En-18
7.6. Switching the upper limit of cooling
temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool
DIP switch setting
Set the DIP switch SET 4 SW3 referring to the Table C.
DIP switch “SET4”
SW
1
SW
2
SW
3
SW
4
ON
OFF
Table C
DIP switch SET 4 SW3
Cooling temperature setting range
OFF (Factory setting)
Standard (18 to 30 °C)
ON
Extension (18 to 32 °C)
NOTE :
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
7.7. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit ad-
dress settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number Default
Details
Filter indicator
interval
11
00
Default
○
Adjust the
fi
lter cleaning interval
noti
fi
cation. If the noti
fi
cation is too
early, change to setting 01. If the
noti
fi
cation is too late, change to
setting 02.
01
Longer
02
Shorter
Filter indicator
action
13
00
Enable
○
Enable or disable the
fi
lter indicator.
Setting 02 is for use with a central
remote controller.
01
Disable
02
Display
only on
central
remote
controller
Cool air
temperature
trigger
30
00
Default
○
Adjust the cool air trigger tempera-
ture. To lower the trigger tempera-
ture, use setting 01. To raise the
trigger temperature, use setting 02.
01
Adjust (1)
02
Adjust (2)
Heat air
temperature
trigger
31
00
Default
○
Adjust the heat air trigger tempera-
ture. To lower the trigger temperature
by 6 degrees C, use setting 01. To
lower the trigger temperature by 4
degrees C, use setting 02. To raise
the trigger temperature, use setting
03.
01
Adjust (1)
02
Adjust (2)
03
Adjust (3)
Auto restart
40
00
Enable
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency func-
tion such as for power failure etc.
Do not start and stop the indoor unit
by this function in normal operation.
Be sure to operate by the control
unit, converter or external input
device.
01
Disable
○
Cool Air
Prevention
43
00
Super low
○
Restrain the cold air
fl
ow with making
the air
fl
ow lower when starting heat-
ing operation. To correspond to the
ventilation, set to 01.
01
Follow the
setting on
the remote
controller
External
control
46
00
Start/Stop
○
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all
refrigerant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
01
Emergency
stop
02
Forced
stop
Error report
target
47
00
All
○
Change the target for reporting
errors. Errors can either be reported
in all locations, or only on the central
remote controller.
01
Display only
on central
remote
controller
Fan setting
when cooling
thermostat
OFF
49
00
Follow the
setting on
the remote
controller
○
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type
or 3-wire type) and switching its
thermistor are necessary.
01
Stop
8. TEST RUN
8.1. Test run using Outdoor unit (PCB)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
8.2. Test run using Remote Controller
• Refer to the Installation Manual for the remote controller to perform the test run using
the wireless remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicators
fl
ash slowly at the same time.
9374342273-01_IM.indb Sec1:18
9374342273-01_IM.indb Sec1:18
7/12/2012 10:19:47 AM
7/12/2012 10:19:47 AM
Содержание ARXD07GALH
Страница 21: ...9374342273 01_IM indb Sec1 20 9374342273 01_IM indb Sec1 20 7 12 2012 10 19 48 AM 7 12 2012 10 19 48 AM...
Страница 41: ...9374342273 01_IM indb Sec1 20 9374342273 01_IM indb Sec1 20 7 12 2012 10 20 37 AM 7 12 2012 10 20 37 AM...
Страница 61: ...9374342273 01_IM indb Sec1 20 9374342273 01_IM indb Sec1 20 7 12 2012 10 21 25 AM 7 12 2012 10 21 25 AM...
Страница 81: ...9374342273 01_IM indb Sec1 20 9374342273 01_IM indb Sec1 20 7 12 2012 10 22 14 AM 7 12 2012 10 22 14 AM...
Страница 101: ...9374342273 01_IM indb Sec1 20 9374342273 01_IM indb Sec1 20 7 12 2012 10 23 02 AM 7 12 2012 10 23 02 AM...
Страница 121: ...9374342273 01_IM indb Sec1 20 9374342273 01_IM indb Sec1 20 7 12 2012 10 23 55 AM 7 12 2012 10 23 55 AM...
Страница 141: ...9374342273 01_IM indb Sec1 20 9374342273 01_IM indb Sec1 20 7 12 2012 10 24 44 AM 7 12 2012 10 24 44 AM...
Страница 161: ...9374342273 01_IM indb Sec1 20 9374342273 01_IM indb Sec1 20 7 12 2012 10 25 38 AM 7 12 2012 10 25 38 AM...