Outdoor unit type
Branch pipe
total indoor capacity(100W)
model(optional)
less than 335
TAU335
Branch pipe selection:
Note:
1. When connecting the pipe and the
outdoor, please pay attention to the outdoor
pipe dimension.
2. When adjusting the diameter among
pipes and among the units, please must execute at the branch pipe side.
3. When welding with hard solder, please must blow nitrogen. If not, a number of oxide will be
produced and cause heavy damage.Besides,to prevent water and dust into the pipe, please
make the brim as outer roll.
Cut off pipe with the cutter
Cut off at the middle
Adhesive side
Prepare on field
Seal the connection and wrap the
heat insulator with adhesive tape
Installation procedure