Scholar V Installation & Startup Manual 07/2016 New
32
F. Check
Room Temp
and
Room RH
to be sure they are reading correctly. Use a good
quality hand-held Temp/RH meter for this check.
Check these values with
a hand-held meter to be
sure they are reading
correctly.
To enter the Change
Set Points mode, press
Set Points
button.
Figure 17. Room Temperature and RH Readout
G. Press
Set Points
button to change HMI screens to the
Set Points
Screen. While
in the
Set Points
screen press and adjust the values shown. When a Set Point is
pressed, another screen will pop up where the numbers can be changed. When
done, just press the arrow key shown.
Press button
to change the
Set Point
Type in the desired
value. Use
ESC
and
BSP
keys
as necessary for
corrections.
Press arrow key to
exit screen
Figure 18. Set Point Selection & Adjustment Screens
H. When the Set Points have been set, go back to the Main screen. Press the desired
mode you want to run. As an example, press
Cooling
to run in the cooling mode.
You should see the word Cooling in the box at the bottom of the screen. This is an
indicator that the cooling mode is running. Whichever mode is operating is shown in
this box.