En-9
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
CNA01
CNA01
CNA01
DC power supply
12 to 24V
Connected unit
Load
resistance
P.C.B
P.C.B
P.C.B
Input
de
vic
e 1
Input
de
vic
e 2
Indo
or
unit
Indo
or
unit
Indo
or
unit
Load
resistance
●
Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
CNA02
*c
*c
*c
*d
CNA04
P.C.B
GND
Ch 1
Ch 3
Ch 2
Connected unit
*c: Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*d: The wiring is different from Apply voltage terminals. Be sufficiently careful when wiring.
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
K1
CNA02
CNA02
CNA02
K2
K3
K4
K5
K6
P
o
w
e
r s
u
p
p
ly
f
o
r r
e
la
y
Indo
or
unit
Indo
or
unit
Indo
or
unit
Input device 2
Input device 1
K1 - K6: Relay
(Device for DC Current)
P.C.B
P.C.B
P.C.B
NOTE :
When connected to multiple indoor units directly, it will cause breakdown.
Operation behavior
●
Input signal type
The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.
DIP switch [Set 2 SW2]
Input signal type
OFF (Factory setting)
Edge
ON
Pulse
Pulse
Edge
The width of pulse must be
longer than 200 msec.
●
When function setting is “Operation/Stop” mode.
[In the case of “Edge” input]
Connector
Input signal
Command
Ch1 of CNA01 or CNA02
OFF
→
ON
Operation
ON
→
OFF
Stop
[In the case of “Pulse” input]
Connector
Input signal
Command
CNA01 or CNA02
Ch1
OFF
→
ON
Operation
Ch2
OFF
→
ON
Stop
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
●
When function setting is “Emergency stop” mode.
[In the case of “Edge” input]
Connector
Input signal
Command
Ch1 of CNA01 or CNA02
OFF
→
ON
Emergency stop
ON
→
OFF
Normal
[In the case of “Pulse” input]
Connector
Input signal
Command
CNA01 or CNA02
Ch1
OFF
→
ON
Emergency stop
Ch2
OFF
→
ON
Normal
* All indoor units of same refrigerant system stops when Emergency stop operates.
●
When function setting is “Forced stop” mode.
[In the case of “Edge” input]
Connector
Input signal
Command
Ch1 of CNA01 or CNA02
OFF
→
ON
Forced stop
ON
→
OFF
Normal
[In the case of “Pulse” input]
Connector
Input signal
Command
CNA01 or CNA02
Ch1
OFF
→
ON
Forced stop
Ch2
OFF
→
ON
Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected
with function setting of indoor unit.
●
Forced thermostat off function
[“Edge” input only]
Function
setting
Connector
Input signal
Command
60-00
Ch3 of CNA03 or
CNA04
OFF
→
ON
Thermostat off
ON
→
OFF
Normal
●
Refrigerant leak detection function (only for J-IIIL series)
[“Edge” input only]
Function
setting
Connector
Input signal
Command
60-09
Ch3 of CNA03 or
CNA04
OFF
→
ON
No command
ON
→
OFF
Refrigerant leak
6.6.2. External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
●
When indicator etc. are connected directly
Operation
indicator
Error
indicator
Indoor unit Fan
status indicator
connected unit
P.C.B
CNB
01
9371022642-02_IM.indb 9
9371022642-02_IM.indb 9
2019/10/11 10:00:39
2019/10/11 10:00:39