When connected to Apply voltage terminals of multiple indoor units with a connected unit, 
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below 
example.

CNA01

CNA01

CNA01

DC power supply 
12 to 24V

Connected unit

Load 
resistance

P.C.B

P.C.B

P.C.B

Input

 

de

vic

e 1

Input

 

de

vic

e 2

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Load 
resistance

 Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 
contact terminal ([CNA02], [CNA04]).

CNA02

*c

*c

*c

*d

CNA04

P.C.B

GND

Ch 1

Ch 3

Ch 2

Connected unit

*c: Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*d: The wiring is different from Apply voltage terminals. Be sufficiently careful when wiring.

When connected to Dry contact terminals of multiple indoor units with a connected unit, 
insulate each indoor unit with relay, etc. as shown on below example.

K1

CNA02

CNA02

CNA02

K2

K3

K4

K5

K6

P

o

w

e

r s

u

p

p

ly

 f

o

r r

e

la

y

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Input device 2

Input device 1

K1 - K6: Relay

(Device for DC Current)

P.C.B

P.C.B

P.C.B

NOTE :

When connected to multiple indoor units directly, it will cause breakdown.

Operation behavior

 Input signal type

The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.

DIP switch [Set 2 SW2]

Input signal type

OFF (Factory setting)

Edge

ON

Pulse

Pulse

Edge

The width of pulse must be 
longer than 200 msec.

 When function setting is “Operation/Stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Operation

ON 

 OFF

Stop

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Operation

Ch2

OFF 

 ON

Stop

*  The last command has priority.
*  The indoor units within the same remote controller group operates in the same mode.

 When function setting is “Emergency stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Emergency stop

ON 

 OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Emergency stop

Ch2

OFF 

 ON

Normal

*  All indoor units of same refrigerant system stops when Emergency stop operates.

 When function setting is “Forced stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Forced stop

ON 

 OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Forced stop

Ch2

OFF 

 ON

Normal

*  When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a 

remote controller is restricted.

*  When forced stop function is used with forming a remote controller group, connect the 

same equipment to each indoor unit within the group.

• Selection method of functions
“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected 
with function setting of indoor unit.

 Forced thermostat off function

[“Edge” input only]

Function 

setting

Connector

Input signal

Command

60-00

Ch3 of CNA03 or 
CNA04

OFF 

 ON

Thermostat off

ON 

 OFF

Normal

 Refrigerant leak detection function (only for J-IIIL series)

[“Edge” input only]

Function 

setting

Connector

Input signal

Command

60-09

Ch3 of CNA03 or 
CNA04

OFF 

 ON

No command

ON 

 OFF

Refrigerant leak

6.6.2. External output

• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
• Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA

Output select

 When indicator etc. are connected directly

Operation 

indicator

Error 

indicator

Indoor unit Fan 
status indicator

connected unit

P.C.B

CNB 

01

9371022642-02_IM.indb   9

9371022642-02_IM.indb   9

2019/10/11   10:00:39

2019/10/11   10:00:39

Содержание AUXK018GLEH

Страница 1: ...CI N UNIT INT RIEURE type cassette UNIDAD INTERIOR Tipo casete Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a cas...

Страница 2: ...sult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A r...

Страница 3: ...that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such...

Страница 4: ...ain piping positions unit mm Drain pipe Connect the attached drain hose 342 293 45 200 140 180 10 80 Gas pipe Liquid pipe Drain pipe Distribution ducts and fresh air inlet positions Distribution duct...

Страница 5: ...flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe a...

Страница 6: ...age may be blown out If it is impossible to have sufficient gradient of pipe perform drain lift up Pipe size Drain pipe VP25 O D 32 mm Hanging fittings 1 5 to 2 m VP25 O D 32 mm Downward gradient 1 10...

Страница 7: ...electricity charged in the body may cause malfunction of the PCB Follow the cautions below Establish an earth ground for the indoor and outdoor units and peripheral devices Cut power breaker off Touch...

Страница 8: ...en the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Strip 10 mm Ring termina...

Страница 9: ...re with solder IMPORTANT Be sure to insulate the connection between the wires Locally purchased Solder and insulate the connected parts Wire kit connector optional parts Wiring arrangement In followin...

Страница 10: ...e controller group operates in the same mode When function setting is Emergency stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF No...

Страница 11: ...AD 1 Factory setting 0 Rotary switch IU AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD SW as shown in the Table A for each refrigerant system Set to the same refrigeran...

Страница 12: ...ntral remote controller 01 Display only on central remote controller Fan set ting when cooling thermostat OFF 49 00 Follow the setting on the remote controller When set to 01 the fan stops when the th...

Страница 13: ...ed remote control ler error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expan...

Отзывы: