En-17

Test operation setting method

Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the indoor unit PC board to 
con

fi

 gure settings according to the procedures below.

Settings for starting test run 
operation

Settings for stopping test run 
operation

Press the “ENTER” button for 
more than 3 seconds.

Press the “ENTER” button for 
more than 3 seconds.

Press the “ENTER” button for 
more than 3 seconds.

Press the “ENTER” button for 
more than 3 seconds.

This will be dis-
played when the 
cooling operation 
mode is canceled.

This will be dis-
played when the 
heating operation 
mode is canceled.

This will be dis-
played when the 
cooling test opera-
tion is complete.

This will be dis-
played when the 
heating test opera-
tion is complete.

This will be 
displayed after 5 
seconds.

This will be 
displayed after 5 
seconds.

This will be 
displayed after 5 
seconds.

This will be 
displayed after 5 
seconds.

First 2 digits Last 2 digits

(When [F4] to [F9] are displayed, continue to 
press the SELECT button until [F3] is displayed.)

For heating operation, press the “SE-
LECT” button until “01” is displayed.

Function settings

EXIT

After the test operation is complete, turn off the power. Attach the cover of the electrical 
component box and the front panel of the outdoor unit.

NOTE:

•  Check that the indoor and outdoor units connected to the same refrigerant system are 

operating normally.

•  When indoor or outdoor units are not operating, or when the indoor and outdoor units 

of other refrigerant systems are operating, the indoor/outdoor unit address are not 
con

fi

 gured correctly.

•  The system will not operate normally with an incorrect DIP switch setting.

Stop the system immediately and recheck the DIP switch setting.

9.1.3 Error displays

•  When error occurs, “Err” and “Number of errors occurred” are alternately displayed on 

the 7 segment display every 1 second.

•  For the content of error, please refer to the “10.2. Error codes”.
•  When error codes are displayed, all the error codes can be con

fi

 rmed by pressing the 

“SELECT” button.

Example:

When “Indoor unit capacity error [E221]” and “Indoor unit duplicate address error [E261]” 
occurred.

(*1)

(*2)

(*1) When the address of the overlap indoor 

unit is displayed, press and hold the “EN-
TER” button for more than 3 seconds.

(*2) When errors other than the address of 

the overlap indoor unit exist, press “SE-
LECT” button to switch to the next error.

If error occurs, it will display “-”.

[Ad + address number]

9.2. Test 

run

Before the test operation, check the following items.
(1) Is 

there 

gas 

leakage? 

(At 

pipe 

connections 

{

fl

 ange connections and brazed areas})

(2)  Is the system charged with the speci

fi

 ed volume of refrigerant?

(3)  Is the refrigerant circuit address correct?
(4)  Is a breaker installed at the power supply cable of outdoor unit?
(5)  Are the cable connected to the terminals without looseness, and in accordance with 

the speci

fi

 cations?

(6)  Are the initial settings of the switches of the outdoor unit correctly con

fi

 gured?

(7)  Is the 3-way valve of the outdoor unit open? (Gas pipe and liquid pipe)
(8)  Is power supplied to the crank case heater for more than 12 hours? Electricity current 

in short period of time may result in compressor damage.

(9) Are 

all 

the 

indoor 

units 

within the same coolant system connected to the power? Op-

erating indoor units which are not connected to the power may result in malfunctions.

(10) Is Indoor unit connection check performed? Test run doesn't operate if Indoor unit 

connection check is not performed.

After checking that the above items are all in order, refer to “9.3. 
Test run method” to test operation the unit.
If there are problems, adjust immediately and recheck.

9.3.  Test run method

Be sure to con

fi

 gure test run settings only when the outdoor unit has stopped oper-

ating.

•  Depending on the communication status between the indoor and outdoor units, it may 

take several minutes for the system to start operating after settings for the test run are 
complete.

•  After the test run settings are complete, the outdoor unit and the connected indoor 

units will start operating. Room temperature control will not activate during test opera-
tion (continuous operation).

•  If a knocking sound can be heard in the liquid compression of the compressor, stop 

the unit immediately and then energize the crank case heater for a suf

fi

 cient length of 

time before restarting the operation.

Perform test operation for each refrigerant system.
You can set “cooling test operation" or “heating test operation” with the push button on the 
outdoor unit PC board.

9380545170_IM.indb   17

9380545170_IM.indb   17

5/19/2016   2:23:17 PM

5/19/2016   2:23:17 PM

Содержание AJH040LBLAH

Страница 1: ... DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli için ...

Страница 2: ...c shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation m...

Страница 3: ...n or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failur...

Страница 4: ...e installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out ...

Страница 5: ...of the unit Otherwise the suction grilles on the sides of the unit may be deformed Front view Rear view Fig B Handle Handle Suction grille Fig A 3 5 Installing the unit Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure ba...

Страница 6: ...n method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 4 SYSTEM CONFIGURATION 4 1 System configuration CAUTION Always keep to the limit on the total amount of refrigerant...

Страница 7: ...ontal line View D View C Horizontal line Vertical line Gas pipe Liquid pipe Outdoor unit side Outdoor unit side H1 0 to 10 mm H2 0 to 10 mm α1 0 to 1 β1 10 to 10 α2 0 to 1 β2 10 to 10 PROHIBITED CAUTION Do not connect a separation tube after a header Leave the distance 0 5 m or more for straight part to branch tube and header Main pipe 0 5 m or more To indoor unit To indoor unit To indoor unit Mai...

Страница 8: ...ve any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked o...

Страница 9: ...breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is installed outdoors place it und...

Страница 10: ...g 2 NOTE Do not use loop wiring This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 F H L G K J E 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enab...

Страница 11: ...rminal Sleeve Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent...

Страница 12: ... This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity ...

Страница 13: ...efrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Set when necessary Perform settings after all indoor units have...

Страница 14: ...s Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Continue to press the SELECT button until the desired number app...

Страница 15: ...e 7 segment display When ERROR is displayed inspect the units Use the MODE EXIT SELECT and ENTER buttons on the outdoor unit PC board to configure settings according to the procedures below 1 Function setting The display when the main power is turned on When F4 to F9 are displayed continue to press the SELECT button until F3 is displayed Press the SELECT button until 11 is displayed Press the ENTE...

Страница 16: ...uation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe...

Страница 17: ... has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units Fig A Putty Insulation 9 TEST RUN 9 1 Indoor unit connection check Normal operation will not be possible without performing the Indoor unit connection check 9 1 1 Things to confirm before startin...

Страница 18: ...he EN TER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SE LECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation check the following items 1 Is there a gas leakage At pipe connections flange connections and brazed areas 2 Is the system charged with the specified v...

Страница 19: ...r E 8 3 2 Outdoor unit liquid pipe temp thermistor 2 error E 8 4 1 Outdoor unit current sensor 1 error permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 ...

Отзывы: