Marvair MPC-10 PDS/Manual, 09/2020 New

 i

mportant

 s

afety

 p

recautions

 

 WARNING

ALWAYS TURN OFF POWER AT THE MAIN POWER SUPPLY BEFORE INSTALLING, CLEANING, OR 

REMOVING THERMOSTAT.

• 

This controller is for 24 VDC applications only; do not use on voltages over 30 VDC

• 

Do not short across terminals of system control to test operation; this will damage your controller and may void 

your warranty

• 

All wiring must conform to local and national electrical and building codes

• 

Use this controller only as described in this manual

 t

o

 i

nstall

 mpc-10 t

elecom

 c

ontroller

 

 WARNING ELECTRICAL SHOCK HAZARD

TURN OFF POWER AT THE MAIN SERVICE PANEL BY REMOVING THE FUSE OR SWITCHING THE 

APPROPRIATE CIRCUIT BREAKER TO THE OFF POSITION BEFORE REMOVING THE EXISTING 

THERMOSTAT.

IMPORTANT

Marvair MPC-10 installation must conform to local and national building and electrical codes and  

ordinances.

Note: Mount the MPC-10 about five feet above the floor. Do not mount the MPC-10, in direct sunlight, behind a door, 

or in an area affected by a vent or duct. The MPC-10 is designed for interior use only.

1. 

Turn off power to the heating and cooling system by removing the fuse or switching off the appropriate circuit 

breaker.

2. 

Put controller against the wall where you plan to mount it (Be sure wires will feed through the wire opening in 

the base of the MPC-10).

3. 

Mark the placement of the mounting holes.

4. 

Using a drill bit, drill holes in the places you have marked for mounting.

5. 

Use screws to mount MPC-10 to wall.

6. 

Feed wires through the bottom left cable gland.

7. 

Insert stripped, labeled wires in matching wire terminals. See Wiring Diagrams. CAUTION! Be sure exposed portion 

of wires do not touch other wires.

8. 

Gently tug wire to be sure of proper connection. Double check that each wire is connected to the proper terminal. 

9. 

Tighten the cable gland to make a water tight seal.

10. 

Close the cover on the MPC-10.

11. 

Plug in ethernet cables from each unit to the bottom of the MPC-10.

12. 

Turn on power to the system at the main service panel.

13. 

Test MPC-10 operation as described in “Testing the MPC-10”. 

 r

emote

 s

ensor

 i

nstallation

 

1. 

Remove cover from the remote sensor housing

2. 

Select an appropriate location for mounting the remote sensor

3. 

Mount remote sensor unit using hardware provided

4. 

Install 4 wires between remote sensor and MPC-10 (use shielded cable that is adequately grounded)

a. 

Wire 1 should run between an unused DC+ terminal in the controller and +V on the temperature/humidity 

sensor

b. 

Wire 2 should run between an unused DC- terminal in the controller and GND on the temperature/humidity 

sensor

c. 

Wire 3 should run between AI0.1 in the controller and RH on the temperature/humidity sensor

d. 

Wire 4 should run between AI0.0 in the controller and T on the temperature/humidity sensor

Содержание Marvair MPC-10

Страница 1: ...unit are as follows Cooling Heating Blower Fault Standby Shutdown and T Stat Off If a fault occurs an alarm window will pop up that displays a description of the alarm the time date at which it occurr...

Страница 2: ...ash code on the PLC There are two classifications of alarms Unit alarms are specific to the unit These alarms will start with the unit designator followed by the alarm E g Unit 3 Phase Fault Shelter a...

Страница 3: ...gh the wire opening in the base of the MPC 10 3 Mark the placement of the mounting holes 4 Using a drill bit drill holes in the places you have marked for mounting 5 Use screws to mount MPC 10 to wall...

Страница 4: ...o the controller before it is reset to remote communication 2 The logo can be pressed to take the user to a factory information screen 3 The alarm indicator will only be visible if there is an unackno...

Страница 5: ...ch unit The controller can be set up for any number of units between 1 and 10 and will only display the units selected E g If the user selects 5 units then only units 1 5 will be visible The status th...

Страница 6: ...time sec the indoor blower s stay on after a call for cooling is satisfied Range 90 thru 600 f W Fan Purge Time The length of time sec the indoor blower s stay on after a call for heating is satisfied...

Страница 7: ...n Controller Setup Screen 1 Input the number of circuits in the system single or dual circuit units 2 Input which communication protocol is required None BACnet or Modbus 3 Input the number of units t...

Страница 8: ...ain screen will be displayed as shutdown until the button is pressed again to resume functionality WARNING When units are shutdown they will be unavailable to aid in heating or cooling the space Alarm...

Страница 9: ...e refer to the Installation Operation manual for determining if the 3 compressors are rotating correctly Incorrect rotation can damage the compressor and may not be covered by the warranty Checking th...

Страница 10: ...Marvair MPC 10 PDS Manual 09 2020 New 10 MPC 10 Dimensions 20 1 2 Front View 15 1 8 1 1 4 6 RH Side View 7 8 1 3 8 TYP Rear View 1 3 8 2 7 8 1 TYP 1 5 8 TYP Bottom View...

Страница 11: ...ult the Marvair website at www marvair com for the latest product literature Detailed dimensional data is available upon request A complete warranty statement can be found in each product s Installati...

Отзывы: