HMF Series 30 Version - 0
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the
air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at
a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way
valve’s service port immediately
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
Electronic scale
Содержание AWAU-YMF009-C12
Страница 16: ...HMF Series 16 Version 0 6 Wiring Diagram 6 1 Indoor Unit AWSI HMF009 N12 AWSI HMF012 N12 AWSI HMF018 N12...
Страница 17: ...HMF Series 17 Version 0 AWSI HMF024 N12 6 2 Outdoor Unit AWAU YMF009 C12 AWAU YMF012 C12...
Страница 18: ...HMF Series 18 Version 0 AWAU YMF018 C12 AWAU YMF024 C12...
Страница 19: ...HMF Series 19 Version 0...
Страница 50: ...HMF Series 50 Version 0 AWSI HMF012 N12 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 52: ...HMF Series 52 Version 0 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 58: ...HMF Series 58 Version 0 AWAU YMF012 C12 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 60: ...HMF Series 60 Version 0 AWAU YMF018 C12 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 62: ...HMF Series 62 Version 0 AWAU YMF024 C12 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 64: ...HMF Series 64 Version 0 SERVICE MANUAL HMF Series...