background image

Classic HVPA & HVPSA M&S 8.09-1 

15700 - 9 

HVAC Equipment

3.1  ELECTRICAL

Classic heat pumps and air conditioners are built in a wide variety of configurations and op

-

tions. The illustrations of the control center and the electrical schematics shown here are typical, 
but probably are not identical to your units. Please refer to the electrical schematic in each unit 

for the specific con

struction of that unit.

model selected.  Voltage must be maintained above minimum specified values listed 

below.  Refer to the unit data plate for ampacity requirements.

Table 1.      Voltage Limitations

Electrical Rating Designations*

A

C

D

Nominal Voltage

208/230

208/230

460

Phase

1

3

3

Minimum Voltage

197

197

414

Maximum Voltage

253

253

506

    * Letters refer to model number code designations. 

4.1  MAINTENANCE

Marvair

®

  strongly recommends that the heat pump be serviced a minimum of twice a 

year – once prior to the heating season and once prior to the cooling season.  At this 

time the filters, evaporator coil, condenser coil, the cabinet, and condensate drains 

should be serviced as described below.  Also at this time, the heat pump should be 

operated in the cooling and heating cycles as described in Chapter 3, Start-Up.  In 

addition to this seasonal check-out, the unit should be maintained as follows:

Air Filter

  

Replace the air filter whenever it is visibly dirty.  

Indoor Coil

  

If the coil becomes clogged or dirty, it may be cleaned by careful vacuuming or with 

a commercial evaporator cleaning spray.  DO NOT use a solvent containing bleach, 

acetone, or flammable substances.  Turn power OFF before cleaning.  Be careful 

not to wet any of the electrical components.  Be sure the unit has dried before 

restarting.

Outdoor Coil

  

Periodically inspect the outdoor coil and the cabinet air reliefs for dirt or obstructions.  

Remove  foreign objects such as leaves, paper, etc. 

  

If the coil is dirty, it may be washed off with a commercial solvent intended for 

this purpose.  TURN OFF POWER BEFORE CLEANING!  Be sure that all electrical 

components are thoroughly dry before restoring power.

Cabinet

  

The cabinet may be cleaned with a sponge and warm, soapy water or a mild 

detergent.  Do not use bleach, abrasive chemicals or harmful solvents. 

Содержание Marvair Classic HVPA24HP

Страница 1: ...rained professional HVAC service person Due to continuous product improvement use only the current issue of this manual The latest version can be downloaded from the Marvair website www marvair com Cl...

Страница 2: ...EAT PUMP TABLE OF CONTENTS Chapter Description Page 1 1 General Description 3 1 2 Model Identification 4 2 1 Start up Instructions 5 2 2 Ventilation System Calibration 7 3 1 Electrical 9 4 1 Maintenan...

Страница 3: ...ion systems operate when there is a call for cooling or heating or independently to provide fresh air Note that with the manual motorized fresh air vent and the power vent options if the compressor is...

Страница 4: ...ering system is shown below The model identification number is on the data label The data label is at the bottom of the of left side panel IMPORTANT WHEN CLASSIC SYSTEMS ARE INSTALLED MODEL NUMBER AND...

Страница 5: ...the thermostats system switch to Cool or Auto position Nothing should operate at this time 4 Set the time delay in the control box to three minutes Note that time delay is an option on some Classic u...

Страница 6: ...e low enthalpy conditions causing the economizer damper to open Alternately when outdoor conditions are lower than the set point a source of heat such as a hair dryer can be directed on the air temper...

Страница 7: ...sure the quantity of the return air from the room Subtract the return air from the supply air The difference is the amount of fresh air c Loosen the set screw that holds the collar onto the rod connec...

Страница 8: ...entage of C A and B must equal 100 Measure the temperature of the indoor return air Multiply the temperature of the indoor air by B d Calculate what the Tmix should be with the desired quantity of out...

Страница 9: ...coil the cabinet and condensate drains should be serviced as described below Also at this time the heat pump should be operated in the cooling and heating cycles as described in Chapter 3 Start Up In...

Страница 10: ...itial field start up of the system Verification of proper rotation is made by observing that the suction pressure drops and the discharge pressure rises when the compressor is energized An alternate m...

Страница 11: ...ssic uses a thermal expansion valve on the indoor cooling circuit and a fixed orifice on the outdoor heating circuit H Reversing Valve The reversing valve reverses the refrigerant s direction of flow...

Страница 12: ...ped with an exhaust fan air speed control which controls the ventilation exhaust blower independently of the fresh air intake blower Demand Control Ventilation A field or factory installed carbon diox...

Страница 13: ...k NO Voltage on Compressor Side of Contactor YES NO Run Capacitor Voltage on Line Side of Contactor Compressor Internal Overload Open NO YES Compressor Winding Open Circuit Breakers or Fuses Open Comp...

Страница 14: ...door Coil Overcharge Inoperative Compressor Valves Inadequate Indoor Air Flow Recirculation of Outdoor Air Outdoor Check Valve Closed Inoperative Indoor Blower Non condensibles Restricted Indoor Meter...

Страница 15: ...Metering Device Restricted Outdoor Metering Device Non condensibles Restricted Filter Drier Restriction in System Wrong Indoor Blower Rotation Reversing Valve Failure Closed Indoor Check Valve Inadeq...

Страница 16: ...ately 6 to 8 from the compressor 4 Compare the suction line temperature to the saturated temperature 5 The difference between saturated temperature and suction line temperature is the superheat Superh...

Страница 17: ...hours for overload to reset If still open replace the compressor Add start kit components 1 2 3 4 Insufficient cooling Improperly sized unit Improper indoor air flow Incorrect refrigerant charge Air n...

Страница 18: ...er refrigerant evacuate and recharge 1 2 Gurgle or pulsing noise at expansion device or liquid line Air or non condensibles in sys tem 1 Recover refrigerant evacuate and recharge 1 Service Analyzer Ch...

Страница 19: ...it wiring Located in supply air stream Differential setting too close Customer mis use Internal foreign matter Power element failure Valve too small Distributor tube tubes restricted Restricted with f...

Страница 20: ...ing 1 Welding scale Nitrogen not used 1 Soldering flux Adding flux before seating copper part way 1 Excess soft solder Wrong solder material 1 Loss of Lubrication Low suction pressure Low charge Refri...

Страница 21: ...charge Remove restriction in liquid line Correct the refrigerant charge Remove non condensible gases Use correct TXV Remove external equalizer line restriction Replace with correct valve Replace power...

Страница 22: ...ng bulb is affected by liq uid refrigerant or refrigerant oil flowing through suction line Unequal refrigerant flow through evaporator circuits Improper superheat adjust ment only possible with TXV ha...

Страница 23: ...r service centers Warranty Policy Information Agreement then fax back to 229 273 5154 Invoices will be paid in accordance with Labor Allowance Guidelines included with this PO Failure to follow these...

Страница 24: ...is covered under this warranty Marvair will honor its warranty and furnish the required replacement part All costs for shipment and risk of loss during shipment of the product to Marvair and back to...

Страница 25: ...Motor Double Shafted 240 Volt ECM 40087 40081 40081 40081 40090 40090 Blower L H 30050 30090 30090 30090 30090 30090 Blower R H 30055 30092 30092 30092 30092 30092 Blower Wheel Housing 9 7T DD 10 8 D...

Страница 26: ...A P 50008 3 0 KVA P 50008 3 0 KVA Contactor Heat 2 Pole 30A 4 to 5 kW 50020 50020 50020 50020 50020 50020 Contactor Heat 3 Pole 40A 6 to 10 kW 50030 50030 50030 50030 50030 50030 Contactor Heat 3 Pole...

Страница 27: ...3 70363 Cable Assembly 01511 01511 01511 01511 Power Cable Assembly 01512 01512 01512 01512 Outdoor Motor 40098 40098 40051 40051 HP RPM 1 3 825 1 3 825 1 2 825 1 2 825 Capacitor Outdoor 50240 50240 5...

Страница 28: ...P 50007 2 0 KVA P 50008 3 0 KVA P 50008 3 0 KVA Contactor Heat 2 Pole 30A 4 to 5 kW 50020 50020 50020 50020 Contactor Heat 3 Pole 40A 6 to 10 kW 50030 50030 50030 50030 Contactor Heat 3 Pole 30A HPC...

Отзывы: