background image

 

Marvair MPC-10 PDS/Manual, 09/2020 New

 G

eneral

 D

escription

 

The Marvair MPC-10 is an HVAC controller designed to control up to ten air 

conditioners, that can be either single or dual compressor, for equipment enclosures. 

In addition to the control of the air conditioners, the MPC-10 provides alarms 

remotely, through BACnet or Modbus, and locally using a built-in Human Machine 

Interface (HMI). The controller is factory programmed with standard industry set 

points, but can be configured on site or remotely. Settings are retained indefinitely 

in the event of a power loss.

 

Control Up to Ten Air Conditioners in a Shelter

The MPC-10 offers the ability to stage cooling and heating operation for both 

dual and single circuit PLC equipped units. This gives the controller a maximum 

of 20 stages of cooling for dual circuit units, 10 stages of cooling for single 

circuit units, and 10 stages of heating. 

 

Ease of Control and Configuration

The MPC-10 comes standard with a 7-inch color touchscreen HMI which provides 

a user-friendly interface. From the main screen of the HMI the user can see room 

conditions, HVAC status for each unit, and change cooling/heating set points. 

The statuses that can be displayed for each unit are as follows: Cooling, Heating, 

Blower, Fault, Standby, Shutdown, and T-Stat Off. If a fault occurs an alarm 

window will pop-up that displays a description of the alarm, the time/date at 

which it occurred, and the current status of the alarm. Along with the pop-up an 

alarm button will appear which allows the user to minimize/maximize the alarm 

window. The alarms will be maintained until the fault is fixed and the alarm is 

cleared. 
The initial setup of the MPC-10 will be done from the built-in HMI. During this 

process the user will input the number of units, whether the units are dual or 

singe circuit, and the desired communication protocol. Once the initial setup is 

complete all other parameters can be changed, at any time, from the 2nd page of 

the HMI (F2 Button) or remotely. 

Marvair MPC-10 PDS/Manual, 09/2020 New

MANUAL/PRODUCT DATA SHEET

Controller for Up To 10 PLC Based HVAC Systems 

Marvair Part # K/40028-100

Features and Benefits

Programmable Logic Board with 
Lead/Lag Control

• 

Balanced Use of Conditioning Equipment

• 

Sequence the Operation of up to 10 PLC Based Units

• 

Ensures Maximum Efficiency

• 

Independent Economizer Control

• 

Remote Communication (BACnet/Modbus)

Alarms and Lockouts

• 

High Pressure Lockout (Both Circuits If Applicable)

• 

Low Pressure Lockout (Both Circuits If Applicable)

• 

Phase Alarm

• 

Communication Alarm

• 

Emergency Shutdown Alarm

• 

High Shelter Temperature Alarm

• 

Low Shelter Temperature Alarm

Содержание Marvair MPC-10

Страница 1: ...unit are as follows Cooling Heating Blower Fault Standby Shutdown and T Stat Off If a fault occurs an alarm window will pop up that displays a description of the alarm the time date at which it occurr...

Страница 2: ...ash code on the PLC There are two classifications of alarms Unit alarms are specific to the unit These alarms will start with the unit designator followed by the alarm E g Unit 3 Phase Fault Shelter a...

Страница 3: ...gh the wire opening in the base of the MPC 10 3 Mark the placement of the mounting holes 4 Using a drill bit drill holes in the places you have marked for mounting 5 Use screws to mount MPC 10 to wall...

Страница 4: ...o the controller before it is reset to remote communication 2 The logo can be pressed to take the user to a factory information screen 3 The alarm indicator will only be visible if there is an unackno...

Страница 5: ...ch unit The controller can be set up for any number of units between 1 and 10 and will only display the units selected E g If the user selects 5 units then only units 1 5 will be visible The status th...

Страница 6: ...time sec the indoor blower s stay on after a call for cooling is satisfied Range 90 thru 600 f W Fan Purge Time The length of time sec the indoor blower s stay on after a call for heating is satisfied...

Страница 7: ...n Controller Setup Screen 1 Input the number of circuits in the system single or dual circuit units 2 Input which communication protocol is required None BACnet or Modbus 3 Input the number of units t...

Страница 8: ...ain screen will be displayed as shutdown until the button is pressed again to resume functionality WARNING When units are shutdown they will be unavailable to aid in heating or cooling the space Alarm...

Страница 9: ...e refer to the Installation Operation manual for determining if the 3 compressors are rotating correctly Incorrect rotation can damage the compressor and may not be covered by the warranty Checking th...

Страница 10: ...Marvair MPC 10 PDS Manual 09 2020 New 10 MPC 10 Dimensions 20 1 2 Front View 15 1 8 1 1 4 6 RH Side View 7 8 1 3 8 TYP Rear View 1 3 8 2 7 8 1 TYP 1 5 8 TYP Bottom View...

Страница 11: ...ult the Marvair website at www marvair com for the latest product literature Detailed dimensional data is available upon request A complete warranty statement can be found in each product s Installati...

Отзывы: