HMF Series 27 Version - 0
Open the handle Lo valve of the manifold valve
slightly to purge air from the charge hose for 5 seconds
and then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and tighten the 2-way and 3-
way valve’s stem nuts.
Use a torque wrench to tighten the 3-way valves service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on
the 2-
way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
Содержание AWAU-YMF009-C12
Страница 16: ...HMF Series 16 Version 0 6 Wiring Diagram 6 1 Indoor Unit AWSI HMF009 N12 AWSI HMF012 N12 AWSI HMF018 N12...
Страница 17: ...HMF Series 17 Version 0 AWSI HMF024 N12 6 2 Outdoor Unit AWAU YMF009 C12 AWAU YMF012 C12...
Страница 18: ...HMF Series 18 Version 0 AWAU YMF018 C12 AWAU YMF024 C12...
Страница 19: ...HMF Series 19 Version 0...
Страница 50: ...HMF Series 50 Version 0 AWSI HMF012 N12 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 52: ...HMF Series 52 Version 0 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 58: ...HMF Series 58 Version 0 AWAU YMF012 C12 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 60: ...HMF Series 60 Version 0 AWAU YMF018 C12 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 62: ...HMF Series 62 Version 0 AWAU YMF024 C12 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Страница 64: ...HMF Series 64 Version 0 SERVICE MANUAL HMF Series...