En-5

Pipe outside diameter 

[in. (mm)]

Dimension A [in. (mm)]

Dimension B

 0 (0)

-0.015 (-0.4) 

[in. (mm)]

Flare tool for R410A, 

clutch type

1/4 (6.35)

0 to 0.020 

(0 to 0.5)

11/32 (9.1)

3/8 (9.52)

17/32 (13.2)

1/2 (12.70)

21/32 (16.6)

5/8 (15.88)

25/32 (19.7)

3/4 (19.05)

15/16 (24.0)

When using conventional (R22) 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should 

be approximately 0.02 in. (0.5 mm) more than indicated in the table (for 

fl

 aring with R410A 

fl

 are tools) to achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the dimen-

sion A. It is recommended that a R410A 

fl

 aring tool is used.

Pipe outside diameter 

[in. (mm)]

Width across flats of Flare 

nut [in. (mm)]

1/4 (6.35)

21/32 (17)

3/8 (9.52)

7/8 (22)

1/2 (12.70)

1-1/32 (26)

5/8 (15.88)

1-5/32 (29)

3/4 (19.05)

1-13/32 (36)

4.3.2. Bending pipes

The pipes are shaped by your hands or pipe bender. Be careful not to collapse them.

• 

Do not bend the pipes in an angle more than 90°.

• 

When pipes are repeatedly bend or stretched, the material will harden, making it dif

fi

 cult 

• 

to bend or stretch them any more. Do not bend or stretch the pipes more than 3 times.

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. 

If the pipe is bent repeatedly at the same place, it will break.

4.3.3. Pipe connection

When the 

fl

 are nut is tightened properly by your hand, hold the body side coupling with a 

separate spanner, then tighten with a torque wrench.

 

CAUTION

Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to 
tighten the 

fl

 are nut correctly.

Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

Connection pipe

Torque wrench

Indoor unit pipe 
(Body side)

Tighten with 2 wrenches.

Holding wrench

Flare nut

 

CAUTION

Be sure to apply the pipe against the port on the indoor unit and the outdoor unit 
correctly. If the centering is improper, the 

fl

 are nut cannot be tightened smoothly. If the 

fl

 are nut is forced to turn, the threads will be damaged.

Do not remove the flare nut from the indoor unit pipe until immediately before 
connecting the connection pipe.

Do not use mineral oil on 

fl

 ared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

Flare nut [in. (mm)]

Tightening torque [lbf·ft. (N·m)]

1/4 (6.35) dia.

11.8 to 13.3 (16 to 18)

3/8 (9.52) dia.

23.6 to 31.0 (32 to 42)

1/2 (12.70) dia.

36.1 to 45.0 (49 to 61)

5/8 (15.88) dia.

46.5 to 55.3 (63 to 75)

3/4 (19.05) dia.

66.4 to 81.1 (90 to 110)

]1

4.4. Installing heat insulation

Install the coupler heat insulation after completing the refrigerant leak check (for details, 
refer to the Installation Manual for the outdoor unit).

Coupler heat 
insulation
(Accessories)

Binder (Large) 
(Accessories)

Heat insulation

Cover this portion with 
heat insulation.

 

CAUTION

There should be no gaps between the insulation and the product.

5.  INSTALLING DRAIN PIPES

]

•  Use general hard polyvinyl chloride pipe ø 3/4 in. [I.D.], ø 1-1/16 in. [O.D.] and connect 

it with adhesive (polyvinyl chloride) so that there is no leakage.

•  The position of the installed drain pipe should have a downward gradient of 1/100 or 

more.

•  To prevent the pipe from freezing, use a heat insulation material as needed.

Position of drain piping

4-1/4 (108)

5-15/32 (139)

Main drain port

Safety drain port

1-5/8 (41)

4-27/32 (123)

8-3/16 (208)

14-1/32 (356)

14-19/32 (371)

Unit: in. (mm)

Pipe size

Drain pipe

• For main drain port

• For safety drain port

Φ

 3/4 in. (19 mm) [I.D.], 

Φ

 1-1/16 in. (27 mm) [O.D.]

•  This product has drain ports in 2 locations. Follow the procedure in the 

fi

 gure to connect 

drain hose and drain pipes to each of them.

INSTALL THE DRAIN HOSE TO THE MAIN AND SAFETY 
DRAIN PORT

Working procedure
(1)   Install the attached drain hose to the main and safety drain port of the body. Install 

the hose band from the top of the hose within the graphic display area. Secure 

fi

 rmly 

with the hose band.

(2)   Use vinyl adhesive agent to glue the drain piping (PVC pipe) [

Φ

 3/4 in. (19 mm) I.D. 

Φ

 1-1/16 in. (27 mm) O.D.] which is prepared on site or piping socket. (Apply color 

adhesive agent evenly until the gauge line and seal)

(3)   Check the drainage. 
(4)   Install the heat insulation.
(5)   Use the attached heat insulation to insulate the drain port and band parts of the body.

Drain hose
(Accessories)

13/32 to 19/32 
(10 to 15)

Hose Band
    (Accessories)

Soft PVC side

Ensure there is no space

Drain pan

Unit: in. (mm)

Width across 

fl

 ats

9373870098-02_IM.indb   5

9373870098-02_IM.indb   5

12/28/2011   4:45:57 PM

12/28/2011   4:45:57 PM

Содержание ARUH36RLAV

Страница 1: ...Duct type APPAREIL INT RIEUR Type conduit UNIDAD INTERIOR Tipo de ducto UNIDADE INTERIOR Tipo de duto For authorized service personnel only Uniquement r serv aux techniciens agr s S lo para personal...

Страница 2: ...It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water...

Страница 3: ...act with a flame it produces a toxic gas 1 2 2 Special tool for R410A WARNING To install a unit that uses R410A refrigerant use dedicated tools and piping materials that have been manufactured specifi...

Страница 4: ...t least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you could st...

Страница 5: ...less at 68 F 20 C 1 4 3 Flare connection pipe connection 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe d...

Страница 6: ...m the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime...

Страница 7: ...onnect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction elec...

Страница 8: ...r use a breaker with large capacitance 6 1 1 Transmission and remote controller wiring specifications Follow the specifications below for the transmission and remote controller cable Cable size Wire t...

Страница 9: ...event the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fi...

Страница 10: ...External input terminals Indoor unit can be Start Stop or Emergency stop by using indoor unit PCB CN27 Wiring methods and specifications A twisted pair cable 22AWG should be used Maximum length of ca...

Страница 11: ...ON Forced stop Ch2 OFF ON Normal When the forced stop is triggered indoor unit stops and Start Stop operation by a remote controller is restricted When forced stop function is used with forming a remo...

Страница 12: ...or is connected set the function setting of indoor unit as indicated below Function Number 30 Set the Setting Number to 00 Default Function Number 31 Set the Setting Number to 02 Refer to 7 3 Function...

Страница 13: ...FF the power before performing the field setting 1 7 1 Setting the address Manual address setting method The indoor unit address and the refrigerant circuit address can also be set up through the wire...

Страница 14: ...n the power of the indoor unit ON before starting the setting Turning on the power to the indoor units initializes EEV so make sure the piping air tight test and vacuuming have been conducted before t...

Страница 15: ...the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage Are the inlets and outlets free of any obstacles No cooling No heating...

Отзывы: