background image

Classic HVPA & HVPSA M&S 8.09-1 

15700 - 3 

HVAC Equipment

SECTION 15700

HEATING, VENTILATING AND AIR CONDITIONING EQUIPMENT

The purpose of this manual is to provide instructions for maintenance and service for the  

Marvair

®

 Classic™ series of heat pumps. In addition to this manual, there are other pieces of 

literature available from Marvair. The Product Manual covers the installation of the unit and 

various accessories and the initial start-up of the unit. An overview of the product line can be 

found in the Classic Product Data Sheets. The current version of this literature can be found 

and downloaded from the Marvair website at www.marvair.com.

To minimize sound levels within the classroom, certain options should be selected. These op-

tions are designated by         throughout the guideline.

1.1  GENERAL OPERATION

A.  Classic™ heat pumps are designed to provide quiet comfort to the classroom.

  

In cooling mode, the compressor will cycle on to provide the cooling required.  The 

system provides cooling, dehumidification and air circulation.

  

In heating mode the compressor (heat pump only) will cycle on to provide the 

heating required.  The system provides heating and air circulation.  At lower outdoor 

temperatures, additional heating capacity may be provided by an optional electric 

resistance heater.

  

Ventilation air may be provided by the manual or motorized fresh air vent, power 

vent or GreenWheel

®

 ERV.  These ventilation systems operate when there is a call 

for cooling or heating or independently to provide fresh air. Note that with the 

manual, motorized fresh air vent and the power vent options, if the compressor is 

not operating and the indoor blower is running, unconditioned outside air is being 

introduced into the classroom. The GreenWheel ERV provides tempered outside air.

  

Control systems are either a remote external thermostat, internal thermostat, or a 

direct digital control interfacing with the building automation system (BAS).

  

Hot Gas Reheat (HGR) Dehumidification (Option).  To provide on demand 

dehumidification, the Classic™ heat pump can have a factory installed hot gas reheat 

coil to allow dehumidification through continued cooling with discharge air reheated 

to avoid over cooling the classroom. The operation of the HGR is controlled by a 

three-way heat reclaim valve. The HGR coil is sized to provide a heating capacity 

approximately equal to the sensible capacity of the unit When the demand for 

cooling is satisfied and the humidity controller calls for dehumidification, hot gas is 

directed to a reheat coil downstream from the evaporator coil to add heat to the 

dehumidified, chilled air supplied to the classroom.  Hot gas reheat is available with 

motorized fresh air, PowerVent and GreenWheel

®

 ventilation systems.  

  

Marvair

®

 recommends that for optimum performance, hot gas reheat be used in 

conjunction with the GreenWheel

®

 heat recovery ventilator.  When used with other 

ventilation options, hot gas reheat may not maintain satisfactory control of the 

humidity in the classroom over all outdoor conditions.

Содержание Marvair Classic HVPA24HP

Страница 1: ...rained professional HVAC service person Due to continuous product improvement use only the current issue of this manual The latest version can be downloaded from the Marvair website www marvair com Cl...

Страница 2: ...EAT PUMP TABLE OF CONTENTS Chapter Description Page 1 1 General Description 3 1 2 Model Identification 4 2 1 Start up Instructions 5 2 2 Ventilation System Calibration 7 3 1 Electrical 9 4 1 Maintenan...

Страница 3: ...ion systems operate when there is a call for cooling or heating or independently to provide fresh air Note that with the manual motorized fresh air vent and the power vent options if the compressor is...

Страница 4: ...ering system is shown below The model identification number is on the data label The data label is at the bottom of the of left side panel IMPORTANT WHEN CLASSIC SYSTEMS ARE INSTALLED MODEL NUMBER AND...

Страница 5: ...the thermostats system switch to Cool or Auto position Nothing should operate at this time 4 Set the time delay in the control box to three minutes Note that time delay is an option on some Classic u...

Страница 6: ...e low enthalpy conditions causing the economizer damper to open Alternately when outdoor conditions are lower than the set point a source of heat such as a hair dryer can be directed on the air temper...

Страница 7: ...sure the quantity of the return air from the room Subtract the return air from the supply air The difference is the amount of fresh air c Loosen the set screw that holds the collar onto the rod connec...

Страница 8: ...entage of C A and B must equal 100 Measure the temperature of the indoor return air Multiply the temperature of the indoor air by B d Calculate what the Tmix should be with the desired quantity of out...

Страница 9: ...coil the cabinet and condensate drains should be serviced as described below Also at this time the heat pump should be operated in the cooling and heating cycles as described in Chapter 3 Start Up In...

