background image

 

Marvair MPC-10 PDS/Manual, 09/2020 New

time/date that the alarm occurred, and the current status of the alarm. To get rid of the alarm the user must 

fix the problem and acknowledge the alarm using the acknowledge button in the bottom right. To hide this 

screen the user can press the "X" in the top right-hand corner, to return to this screen press the alarm indicator 

shown below in the Alarm Indicator section. The different Status are shown below:

1. 

I - Incoming, the alarm is currently active

2. 

O - Outgoing, the alarm occurred at the time specified but was later fixed

3. 

A - Acknowledged, the alarm has been acknowledged by the user

4. 

IA - Incoming & Acknowledged, the user has acknowledged the alarm however the alarm is still active

 

 

Alarm Indicator 

The alarm indicator will appear in the header of the HMI when there is 

an unacknowledged alarm. The number at the bottom of the indicator 

represents the number of incoming unacknowledged alarms. If the alarm 

indicator shows "0" then there is an outgoing alarm that has not been 

acknowledged. In this scenario the user would need to acknowledge the 

alarm to get rid of the alarm indicator. By pressing the alarm indicator, 

you can open or close the alarm window.

 t

estinG

 

the

 mpc-10 

IMPORTANT

Be sure that the crankcase heater (if used) has been energized for at least 24 hours before 

starting the unit(s). Double-check all electrical connections before applying power. Air 

conditioners with scroll compressors running on 3Ø power must be checked for proper rotation 

during the initial start-up. Please refer to the Installation & Operation manual for determining 

if the 3Ø compressors are rotating correctly. Incorrect rotation can damage the compressor and 

may not be covered by the warranty.

Checking the Cooling Cycle

Procedure:

1. 

On the parameters page (F2) verify that the cooling stage differential is 1ºF and the anti-short cycle is 3 

minutes (default values).

2. 

Make note of the temperature in the room and then press the thermostat button.

3. 

Increase the cooling setpoint above the room temperature and decrease the heating setpoint down to 

35ºF.

4. 

Change the thermostat mode to auto.

5. 

Slowly decrease the cooling setpoint below the room temperature. When the setpoint temperature is 1 

degree below the room temperature the first stage cooling will come on. The lead unit will display cooling 

as the mode on the home screen. Continue decreasing the cooling setpoint until all stages are on (2 

stages per dual circuit unit and 1 stage per single circuit unit).

6. 

To stop cooling, slowly increase the cooling set point to a temperature higher than the room temperature.

Note: The fan purge allows the indoor fan to run for 90 seconds (by default) after the compressor is off. This 

operation provides a small improvement in system rated efficiency.

Checking the Heating Cycle

Procedure: (Applies only to air conditioners with resistance elements)

1. 

From the main screen, increase the heating set point to a setting higher than room temperature. The fan 

will start immediately followed by the electric resistance heater 5 seconds later.

2. 

To test additional units, continue to increase the heating set point until all units are on, in heating mode.

3. 

To stop heating, slowly decrease the heating set point to a temperature lower than room temperature. 

Содержание Marvair MPC-10

Страница 1: ...unit are as follows Cooling Heating Blower Fault Standby Shutdown and T Stat Off If a fault occurs an alarm window will pop up that displays a description of the alarm the time date at which it occurr...

Страница 2: ...ash code on the PLC There are two classifications of alarms Unit alarms are specific to the unit These alarms will start with the unit designator followed by the alarm E g Unit 3 Phase Fault Shelter a...

Страница 3: ...gh the wire opening in the base of the MPC 10 3 Mark the placement of the mounting holes 4 Using a drill bit drill holes in the places you have marked for mounting 5 Use screws to mount MPC 10 to wall...

Страница 4: ...o the controller before it is reset to remote communication 2 The logo can be pressed to take the user to a factory information screen 3 The alarm indicator will only be visible if there is an unackno...

Страница 5: ...ch unit The controller can be set up for any number of units between 1 and 10 and will only display the units selected E g If the user selects 5 units then only units 1 5 will be visible The status th...

Страница 6: ...time sec the indoor blower s stay on after a call for cooling is satisfied Range 90 thru 600 f W Fan Purge Time The length of time sec the indoor blower s stay on after a call for heating is satisfied...

Страница 7: ...n Controller Setup Screen 1 Input the number of circuits in the system single or dual circuit units 2 Input which communication protocol is required None BACnet or Modbus 3 Input the number of units t...

Страница 8: ...ain screen will be displayed as shutdown until the button is pressed again to resume functionality WARNING When units are shutdown they will be unavailable to aid in heating or cooling the space Alarm...

Страница 9: ...e refer to the Installation Operation manual for determining if the 3 compressors are rotating correctly Incorrect rotation can damage the compressor and may not be covered by the warranty Checking th...

Страница 10: ...Marvair MPC 10 PDS Manual 09 2020 New 10 MPC 10 Dimensions 20 1 2 Front View 15 1 8 1 1 4 6 RH Side View 7 8 1 3 8 TYP Rear View 1 3 8 2 7 8 1 TYP 1 5 8 TYP Bottom View...

Страница 11: ...ult the Marvair website at www marvair com for the latest product literature Detailed dimensional data is available upon request A complete warranty statement can be found in each product s Installati...

Отзывы: