Page 84
•
The correct installation will not cause converse
water flow and the slope of the branch pipes can be
adjusted freely
•
The false installation will cause converse water flow
and the slope of the branch pipe can not be ad-
justed.
6. Water storage pipe setting
•
If the indoor unit has high extra static pressure and
without water pump to elevate the condensate wa-
ter, such as high extra static pressure duct unit , the
water storage pipe should be set to avoid converse
flow or blow water phenomena.
7. Lifting pipe setting of indoor unit with water pump
•
The length of lifting pipe should not exceed
750mm.
•
The drainage pipe should be set down inclined after
the lifting pipe immediately to avoid wrong opera-
tion of water level switch.
•
Refer the following picture for installation reference.
8. Blowhole setting
•
For the concentrated drainage pipe system, there
should design a blowhole at the highest point of
main pipe to ensure the condensate water discharge
smoothly.
•
The air outlet shall face down to prevent dirt enter-
ing pipe.
•
Each indoor unit of the system should be installed it.
•
The installation should be considering the conve-
nience for future cleaning.
9. The end of drainage pipe shall not contact with ground
directly.
5.3 Drainage test
1. Water leakage test
•
After finishing the construction of drainage pipe
system, fill the pipe with water and keep it for 24
hours to check whether there is leakage at joint
section.
2. Water discharge test
Check that the drainpipe is unhindered.
This test should be performed on newly built houses
before the ceiling is paved.
2.1 Units without a pump
Stow tube
•
Fill the water pan with 2 liters of water.
•
Check that the drainpipe is unhindered
.2.2 Units with a pump
1. Remove the test cover.
•
Fill the water pan with 2 liters of water.
Installation
Содержание YFAD-100R-01M25
Страница 15: ...Page 15 4 Centre of gravity 18K 24K...
Страница 16: ...Page 16 36K...
Страница 17: ...Page 17 48K 60K...
Страница 19: ...Page 19 DFMD 100N 01M25...
Страница 20: ...DFMD 100N 01T35 Page 20...
Страница 22: ...DFMD 160N 01M25 Page 22...
Страница 27: ...Page 27 YFAD 100R 01M25...
Страница 28: ...YFAD 100R 01T35 Page 28...
Страница 29: ...Page 29 YFAD 140R 01T35...
Страница 30: ...YFAD 160R 01T35 Page 30...
Страница 56: ...Page 56 11 Static Pressure 18K 24K...
Страница 57: ...Page 57 30K 36K 48K 60K...
Страница 93: ...Page 93 Design Static Pressure 3 Dynamic Losses For dynamic losses please refer to below image...
Страница 94: ...Page 94 Design Static Pressure 4 Corresponding Relation Between Rectangular Duct and Round Duct...