.
Values: 10 to 120 minutes in steps of 10 minutes. By default, 60 minutes.
−
Autochange.
This option allows the user to configure the three values that
define the auto-changeover operation that sets the mode of the indoor unit.
o
Setpoint Differential.
Defines the minimum differential between heating
and cooling set points. Values: 0 to 3.5˚C / 0 to 7˚F in increments of 0.5˚C /
1˚F, by default 1˚C / 2˚F.