background image

En-4

3.3.4. Leveling

• Using a level, or vinyl hose 

filled with water, fine adjust 
so that the body is level.

• Inclined installation so 

as the drain pipe side 
is higher may cause a 
malfunction of the float 
switch, and may cause 
water leakage.

Vinyl hoses

Drain pipe

4.  PIPE INSTALLATION

 

CAUTION

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 
refrigerant R410A models. Also, when storing the piping, securely seal the openings by 
pinching, taping, etc.

While welding the pipes, be sure to blow dry nitrogen gas through them.

4.1.  Selecting the pipe material

 

CAUTION

Do not use existing pipes from another refrigeration system or refrigerant.

Use pipes that have clean external and internal sides without any contamination which 
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.

It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 40 mg/10 m.

Do not use copper pipes that have a collapsed, deformed, or discolored portion (es-
pecially on the interior surface). Otherwise, the expansion valve or capillary tube may 
become blocked with contaminants.

Improper pipe selection will degrade performance. As an air conditioner using R410A 
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary to 
choose adequate materials.

• Thicknesses of copper pipes used with R410A are as shown in the table.
• Never use copper pipes thinner than those indicated in the table even if they are avail-

able on the market.

Thicknesses of 
Annealed Copper 
Pipes (R410A)

Pipe outside diameter [mm (in)]

Thickness [mm]

6.35 (1/4)

0.80

9.52 (3/8)

0.80

12.70 (1/2)

0.80

15.88 (5/8)

1.00

19.05 (3/4)

1.20

4.2.  Pipe requirement

 

CAUTION

Refer to the installation manual for the outdoor unit for description of allowable pipe 
length and height difference.

Use pipe with water-resistant heat insulation.

 

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause 
water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is 
expected to exceed 70 %, install heat insulation around the refrigerant piping. If the 
expected humidity level is 70 to 80 %, use heat insulation that is 15 mm or thicker and 
if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker. If 
heat insulation is used that is not as thick as specified, condensation may form on the 
surface of the insulation. In addition, use heat insulation with heat conductivity of 0.045 
W/(m·K) or less (at 20 °C).

4.3.  Flare connection (pipe connection)

 

WARNING

Tighten the flare nuts with a torque wrench using the specified tightening method. Other-
wise, the flare nuts could break after a prolonged period, causing refrigerant to leak and 
generate hazardous gas if the refrigerant comes into contact with a flame.

4.3.1. Flaring

Use special flare tool exclusive for R410A.
(1)  Cut the connection pipe to 

the necessary length with a 
pipe cutter.

(2)  Hold the pipe downward so 

that cuttings will not enter the 
pipe and remove any burrs.

(3)  Insert the flare nut (always 

use the flare nut attached to 
the indoor and outdoor units 
(or RB unit) respectively) 
onto the pipe and perform 
the flare processing with a 
flare tool. Use the special 
R410A flare tool. Leakage of 
refrigerant may result if other 
flare nuts are used.

(4)  Protect the pipes by pinching 

them or with tape to prevent 
dust, dirt, or water from 
entering the pipes.

Check if [L] is 
flared uniformly 
and is not cracked 
or scratched.

Pipe

Die

Pipe outside 

diameter 

[mm (in)]

Dimension A 

[mm]

(Flare tool for 

R410A, clutch 

type)

Dimension 

B

 0

-0.4

 [mm]

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional (R22) 
flare tools to flare R410A pipes, the 
dimension A should be approxi-
mately 0.5 mm more than indicated 
in the table (for flaring with R410A 
flare tools) to achieve the speci-
fied flaring. Use a thickness gauge 
to measure the dimension A. It is 
recommended that a R410A flaring 
tool is used.

Pipe outside 

diameter 

[mm (in)]

Width across 

flats of Flare nut 

[mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

Width across 

flats

4.3.2. Bending pipes

• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it difficult 

to bend or stretch them anymore. 

• Do not bend or stretch the pipes more than 3 times.

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. 

If the pipe is bent repeatedly at the same place, it will break.

4.3.3. Pipe connection 

 

CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the flare nut cannot tightened smoothly. If the flare 
nut is forced to turn, the threads will be damaged.

Do not remove the flare nut from the indoor unit pipe until immediately before connect-
ing the connection pipe.

Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as 
this would reduce the lifetime of the units.

Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to 
tighten the flare nut correctly.

(1)  Detach the caps and 

plugs from the pipes.

(2)  Center the pipe against 

the port on the indoor 
unit,  and then turn the 
flare nut by hand.

Connection pipe (Gas)

Connection pipe 
(Liquid)

(3)  When the flare nut is tightened properly 

by your hand, hold the body side coupling 
with a separate spanner, then tighten with 
a torque wrench. (See the table below for 
the flare nut tightening torques.)

Tighten with 2 
wrenches.

Holding 
wrench

Flare nut 

Connection pipe

Indoor unit pipe 
(Body side)

Torque 
wrench

Flare nut 
[mm (in)]

Tightening torque 

[N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

9371022642-02_IM.indb   4

9371022642-02_IM.indb   4

2019/10/11   10:00:39

2019/10/11   10:00:39

Содержание AUXK018GLEH

Страница 1: ...CI N UNIT INT RIEURE type cassette UNIDAD INTERIOR Tipo casete Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a cas...

Страница 2: ...sult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A r...

Страница 3: ...that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such...

Страница 4: ...ain piping positions unit mm Drain pipe Connect the attached drain hose 342 293 45 200 140 180 10 80 Gas pipe Liquid pipe Drain pipe Distribution ducts and fresh air inlet positions Distribution duct...

Страница 5: ...flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe a...

Страница 6: ...age may be blown out If it is impossible to have sufficient gradient of pipe perform drain lift up Pipe size Drain pipe VP25 O D 32 mm Hanging fittings 1 5 to 2 m VP25 O D 32 mm Downward gradient 1 10...

Страница 7: ...electricity charged in the body may cause malfunction of the PCB Follow the cautions below Establish an earth ground for the indoor and outdoor units and peripheral devices Cut power breaker off Touch...

Страница 8: ...en the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Strip 10 mm Ring termina...

Страница 9: ...re with solder IMPORTANT Be sure to insulate the connection between the wires Locally purchased Solder and insulate the connected parts Wire kit connector optional parts Wiring arrangement In followin...

Страница 10: ...e controller group operates in the same mode When function setting is Emergency stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF No...

Страница 11: ...AD 1 Factory setting 0 Rotary switch IU AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD SW as shown in the Table A for each refrigerant system Set to the same refrigeran...

Страница 12: ...ntral remote controller 01 Display only on central remote controller Fan set ting when cooling thermostat OFF 49 00 Follow the setting on the remote controller When set to 01 the fan stops when the th...

Страница 13: ...ed remote control ler error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expan...

Отзывы: