Scholar V Installation & Startup Manual 07/2016 New
34
M.
De-humidification is automatic and takes place in cooling only. If, while in the
Cooling Mode, the humidity set-point hasn’t been satisfied by a pre-determined
time (adjustable with password) the compressor is set to run at full speed. If the
compressor shuts off due to the room temperature being 1.5 °F below set point
(adjustable with password) and humidity is not satisfied, maximum cooling is turned
on along with hot gas reheat to keep from overcooling the room.