Piping installation

Please don't let the pipe and the parts in the unit collide each other.

The connection between outdoor liquid pipe and the distributing pipe is flared type. Please
expand the pipe with the special tool for R410A after installing the expanding nut. But if the
projecting pipe length has been adjusted with the copper pipe gauge, you can use the original
tool to expand the pipe.
Since the unit is with R410A, the expanding oil is ester oil, not the mineral oil.

When connecting the pipes, close the valves fully.
Protect the pipe end against the water, impurity into the pipes (welding after being flat,
or being sealed with adhesive tape).
Bend the pipe as large semi-diameter as possible(over 4 times of the pipe diameter).

When connecting the expanding pipe, fasten the pipes with double-spanner. The torque refers
to the former info.

Important

A

0

-0.4

6.35

9.52

12.7

15.88

9.1

13.2

16.6

19.7

Expanding pipe:A(mm)

pipe outer
diameter

Projecting length of pipe to be expanded:B(mm)

6.35
9.52
12.7

15.88

when it is hard pipe

0-0.5

1.0-1.5

pipe outer

diameter special tool

for R410A

the former

tool

welding

adhesive tape

flat

Protect the pipe end against the water, impurity into the pipes (welding after being flat, or being
sealed with adhesive tape).

Seal the pipe end with adhesive tape or the stopper
to increase the resistance, fill up the pipe with nitrogen.

<N2>

taping

Only  nitrogen
gas can be used

brazing

The outdoor gas pipe and the refrigerant distributing pipe, as well the refrigerant distributing
pipe and the branch pipe should be welded with hard solder.
Weld the pipe at the same time charge the nitrogen. Or it will cause a number of impurity (a
film of oxidation) to clog the capillary and the expansion valve, further cause the deadly failure.

Installation procedure

Содержание AWAU-B-YCV150-H13

Страница 1: ...AWAU YCV080 H11 AWAU B YCV150 H13 AWAU YCV180 H13 No 0150510082 Please read this manual carefully before using Keep this operation manual for future reference...

Страница 2: ...ting indoor outdoor indoor outdoor max min max min max min max min DB 32 WB 15 5 DB 18 DB 43 DB 5 DB 27 DB 15 DB 21 DB 15 WB 23 WB 14 WB 26 Operating Range of Air Conditioner 1 2 3 4 5 13 14 15 16 22...

Страница 3: ...oisonous gas will enter indoor In installation or after installation please confirm if there is refriegerant leakage please take measures for ventilation The refrigerant will cause poisonous gas as me...

Страница 4: ...the refrigerant leaks in a small room and exceeds the limited concentration it will cause lack of oxygen Don t use the other refrigerant except for R410A The R410A pressure is 1 6 times higher than R2...

Страница 5: ...ata marked on the rating label If the address of indoors has been set indoor capacity 100W outdoor combination type indoor Qty total indoor capacity 100W 80 180 single single 5 9 40 104 90 234 indoor...

Страница 6: ...ial hole at bottom of the unit When being hanged the rope should be 4 pieces of steel cable with over 6mm diameter Put the cushion at the contact section between steel cable and the unit against the d...

Страница 7: ...der the pressure of about 0 5Mpa and when charging the nitrogen stop up the end of the pipe by hand to enhance the pressure in the pipe then loose the hand meanwhile stop up the other end 3 The piping...

Страница 8: ...en the distance from outdoor to the longest indoor is over 30m the main pipe should be the enlarged diameter 3 Pipe c diameter outdoor pipe diameter Outdoor capacity 100W 80 180 15 88 19 05 9 52 Gas p...

Страница 9: ...oor units h Total length of piping actual length Actual length Up outdoor Under outdoor B YCV150 YCV180 Maximal length and drop height permissible of refrigerant piping L2 L3 L4 e L1 L2 L3 L4 a b c d...

Страница 10: ...ed joint Liquid pipe side Diameter Connecting method Diameter Connecting method 24 18 16 12 09 Flared joint 9 52 12 7 12 7 6 35 9 52 6 35 6 35 6 35 C Pipe spec and the torque Not less than 28 58 diame...

Страница 11: ...g pipes and among the units please must execute at the branch pipe side 3 When welding with hard solder please must blow nitrogen If not a number of oxide will be produced and cause heavy damage Besid...

Страница 12: ...h double spanner The torque refers to the former info Important A 0 0 4 6 35 9 52 12 7 15 88 9 1 13 2 16 6 19 7 Expanding pipe A mm pipe outer diameter Projecting length of pipe to be expanded B mm 6...

Страница 13: ...e chlorin oxygen flammable gas in the leakage test Apply pressure both on the gas pipe and the liquid pipe 3 Apply the pressure step by step to the target pressure a Apply the pressure to 0 5MPa for m...

Страница 14: ...valve and the gas stop valve with hexangular spanner until it stops If opening the valve strongly the valve will be damaged Tighten the valve cap Operation procedure after reaching 100 7KPa or less b...

Страница 15: ...r because the R410A will change when transferring to the cylinder When charging refrigerant the refrigerant should be taken out from the tank as liquid state Mark the counted refrigerant volume due to...

Страница 16: ...Indoor motor will run at low speed or stop and outdoor motor will stop The unit operation condition To use the unit properly please operate the unit under the allowed condition range If operating beyo...

Страница 17: ...icate the connected indoor unit As the below figure Trial operation Trial operation In trial operation refer to the information of performance section When the unit can not start up at the room temper...

Страница 18: ...cted to wired controller is connected by 3 polar wires the other indoors and the master indoors are connected by 2 polar wires B 1 to 1 one wired controller controls one indoor as shown in above figur...

Страница 19: ...reaker L1 L2 L3 N outdoor power source 3N 380 400V 50Hz L N indoor 3 non wall mounted unit power source 1PH 220 230V 50Hz L N indoor 1 wall mounted unit power source 1PH 220 230V 50Hz over current bre...

Страница 20: ...30mA below 0 1s 30A 30mA below 0 1s 40A 30mA below 0 1s 50A 30mA below 0 1s 2 core 0 75 2 0mm 2 shielded wire indoor total current A rated current of overcurrent breaker A communication wire section o...

Страница 21: ...or unit PMV decimal number Sensor TD Air Discharge value decimal number Sensor TA Environment timP value decimal number Sensor TS Air suction value decimal number Sensor TE Defrost value decimal numbe...

Страница 22: ...function with 0151800123 PCB 11 15 No used 0 2 No used 3 Error view previous 10 error code displayed quit this condition automatically in 2 min check the last next error code with UP DOWN button This...

Страница 23: ...4 1 0 1 0 1 SW01 identify 1 LED2 flashing times 5 LED2 change to indication lamp for indoor and outdoor unit communication after confirming model SW01 Function identify B YCV150 1 2 3 4 1 0 0 1 SW01...

Страница 24: ...ime short function 60 seconds become to 1 second CJ2 Reserved LED1 error lamp flash times LED2 communication commissioning lamp it is flashing constantly under communication The flash times is differe...

Страница 25: ...otection TS Low pressure switch circuit High pressure switch circuit Compressor discharge temp Protection TD Main board eeprom failure The current indoor unit qty is different from the qty of indoor u...

Страница 26: ...antly The phase is missing 41 42 49 4A The current detect circuit is abnormal Temp Sensor is abnormal 39 40 47 48 Flashing times and error code displayed of outdoor unit Malfunction position Power mod...

Страница 27: ...efinition outdoor code outdoor code indoor ambient temp sensor TA failure indoor coil temp sensor TC1 failure indoor pipe temp sensor TC2 failure indoor TES sensor failure indoor EEPROM failure commun...

Страница 28: ...ectronic waste can be disposed of ate least free of charge to the user b When buying a new product the retailer will take back the old product at least free of charge c The manufacturer will take back...

Страница 29: ...27...

Страница 30: ......

Страница 31: ......

Страница 32: ......

Отзывы: