En-8

A. For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable.

(2)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3) Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(5)  See the table for the terminal screw tightening torques.
(6)  Please do not 

fi

 x 2 power supply cables with 1 screw.

Loop

Screw with 
special washer

Screw with 
special washer

Cable end (Loop)

Cable end (Loop)

Cable

Cable

Terminal block

Strip 31/32 in.  

(25 mm)

 

WARNING

When using solid core cables, do not use the ring terminal. If you use the solid core 
cables with the ring terminal, the ring terminal’s pressure bonding may malfunction 
and cause the cables to abnormally heat up.

B. For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table for the terminal screw tightening torques.
(7)  Please do not 

fi

 x 2 power supply cables with 1 screw.

 Sleeve

Screw with 
special washer

Screw with 
special washer

Ring terminal

Cable

Cable

Terminal block

Ring terminal

Ring terminal

Strip 13/32 in.

(10 mm)

 

WARNING

Use ring terminals and tighten the terminal screws to the speci

fi

 ed torques, otherwise, 

abnormal overheating may be produced and possibly cause heavy damage inside the unit.

Tightening torque

M4 screw 

(Power supply/L1, L2 (N), GND)

11 to 16 lbf·in 

(1.2 to 1.8 N·m)

6.3.2. Transmission and Remote controller cable

Shielded wire 

(no 

fi

 lm)

1-3/8 in. (35 mm)

31/32 in. (25 mm)

Transmission cable

25/32 in. (20 mm)

Remote controller cable

•  Connect remote controller and transmission cables as shown in Fig. B.
•  When the 2 cables are attached.

Fig. B

Screw

Terminal block

Cable of the 

same caliber: 

Good

Cable of the 

different caliber: 

Prohibited

Cable

 

WARNING

Tighten the terminal screws to the speci

fi

 ed torques, otherwise, abnormal overheating 

may be produced and possibly cause heavy damage inside the unit.

Tightening torque

M3.5 screw 

(Transmission/X1, X2) 

(Remote controller/Y1, Y2, Y3)

7.1 to 8.9 lbf·in 

(0.8 to 1.0 N·m)

 

CAUTION

To peel the 

fi

 lm from the lead cable, use a dedicated tool that will not damage the 

conductor cable.

When installing a screw on the terminal block, do not cut the cable by overtightening 
the screw. On the other hand, an under tightened screw can cause faulty contact, 
which will lead to a communication failure.

1

6.4. Connection of wiring

(1)  Remove the control box cover and install each connection cable.

Loosen the screws. 
(2 locations)

Cover box

9373870098-02_IM.indb   8

9373870098-02_IM.indb   8

12/28/2011   4:45:59 PM

12/28/2011   4:45:59 PM

Содержание ARUH36RLAV

Страница 1: ...Duct type APPAREIL INT RIEUR Type conduit UNIDAD INTERIOR Tipo de ducto UNIDADE INTERIOR Tipo de duto For authorized service personnel only Uniquement r serv aux techniciens agr s S lo para personal...

Страница 2: ...It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water...

Страница 3: ...act with a flame it produces a toxic gas 1 2 2 Special tool for R410A WARNING To install a unit that uses R410A refrigerant use dedicated tools and piping materials that have been manufactured specifi...

Страница 4: ...t least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you could st...

Страница 5: ...less at 68 F 20 C 1 4 3 Flare connection pipe connection 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe d...

Страница 6: ...m the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime...

Страница 7: ...onnect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction elec...

Страница 8: ...r use a breaker with large capacitance 6 1 1 Transmission and remote controller wiring specifications Follow the specifications below for the transmission and remote controller cable Cable size Wire t...

Страница 9: ...event the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fi...

Страница 10: ...External input terminals Indoor unit can be Start Stop or Emergency stop by using indoor unit PCB CN27 Wiring methods and specifications A twisted pair cable 22AWG should be used Maximum length of ca...

Страница 11: ...ON Forced stop Ch2 OFF ON Normal When the forced stop is triggered indoor unit stops and Start Stop operation by a remote controller is restricted When forced stop function is used with forming a remo...

Страница 12: ...or is connected set the function setting of indoor unit as indicated below Function Number 30 Set the Setting Number to 00 Default Function Number 31 Set the Setting Number to 02 Refer to 7 3 Function...

Страница 13: ...FF the power before performing the field setting 1 7 1 Setting the address Manual address setting method The indoor unit address and the refrigerant circuit address can also be set up through the wire...

Страница 14: ...n the power of the indoor unit ON before starting the setting Turning on the power to the indoor units initializes EEV so make sure the piping air tight test and vacuuming have been conducted before t...

Страница 15: ...the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage Are the inlets and outlets free of any obstacles No cooling No heating...

Отзывы: