En-3

3.2.  Installation dimension

Ceiling height is as shown in the figure.

Strong and durable ceiling

3,000 mm or more

1,800 mm to 

H

1,000 mm or more 

Floor

Obstruction

1,500 mm 
or more

256 mm or more (AUXM018,024,030)
298 mm or more (AUXK018,024,030,034,036,045,054)

H: Maximum height from floor to ceiling

Function setting

H (mm)

AUXM

018/024/030

AUXK

018/024/030/034

AUXK

036/045/054

Standard 

mode

3,000 3,200 3,200 

High Ceiling mode

3,500 

3,600 

4,200 

*  Be sure to make the function settings with the remote controller according to the 

installed ceiling height.

Discharge direction setting

• The discharge direction can be selected as shown below.

4 direction

3 direction

100 mm or more *1

*1:  Please ensure sufficient 

service access during 
installation.

*  Select the most appropriate airflow direction from 3 or 4 directions according to the 

shape of the room and the installation position.

*  When changing the number of outlets, we recommend using the optional AIR OUTLET 

SHUTTER PLATE KIT to close the outlet.

*  For the specific closing pattern, please refer to the attached AIR OUTLET SHUTTER 

PLATE KIT’S MANUAL. (Do so before installing the cassette grille as it will be installed 
on the body.)

3.3.  Installing the unit

 

WARNING

Install the air conditioner in a location which can withstand a load of at least 5 times the 
weight of the main unit and which will not amplify sound or vibration. If the installation 
location is not strong enough, the indoor unit may fall and cause injuries.

If the job is done with the panel frame only, there is a risk that the unit will come loose. 
Please take care.

3.3.1. Position the ceiling hole and hanging bolts

(1)  Positions of the ceiling opening, hanging bolt pitch, piping and ducts.
• Ceiling opening and hanging bolt pitch. (unit: mm)

950 (Cassette grille)

860 to 910 (Ceiling opening)

840 (Indoor unit)

796 (Hanging bolt pitch)

20 to 45

20 to 45

20 to 45

20 to 45

130

130

130

768 (Hanging bolt pitch)

950 (Cassette grille)

860 to 910 (Ceiling opening)

840 (Indoor unit)

200

130

50

A

B

50 to 100

10

39

200 to 205

Type

Dimension (mm)

A

B

AUXM

246

256

AUXK

288

298

• Refrigerant piping and drain piping positions. (unit: mm)

Drain pipe 
(Connect the attached 
drain hose)

342

293

45

200

140

180

10

80

Gas pipe

Liquid pipe

Drain pipe

• Distribution ducts and fresh air inlet positions.

Distribution duct 

connecting port

Distribution duct 
connecting port

Fresh air 
inlet position

Distribution duct 

connecting port

Distribution duct connecting port

Drain pipe

Refrigerant pipe

10 × Ø 3.2 hole

100

100

352

83

83

Cut out

90

163

Detailed diagram of distribution duct con-
necting port (4 sides)

250

4 × Ø 3.2 hole

Ø 70 
(cut out)

Ø 144 
(bolt pitch)

163

Fresh air inlet position

NOTE:

Conduct proper insulation when connecting the 
distribution ducts and fresh air inlet.
*  When sucking in the fresh air, please detach the 

insulation affixed to the drain pan.

Fresh air 
inlet position

Insulation

(2)  Setting the positions of hanging bolt and 

ceiling opening.

• Use an installation template (packaging top 

surface) to set the positions of the hanging bolt 
and ceiling opening and drill holes.

(3) Hanging 

structure.

• Select a strong structure for the hanging location.
• If necessary, reinforce the hanging bolt with quakeproof columnar support material to 

prevent shaking.

• Use hanging bolts of M8 to M10.

3.3.2. Hanging preparations

• Firmly fasten the hanging bolts as shown 

in the figure or by another method.

• Install the hanging bolts at a place 

where they would be capable of holding 
a weight of at least 490 N per bolt.

Hole-in anchor
Hole-in plug

Concrete

Insert

Hanging bolt M10 
(locally purchased)

3.3.3. Body installation

 

WARNING

Perform final tightening by tightening the double nut firmly.

Be sure to install the body horizontally and adjust the height below the body and the 
ceiling surface properly.

(1)  Install the attached 

washer and nut (prepared 
on site) onto the hang-
ing bolt.

(2)  Hook the body onto the 

hanging bolt.

(3)  Adjust the dimensions of 

the ceiling surface from 
the body.
After installing the 
cassette grille, you can 
make fine adjustment of 
the height of the body. 
For details, refer to the 
installation manual of the 
cassette grille.

Hanging bolt 
(locally purchased)

Nut A 
(locally purchased)

Washer 
(Accessories)

Washer 
(Accessories)

Nut B (Double Nut) 
(locally purchased)

30 mm or more

10 to 15 mm

After installing 
the body, tighten 
the nuts.

9371022642-02_IM.indb   3

9371022642-02_IM.indb   3

2019/10/11   10:00:39

2019/10/11   10:00:39

Содержание AUXK018GLEH

Страница 1: ...CI N UNIT INT RIEURE type cassette UNIDAD INTERIOR Tipo casete Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a cas...

Страница 2: ...sult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A r...

Страница 3: ...that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such...

Страница 4: ...ain piping positions unit mm Drain pipe Connect the attached drain hose 342 293 45 200 140 180 10 80 Gas pipe Liquid pipe Drain pipe Distribution ducts and fresh air inlet positions Distribution duct...

Страница 5: ...flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe a...

Страница 6: ...age may be blown out If it is impossible to have sufficient gradient of pipe perform drain lift up Pipe size Drain pipe VP25 O D 32 mm Hanging fittings 1 5 to 2 m VP25 O D 32 mm Downward gradient 1 10...

Страница 7: ...electricity charged in the body may cause malfunction of the PCB Follow the cautions below Establish an earth ground for the indoor and outdoor units and peripheral devices Cut power breaker off Touch...

Страница 8: ...en the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Strip 10 mm Ring termina...

Страница 9: ...re with solder IMPORTANT Be sure to insulate the connection between the wires Locally purchased Solder and insulate the connected parts Wire kit connector optional parts Wiring arrangement In followin...

Страница 10: ...e controller group operates in the same mode When function setting is Emergency stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF No...

Страница 11: ...AD 1 Factory setting 0 Rotary switch IU AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD SW as shown in the Table A for each refrigerant system Set to the same refrigeran...

Страница 12: ...ntral remote controller 01 Display only on central remote controller Fan set ting when cooling thermostat OFF 49 00 Follow the setting on the remote controller When set to 01 the fan stops when the th...

Страница 13: ...ed remote control ler error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expan...

Отзывы: