Installation Procedures
4. Drainpipes
(a) Keep a gradient (1/50-1/100) of the drainpipes and avoid lobing or curving.
(b)
When connecting the drainpipe to the equipment, don
’
t apply too much force on one side of
the equipment. Meanwhile, the piping should be positioned as close to the equipment as
possible.
1.5m ~ 2m
Proper Piping
hanging bolt
heat insultor
gradient of 1/100 or over
Improper Piping
air outlet port
avoid lobing
avoid curving
don't put pipe
into water
standard blowing wind (at delivery)
blue
white
yellow
red
blue
white
yellow
red
blue
white
yellow
red
black
white
blue
red
high-speed blowing wind
50
96
Standard
Static
Pressure
Max.
Static
Pressure
Static Pressure Range
unit: Pa
(c)
For the drainpipe, the general purpose hard PVC tube can be purchased at local shops. During
the connection, insert the end of PVC tube into the wash port and fasten it with drainage hose
and thread clip. Binding agents shouldn
’
t be used to connect the wash port and drainage hose.
(b) Unless it is regulated to the level position, faults or errors might occur for the floater switch.
0~5 mm
(0~0.2")
one side of piping
water supply
level
PVC tube
make one side of piping a little lower
The blower is provided with a red terminal and a white terminal. The standard wind choice has
been set before delivery. When the use of optional components, such as the high performance
filter, causes the static pressure rising, change the connection of the connector mounted on the
side of the control cabinet, as shown as follows.
Choice of Blowing Wind from Blower
(when using the high performance filter)