5.3  Outdoor Unit

Abbreviation

Paraphrase

CAP1, CAP2, CAP3,CAP4

Capacitor

FAN1

Outdoor Fan Motor

KM8

Contactor

CT1, CT2

AC Current Detector

COMP

Compressor

L-PRO, K2

Low Pressure Switch/Shorting Stub

K1

High Pressure Switch/Shorting Stub

TRANS

Power Transformer

T4

10K

Ω

 RESISTANCE/Outdoor Ambient Temperature

T3

10K

Ω

 RESISTANCE/Coil Temperature of Condenser

XT1

2-Way Terminal/4-Way Terminal

XT2

3-Way Terminal

XT4

Terminal

K3

Compressor Discharge Temperature/Shorting Stub

XP1~XP5,XT5~XT7

Connectors

Содержание YFAD-100R-01M25

Страница 1: ...25 YFAD 100R 01M25 DFMD 100N 01T35 YFAD 100R 01T35 DFMD 140N 01M25 YFAD 140R 01M25 DFMD 160N 01M25 YFAD 160R 01M25 IMPORTANT NOTE Read this manual carefully before installing or operating your new air...

Страница 2: ...ta 10 Electrical Characteristics 11 Static Pressure 2 Product Features 58 1 Operation Modes and Functions 2 Remote Controller Functions 3 Installation 75 1 Installation Overview 2 Location Selection 3...

Страница 3: ...91 1 Introduction 2 Charts for friction losses in round ducts 3 Dynamic losses 4 Corresponding relation between Rectangular duct and Round duct 5 Method for duct calculation 6 Unit conversion 7 Recom...

Страница 4: ...6 Dimensional Drawings 12 Centre of Gravity 15 Electrical Wiring Diagrams 18 Refrigerant Cycle Diagrams 31 Capacity Tables 33 Capacity Correction Factor for Height Difference 48 Noise Data 53 Electric...

Страница 5: ...of your purchased equipment Indoor Unit Model Outdoor Unit Model Capacity Btu h Power Supply DFMD 100N 01M25 YFAD 100R 01M25 36K 1 220 240V 50Hz DFMD 100N 01T35 YFAD 100R 01T35 36K 3 380 415V 50Hz DF...

Страница 6: ...7 Range Pa 0 100 Indoor air flow Hi Mi Lo m3 h 1700 1280 950 Sound level sound pressure dB A 45 41 5 38 5 Throttle type Indoor unit Dimension W D H mm 1100x774x249 Packing W D H mm 1305x805x305 Net Gr...

Страница 7: ...Charged volume Kg 2 8 Design pressure MPa 4 2 1 5 Refrigerant piping Liquid side Gas side mm inch 9 52 19 3 8 3 4 Max refrigerant pipe length m 30 Max difference in level m 20 Room tempera ture Coolin...

Страница 8: ...40 5 38 48 5 45 41 Throttle type Indoor unit Dimension W D H mm 1100x774x249 1200x874x300 Packing W D H mm 1305x805x315 1405x915x365 Net Gross weight Kg 32 2 39 4 46 54 5 Design pressure MPa 4 2 1 5...

Страница 9: ...Design pressure MPa 4 2 1 5 4 2 1 5 Refrigerant piping Liquid side Gas side mm inch 9 52 19 3 8 3 4 9 52 19 3 8 3 4 Max refrigerant pipe length m 30 50 Max difference in level m 20 30 Room temperatur...

Страница 10: ...ound level sound pressure dB A 51 7 46 9 44 4 Throttle type Indoor unit Dimension W D H mm 1200x874x300 Packing W D H mm 1405x915x365 Net Gross weight Kg 46 54 5 Design pressure MPa 4 2 1 5 Drainage w...

Страница 11: ...5 Refrigerant piping Liquid side Gas side mm inch 9 52 19 3 8 3 4 Max refrigerant pipe length m 50 Max difference in level m 30 Room temperature Cooling 18 43 Heating 7 24 Qty per 20 40 40 HQ Outdoor...

Страница 12: ...27 80 1 97 5 35 30 79 7 48 1 57 36 22 20 3 07 5 83 3 46 4 41 24 36 mm 1100 249 774 700 140 926 50 175 1001 228 5 1140 598 80 150 130 155 inch 43 31 9 80 30 47 27 56 5 51 36 46 1 97 6 89 39 41 8 98 0...

Страница 13: ...it Model KBtu h unit W D H W1 A B 18 mm 770 300 555 840 487 298 inch 30 31 11 81 21 85 33 07 19 17 11 73 24 mm 845 363 702 914 540 350 inch 33 27 14 29 27 64 35 98 21 26 13 78 36 mm 946 410 810 1030 6...

Страница 14: ...Page 14 Double Fan Outdoor Unit Model KBtu h unit W D H W1 A B 48 60 mm 900 350 1170 985 590 378 inch 35 43 13 78 46 06 38 78 23 23 14 88...

Страница 15: ...Page 15 4 Centre of gravity 18K 24K...

Страница 16: ...Page 16 36K...

Страница 17: ...Page 17 48K 60K...

Страница 18: ...reviation Paraphrase Y G Yellow Green Conductor CAP1 Indoor Fan Capacitor FAN Indoor Fan PUMP PUMP L LIVE N NEUTRAL TO CCM Comm Bus Central Controller T1 Indoor Room Temperature T2 Coil Temperature of...

Страница 19: ...Page 19 DFMD 100N 01M25...

Страница 20: ...DFMD 100N 01T35 Page 20...

Страница 21: ...SENSOR ROOM TEMP SENSOR CN40 WIRE CONTROLLER 4 CN5 CN9 X Y E To CCM Comm Bus Y G CN18 RED CN2 CN1 BLACK CN111 Y G 3 BLACK BROWN BLUE CN33 ALARM Alarm Output CN23 ON OFF Remote Control M CN43 FAN FOR...

Страница 22: ...DFMD 160N 01M25 Page 22...

Страница 23: ...L N of the motor 2 The output voltage is the power supply 3 The fresh motor can not excess 200W or 1A follow the smaller one 4 The new fresh motor will be worked when the indoor fan motor work when th...

Страница 24: ...voltage of the terminal port the power from the ALARM system not from the unit 2 Althought design voltage can support higher voltage but we strongly ask you connect the power less than 24V current le...

Страница 25: ...the remote switch the unit would be responded the demand within 2 seconds 5 When the remote switch on you can use remote controller wire controller to select the mode what you want when the remote swi...

Страница 26: ...ompressor L PRO K2 Low Pressure Switch Shorting Stub K1 High Pressure Switch Shorting Stub TRANS Power Transformer T4 10K RESISTANCE Outdoor Ambient Temperature T3 10K RESISTANCE Coil Temperature of C...

Страница 27: ...Page 27 YFAD 100R 01M25...

Страница 28: ...YFAD 100R 01T35 Page 28...

Страница 29: ...Page 29 YFAD 140R 01T35...

Страница 30: ...YFAD 160R 01T35 Page 30...

Страница 31: ...iameter mm inch Piping length m ft Elevation m ft Additional Refrigerant Gas Liquid Rated Max Rated Max 19 3 4 9 52 3 8 5 16 4 30 98 4 0 20 65 6 30g m 0 32oz ft 19 3 4 9 52 3 8 5 16 4 30 98 4 0 20 65...

Страница 32: ...m inch Piping length m ft Elevation m ft Additional Refrigerant Gas 19 3 4 19 3 4 Liquid 9 52 3 8 9 52 3 8 Rated 5 16 4 5 16 4 Max 50 164 50 164 Rated 0 0 Max 30 98 4 30 98 4 YFAD 140R 01T35 YFAD 160R...

Страница 33: ...3 41 10 00 0 59 3 73 9 21 0 60 4 27 8 74 0 61 4 59 11 85 0 59 2 77 11 73 0 59 2 86 11 21 0 60 3 17 10 72 0 60 3 48 10 18 0 61 3 81 9 30 0 63 4 36 8 83 0 63 4 69 27 0 11 61 0 65 2 71 11 50 0 65 2 80 11...

Страница 34: ...23 3 23 3 23 3 23 30 TC 9 98 10 06 10 18 10 29 10 61 10 61 10 61 10 72 10 92 10 92 10 92 10 92 11 76 11 76 11 76 11 76 S T 0 81 0 93 1 00 1 00 0 62 0 74 0 85 0 97 0 54 0 65 0 76 0 87 0 34 0 44 0 55 0...

Страница 35: ...74 9 46 9 46 9 46 9 46 S T 0 71 0 79 0 87 0 94 0 57 0 65 0 72 0 80 0 51 0 59 0 66 0 73 0 37 0 44 0 50 0 57 PI 4 56 4 56 4 56 4 56 4 58 4 58 4 58 4 58 4 59 4 59 4 59 4 59 4 63 4 63 4 63 4 63 1280 15 TC...

Страница 36: ...23 3 23 3 23 3 23 30 TC 9 98 10 06 10 18 10 29 10 61 10 61 10 61 10 72 10 92 10 92 10 92 10 92 11 76 11 76 11 76 11 76 S T 0 79 0 90 1 00 1 00 0 61 0 72 0 83 0 93 0 53 0 63 0 74 0 84 0 34 0 44 0 54 0...

Страница 37: ...74 9 46 9 46 9 46 9 46 S T 0 74 0 84 0 93 1 00 0 59 0 68 0 77 0 86 0 52 0 61 0 69 0 78 0 36 0 44 0 52 0 60 PI 4 27 4 27 4 27 4 27 4 29 4 29 4 29 4 29 4 30 4 30 4 30 4 30 4 34 4 34 4 34 4 34 1372 15 TC...

Страница 38: ...02 3 02 3 02 3 02 30 TC 9 98 10 06 10 18 10 29 10 61 10 61 10 61 10 72 10 92 10 92 10 92 10 92 11 76 11 76 11 76 11 76 S T 0 80 0 92 1 00 1 00 0 62 0 73 0 85 0 96 0 53 0 65 0 76 0 87 0 34 0 44 0 55 0...

Страница 39: ...2 59 12 59 12 59 S T 0 73 0 81 0 90 0 98 0 58 0 66 0 75 0 83 0 51 0 60 0 68 0 76 0 36 0 44 0 51 0 58 PI 6 25 6 25 6 25 6 25 6 28 6 28 6 28 6 28 6 29 6 29 6 29 6 29 6 34 6 34 6 34 6 34 1800 15 TC 14 49...

Страница 40: ...44 30 TC 13 29 13 29 13 44 13 58 14 13 14 13 14 13 14 27 14 56 14 56 14 56 14 56 15 68 15 68 15 68 15 68 S T 0 77 0 88 0 98 1 00 0 60 0 70 0 81 0 90 0 53 0 62 0 72 0 82 0 35 0 44 0 53 0 62 PI 4 86 4 8...

Страница 41: ...4 46 14 46 14 46 S T 0 71 0 79 0 88 0 96 0 58 0 65 0 73 0 81 0 51 0 59 0 66 0 74 0 37 0 44 0 51 0 57 PI 7 43 7 43 7 43 7 43 7 47 7 47 7 47 7 47 7 49 7 49 7 49 7 49 7 55 7 55 7 55 7 55 1850 15 TC 16 62...

Страница 42: ...27 30 TC 15 23 15 23 15 37 15 52 16 18 16 18 16 18 16 35 16 69 16 69 16 69 16 69 17 99 17 99 17 99 17 99 S T 0 76 0 87 0 97 1 00 0 60 0 70 0 80 0 89 0 52 0 62 0 72 0 81 0 35 0 44 0 53 0 62 PI 5 77 5 7...

Страница 43: ...7 36 2 34 2 39 2 50 2 55 5 6 8 01 7 92 7 86 7 81 2 41 2 52 2 57 2 63 2 8 8 44 8 33 8 27 8 21 2 55 2 68 2 74 2 80 0 0 8 76 8 65 8 56 8 50 2 70 2 84 2 90 2 97 2 8 9 40 9 28 9 23 9 14 2 89 3 03 3 10 3 18...

Страница 44: ...7 41 7 36 2 53 2 59 2 71 2 78 5 6 8 01 7 92 7 86 7 81 2 61 2 73 2 80 2 86 2 8 8 44 8 33 8 27 8 21 2 77 2 91 2 98 3 05 0 0 8 76 8 65 8 56 8 50 2 94 3 08 3 16 3 23 2 8 9 40 9 28 9 23 9 14 3 14 3 29 3 3...

Страница 45: ...6 88 6 86 2 81 2 89 2 94 2 98 5 6 7 58 7 46 7 41 7 38 2 82 2 91 2 96 3 00 2 8 8 07 7 99 7 93 7 87 2 86 2 96 3 00 3 05 0 0 8 48 8 37 8 31 8 25 2 91 3 00 3 05 3 10 2 8 9 24 9 12 9 03 8 98 2 98 3 08 3 1...

Страница 46: ...02 3 97 4 08 4 16 4 23 5 6 10 15 10 00 9 94 9 86 4 00 4 13 4 20 4 26 2 8 10 96 10 81 10 76 10 67 4 08 4 22 4 29 4 36 0 0 11 66 11 48 11 39 11 31 4 16 4 31 4 38 4 45 2 8 12 79 12 61 12 53 12 44 4 29 4...

Страница 47: ...4 71 4 81 4 88 5 6 10 51 10 37 10 28 10 22 4 62 4 78 4 85 4 92 2 8 11 53 11 38 11 30 11 21 4 71 4 87 4 95 5 03 0 0 12 40 12 20 12 11 12 02 4 81 4 97 5 05 5 14 2 8 13 77 13 56 13 48 13 36 4 95 5 12 5...

Страница 48: ...0 929 0 874 5 0 995 0 967 0 939 0 883 0 1 000 0 972 0 944 0 887 Outdoor Upper than Indoor 5 1 000 0 972 0 944 0 887 10 0 972 0 944 0 887 15 0 944 0 887 Heating 5 10 15 25 Height difference H m Indoor...

Страница 49: ...51 0 1 000 0 964 0 928 0 855 Outdoor Upper than Indoor 5 1 000 0 964 0 928 0 855 10 0 964 0 928 0 855 15 0 928 0 855 Heating 5 10 15 25 Height difference H m Indoor Upper than Outdoor 15 0 973 0 946 1...

Страница 50: ...1 000 0 953 0 905 0 858 0 810 0 763 10 0 953 0 905 0 858 0 810 0 763 15 0 905 0 858 0 810 0 763 20 0 858 0 810 0 763 Heating 5 10 15 20 25 30 Height difference H m Indoor Upper than Outdoor 20 0 935 0...

Страница 51: ...1 000 0 969 0 907 0 846 0 784 0 722 10 0 969 0 907 0 846 0 784 0 722 20 0 907 0 846 0 784 0 722 30 0 846 0 784 0 722 Heating 5 10 20 30 40 50 Height difference H m Indoor Upper than Outdoor 30 0 929 0...

Страница 52: ...1 000 0 962 0 885 0 808 0 731 0 654 10 0 962 0 885 0 808 0 731 0 654 20 0 885 0 808 0 731 0 654 30 0 808 0 731 0 654 Heating 5 10 20 30 40 50 Height difference H m Indoor Upper than Outdoor 30 0 909 0...

Страница 53: ...ition Reference acoustic pressure OdB 20 Pa Sound level will vary depending on a range of factors such as theconstruction acousticabsorptioncoefficient ofparticular room in which the equipment is inst...

Страница 54: ...nal operation condition Reference acoustic pressure OdB 20 Pa Sound level will vary depending on arrange off actors such as the construction acoustic absorption coefficient of particular room in which...

Страница 55: ...Wiring mm2 Ground Wiring 2 5 2 5 4 0 Strong Electric Signal 2 1 0 3 2 5 3 1 0 3 2 5 3 1 0 3 1 5 Weak Electric Signal 2 0 75 2 0 5 2 0 2 2 0 2 Type 36000 Btu h 48000 Btu h 60000 Btu h Phase 3 phase 3...

Страница 56: ...Page 56 11 Static Pressure 18K 24K...

Страница 57: ...Page 57 30K 36K 48K 60K...

Страница 58: ...ay Function 59 Fan 59 Cooling Mode 59 Heating Mode 59 Auto Mode 60 Drying Mode 60 Timer Function 60 1 10 Sleep Function 60 1 11 Auto Restart 61 1 12 Follow Me 61 1 13 Drain Pump Control 61 Remote Cont...

Страница 59: ...f the rated for 3 seconds the compressor will stop and an error code will be displayed on the outdoor PCB If the current becomes normal the indoor sends signal to the outdoor the outdoor will display...

Страница 60: ...or and outdoor fan cease operations 1 7 Auto Mode This mode can be selected with the remote controller and the temperature setting can be adjusted between 17 30 In auto mode the machine selects coolin...

Страница 61: ...arts If the unit was already off before the power failure the compressor starts 1 minute after the unit restarts 1 12 Follow Me If you press Follow Me on the remote the indoor unit will beep This indi...

Страница 62: ...eater function becomes ineffective Used to restore the system to its default settings Used to start stop the air conditioner Press these two buttons at the same time to switch between Celsius and Fahr...

Страница 63: ...Shield Cable Wire Joint 5p Infrared Pipe Indoor Unit RUN GND 5V Indoor Unit Switch Board Wir e Con troll er Installation Diagram Connect the wire from the display panel of the indoor unit to a connect...

Страница 64: ...s For exposed mounting cut holes on four of the sides according to the picture below Cut three holes for wire outlet Cut one holes for wire outlet For shielded wiring please refer to the picture below...

Страница 65: ...ss for adjusting the angel of louver hold for vertical swing individual louver control for cassette panel 6 Left righ airflow swing Button Press for activing the horizontal swing 7 FOLLOW ME PTC butto...

Страница 66: ...own swing indication 5 Faceplate function indication 6 Main unit and secondary unit indication 7 Follow me function indication 8 PTC function indication 9 C F indication 10 Temperature display 11 Lock...

Страница 67: ...inboard CN40 Wire controller Indoor unit mainboard 4 Core Shield Cable the length is decided by installation Installation Diagram Connect the female joint of wires group from the mainboard with the ma...

Страница 68: ...ed mounting four outletting positions There are three need cutting Cutting place of top side wire outlet Cutting place of left side wire outlet Cutting place of right side wire outlet For shielded wir...

Страница 69: ...or down the auto lifting panel 4 FAN SPEED button Usedtoselect the fan speed 5 Swing Button Press to active vertical swing hold for horizontal swing 6 TIMER button To set timer on and timer off time...

Страница 70: ...swing indication 5 Faceplate function indication 6 Main unit and secondary unit indication 7 Follow me function indication 8 Turbo PTC function indication 9 C F indication 10 Temperature display 11 L...

Страница 71: ...ects to main control board directly HA HB HA HB Main control board Wired controller ADSS 01 2 3 4 5 6 7 8 9 A B C D EF For Duct Ceiling floor The wired controller connects to terminal board terminal b...

Страница 72: ...ts every air conditioner in network has only one network address to distinguish each other c Address code of air conditioner in LAN is set by code switch ENC1 Duct and Ceiling Floor or ADSS Cassette o...

Страница 73: ...e are three methods From the rear From the bottom From the top From the top center PCB PCB PCB PCB HA HB 1 2 HA HB HA HB 2 HA HB 1 2 1 2 3 4 1 Indoor Unit 2 Notch the part for the wiring to pass throu...

Страница 74: ...ddress can be set from 0 to 63 by the switch Turn on the unit then the address will be effective Note For light commercial aire conditioner with XYE port it can be also connected to BMS Building Manag...

Страница 75: ...Indoor Unit Installation 79 Outdoor Unit Installation 82 Drainage Pipe Installation 83 Refrigerant Pipe Installation 86 Vacuum Drying and Leakage Checking 87 Additional Refrigerant Charge 88 Engineeri...

Страница 76: ...5 9 52 0 25in 0 375in Packed with the indoor unit NOTE Pipe size may differ from appliance to appliance To meet different pipe size requirements sometimes the pipe connections need a transfer connecto...

Страница 77: ...ew Installation Order L N 1 2 3 5 MC MC 6 7 Install the indoor unit Install the outdoor unit Install the drainpipe Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Per...

Страница 78: ...nce between the outdoor unit and walls described in the installation guide does not apply to airtight rooms Be sure to keep the unit unobstructed in at least two of the three directions M N P M N P 30...

Страница 79: ...pipes as well as indoor and outdoor wires with their connection points before mounting the unit 5 Drill 4 holes 10cm 4 deep at the ceiling hook positions in the internal ceiling Be sure to hold the dr...

Страница 80: ...uct underlayer to muffle the duct system and weaken the air encounter noise in the duct Adjust the air inlet direction From rear side to under side 1 Take off ventilation panel and flange Air return f...

Страница 81: ...e connector D Connector A Connector B Connector C Connector D Hose Plug the external pump to the PUMP pin and the water level sensor to the CN5 to enable the pump Short connect the CN5 Unplug the PUMP...

Страница 82: ...A B D 18 487 298 300 24 540 350 363 36 673 403 410 48 60 590 378 350 4 3 Install Outdoor Unit Fix the outdoor unit with anchor bolts M10 Cation Since the gravity center of the unit is not at its physi...

Страница 83: ...pipe Reference value of inner diameter of pipe mm Allowable maximum water flowrate l h Remark Slope 1 50 Slope 1 100 PVC25 20 39 27 For branch pipe PVC32 25 70 50 PVC40 31 125 88 Could be used for co...

Страница 84: ...Blowhole setting For the concentrated drainage pipe system there should design a blowhole at the highest point of main pipe to ensure the condensate water discharge smoothly The air outlet shall face...

Страница 85: ...d receiving board and even water shall run over the water collector Continuously infusing water until water level alarmed check whether the drainage pump could discharge water at once If water level d...

Страница 86: ...y of the pipes 3 Measure the necessary pipe length 4 Cut the selected pipe with pipe cutter Make the section flat and smooth Oblique Rough Warped 90 5 Insulate the copper pipe Before test operation th...

Страница 87: ...icates that there is moisture or leakage in pipeline system and need to go on with drying for half an hour 3 If the vacuum degree of vacuum pump still could not reach 755mmHg after 1 5 hours of drying...

Страница 88: ...itable pipe insulation except joint section flare the pipe piping layout and connection vacuum drying insulate the joint parts 2 Purpose of refrigerant pipe insulation During operation temperature of...

Страница 89: ...ighlights of electrical wiring installation All field wiring construction should be finished by qualified electrician Air conditioning equipment should be grounded ac cording to the local electrical r...

Страница 90: ...ler works well Whether the buttons on the remote controller works well Whether the air flow louver moves normally Whether the room temperature is adjusted well Whether the indicator lights normally Wh...

Страница 91: ...uction 95 Charts for friction losses in round ducts 95 Dynamic losses 96 Corresponding relation between Rectangular duct and Round Duct 97 Method for duct calculation 98 Unit conversion 98 Recommended...

Страница 92: ...or between individual particles of adjacent fluid layers moving at different velocities in turbulent flow Friction losses occur along the entire duct length Dynamic losses result from flow disturbanc...

Страница 93: ...Page 93 Design Static Pressure 3 Dynamic Losses For dynamic losses please refer to below image...

Страница 94: ...Page 94 Design Static Pressure 4 Corresponding Relation Between Rectangular Duct and Round Duct...

Страница 95: ...art of main duct through Fricitions loss chart 1 Find the dynamic loss of main ducting route according to the velocity and type of special fittings elbows junctions regulating flaps etc 1 Obtain the d...

Страница 96: ...t with the sales agency or manufacturer for details ATTENTION Le design et les donn es techniques sont donn s titre indicatif et peuvent tre modifi s sans pr avis AIRWELL RESIDENTIAL SAS 10 Rue du For...