Страница 10: ...itial field start up of the system Verification of proper rotation is made by observing that the suction pressure drops and the discharge pressure rises when the compressor is energized An alternate m...

Страница 11: ...ssic uses a thermal expansion valve on the indoor cooling circuit and a fixed orifice on the outdoor heating circuit H Reversing Valve The reversing valve reverses the refrigerant s direction of flow...

Страница 12: ...ped with an exhaust fan air speed control which controls the ventilation exhaust blower independently of the fresh air intake blower Demand Control Ventilation A field or factory installed carbon diox...

Страница 13: ...k NO Voltage on Compressor Side of Contactor YES NO Run Capacitor Voltage on Line Side of Contactor Compressor Internal Overload Open NO YES Compressor Winding Open Circuit Breakers or Fuses Open Comp...

Страница 14: ...door Coil Overcharge Inoperative Compressor Valves Inadequate Indoor Air Flow Recirculation of Outdoor Air Outdoor Check Valve Closed Inoperative Indoor Blower Non condensibles Restricted Indoor Meter...

Страница 15: ...Metering Device Restricted Outdoor Metering Device Non condensibles Restricted Filter Drier Restriction in System Wrong Indoor Blower Rotation Reversing Valve Failure Closed Indoor Check Valve Inadeq...

Страница 16: ...ately 6 to 8 from the compressor 4 Compare the suction line temperature to the saturated temperature 5 The difference between saturated temperature and suction line temperature is the superheat Superh...

Страница 17: ...hours for overload to reset If still open replace the compressor Add start kit components 1 2 3 4 Insufficient cooling Improperly sized unit Improper indoor air flow Incorrect refrigerant charge Air n...

Страница 18: ...er refrigerant evacuate and recharge 1 2 Gurgle or pulsing noise at expansion device or liquid line Air or non condensibles in sys tem 1 Recover refrigerant evacuate and recharge 1 Service Analyzer Ch...

Страница 19: ...it wiring Located in supply air stream Differential setting too close Customer mis use Internal foreign matter Power element failure Valve too small Distributor tube tubes restricted Restricted with f...

Страница 20: ...ing 1 Welding scale Nitrogen not used 1 Soldering flux Adding flux before seating copper part way 1 Excess soft solder Wrong solder material 1 Loss of Lubrication Low suction pressure Low charge Refri...

Страница 21: ...charge Remove restriction in liquid line Correct the refrigerant charge Remove non condensible gases Use correct TXV Remove external equalizer line restriction Replace with correct valve Replace power...

Страница 22: ...ng bulb is affected by liq uid refrigerant or refrigerant oil flowing through suction line Unequal refrigerant flow through evaporator circuits Improper superheat adjust ment only possible with TXV ha...

Страница 23: ...r service centers Warranty Policy Information Agreement then fax back to 229 273 5154 Invoices will be paid in accordance with Labor Allowance Guidelines included with this PO Failure to follow these...

Страница 24: ...is covered under this warranty Marvair will honor its warranty and furnish the required replacement part All costs for shipment and risk of loss during shipment of the product to Marvair and back to...

Страница 25: ...Motor Double Shafted 240 Volt ECM 40087 40081 40081 40081 40090 40090 Blower L H 30050 30090 30090 30090 30090 30090 Blower R H 30055 30092 30092 30092 30092 30092 Blower Wheel Housing 9 7T DD 10 8 D...

Страница 26: ...A P 50008 3 0 KVA P 50008 3 0 KVA Contactor Heat 2 Pole 30A 4 to 5 kW 50020 50020 50020 50020 50020 50020 Contactor Heat 3 Pole 40A 6 to 10 kW 50030 50030 50030 50030 50030 50030 Contactor Heat 3 Pole...

Страница 27: ...3 70363 Cable Assembly 01511 01511 01511 01511 Power Cable Assembly 01512 01512 01512 01512 Outdoor Motor 40098 40098 40051 40051 HP RPM 1 3 825 1 3 825 1 2 825 1 2 825 Capacitor Outdoor 50240 50240 5...

Страница 28: ...P 50007 2 0 KVA P 50008 3 0 KVA P 50008 3 0 KVA Contactor Heat 2 Pole 30A 4 to 5 kW 50020 50020 50020 50020 Contactor Heat 3 Pole 40A 6 to 10 kW 50030 50030 50030 50030 Contactor Heat 3 Pole 30A HPC...

Отзывы: