En-10
Operation behavior
• Input signal type
The input signal type can be selected.
It is switched by Dip-sw on the indoor unit PCB.
Dip-sw [Set 2-2]
Input signal type
OFF
Edge
ON
Pulse
• When function setting is “Start/Stop” mode [In the case of “Edge” input]
Connector
Input signal
Command
Ch1 of CN27
OFF
→
ON
Operation
ON
→
OFF
Stop
1
2
3
Ch 1
Connected unit
P.C.B
CN27
[In the case of “Pulse” input]
Connector
Input signal
Command
CN27
Ch1
OFF
→
ON
Operation
Ch2
OFF
→
ON
Stop
1
2
3
Ch 2
Ch 1
Connected unit
P.C.B
CN27
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
• When function setting is “Emergency stop” mode. [In the case of “Edge” input]
Connector
Input signal
Command
Ch1 of CN27
OFF
→
ON
Emergency stop
ON
→
OFF
Normal
[In the case of “Pulse” input]
Connector
Input signal
Command
CN27
Ch1
OFF
→
ON
Emergency stop
Ch2
OFF
→
ON
Normal
• When function setting is “Forced stop” mode In the case of “Edge” input
Connector
Input signal
Command
Ch1 of CN27
OFF
→
ON
Forced stop
ON
→
OFF
Normal
In the case of “Pulse” input
Connector
Input signal
Command
CN27
Ch1
OFF
→
ON
Forced stop
Ch2
OFF
→
ON
Normal
* When the forced stop is triggered, indoor unit stops and Start/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group.
• Selection method of functions
“Start/Stop” mode or “Emergency stop”, “Forced stop” mode can be selected with
function setting of indoor unit.
(2) External output terminals
• When picking up output signals for operating status, abnormal conditions or indoor unit
status.
Wiring methods and speci
fi
cations
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft. (150 m)
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Operation behavior
Connector
Output voltage
Status
CN22
12V
Operation
0V
Stop
CN23
12V
Error
0V
Normal
CN24
12V
Indoor unit fan operation
0V
Indoor unit fan stop
Output voltage : Hi DC12V ± 2V
Lo
0V
Permissible current : 15mA
1
2
+
-
Connected unit
Operation
indicator
P.C.B
CN22
1
2
+
-
1
2
+
-
Connected unit
Connected unit
Indoor unit
fan status
indicator
Error
indicator
P.C.B
P.C.B
CN24
CN23
Edge
Pulse
The width of pulse
must be longer
than 200msec.