background image

En-12

24

(Forbidden)

2

4

0

0

(Factory default)

25

(Forbidden)

2

5

0

0

(Factory default)

26

(Forbidden)

2

6

0

0

(Factory default)

27

(Forbidden)

2

7

0

0

(Factory default)

28

(Forbidden)

2

8

0

0

(Factory default)

29

(Forbidden)

2

9

0

0

(Factory default)

30

Energy saving 
level setting *1

Level 1 (stop)

3

0

0

0

Level 2 
(operated at 40% capacity)

0

1

Level 3 
(operated at 60% capacity)

0

2

Level 4 
(operated at 80% capacity)

0

3

Level 5 
(operated at 100% capacity)

0

4

The capacity limit can be selected by the external input terminal (CN133) when operating 
with the “Energy Saving Peak Cut function”.
The lower the level, the more the effect of energy saving, but the cooling/heating perfor-
mance will also drop.

31

(Forbidden)

3

1

0

0

(Factory default)

34

(Forbidden)

3

4

0

0

(Factory default)

35

(Forbidden)

3

5

0

0

(Factory default)

36

(Forbidden)

3

6

0

0

(Factory default)

37

(Forbidden)

3

7

0

0

(Factory default)

40

Capacity prior-
ity setting (in low 
noise mode) *1

Off (quiet priority)

4

0

0

0

On (capacity priority)

0

1

If the cooling/heating performance becomes insuf

fi

 cient when the low noise mode is set, it is pos-

sible to set “capacity priority” that automatically cancels the low noise mode (once performance is 
restored, the mode will automatically return to the low noise mode).

41

Low noise mode 
setting *1

Off (Normal)

4

1

0

0

On (Low noise mode)

0

1

42

(Forbidden)

4

2

0

0

(Factory default)

60

(Forbidden)

6

0

0

0

(Factory default)

61

(Forbidden)

6

1

0

0

(Factory default)

62

(Forbidden)

6

2

0

0

(Factory default)

70

Electricity meter 
No. setting 1 *2

Setting number (x00)

7

0

0

0

Setting number (x01)

0

1

······

···

···

Setting number (x98)

9

8

Setting number (x99)

9

9

Set the ones digit and tens digit of the No. of the electricity meter connected to CN135.

71

Electricity meter 
No. setting 2 *2

Setting number (0xx)

7

1

0

0

Setting number (1xx)

0

1

Setting number (2xx)

0

2

Set the hundreds digit of the No. of the electricity meter connected to CN135.

72

Electricity meter 
pulse setting 1 *3

Setting number (xx00)

7

2

0

0

Setting number (xx01)

0

1

······

···

···

Setting number (xx98)

9

8

Setting number (xx99)

9

9

Set the ones digit and tens digit of the No. of the electricity meter pulse setting connected 
to CN135.

7.3.  Rotary switch setting

The rotary switch (REF AD) sets the refrigerant circuit address of the outdoor unit. Con

fi

 g-

ure the settings only on the master unit of a refrigerant system.
If multiple refrigerant systems are connected, set the rotary switch (REF AD) as shown in 
the table below.

Refrigerant 

circuit 

address

Rotary 
Switch 

Setting

Setting

Setting 

range

Type of switch

REF AD

×10

×1

Refrigerant 
circuit 
address

0–99

Setting 
example
63

0

0

0

1

0

1

2

0

2

REF AD × 10 REF AD × 1

Rotary Switch (REF AD × 1): Factory setting “0”
Rotary Switch (REF AD × 10): Factory setting “0”

98

9

8

99

9

9

7.4.  Push button setting

Various functions can be set. Set when necessary.
Perform settings after all indoor units have stopped operation.

Table. A:  List  of  Settings

No

Setting Item

7 segment display

Factory 

default

First 2 digits Last 2 digits

00

Pipe length setting 
*1

Standard (40 to 65 m)

0

0

0

0

Short (less than 40 m)

0

1

Medium (65 to 90 m)

0

2

Long 1 (90 to 120 m)

0

3

Pipe length means the length between master outdoor unit and the nearest indoor unit.

10

(Forbidden)

1

0

0

0

(Factory default)

11

Cooling capacity 
shift *1

Normal mode

1

1

0

0

Save energy mode

0

1

High power mode 1

0

2

High power mode 2

0

3

(Forbidden)

0

4

Set this item when necessary.

12

Heating capacity 
shift *1

Normal mode

1

2

0

0

Save energy mode

0

1

High power mode 1

0

2

High power mode 2

0

3

Set this item when necessary.

13

(Forbidden)

1

3

0

0

(Factory default)

14

(Forbidden)

1

4

0

0

(Factory default)

20

Switching between 
batch stop or 
emergency stop *1

Batch stop

2

0

0

0

Emergency stop

0

1

This mode selects the pattern of the stop function to be operated by the external input 
terminal (CN134).
•  Batch stop: The stop of all indoor units connected to same refrigerant system due to 

input signal coming from CN134.

•  Emergency stop: When emergency stop is actuated, the indoor unit does not accept the 

operation command from the remote controller. On the other hand, when the emergency 
stop is released (no input from CN134), the air conditioner does not return to the original 
operation until the indoor unit is turned on by the remote controller.

21

Operation mode 
selecting method 
*1

Priority given to the 

fi

 rst command

2

1

0

0

Priority given to external input 
of outdoor unit

0

1

Priority given to administrative 
indoor unit

0

2

Select the priority setting of the operation mode.
• Priority given to the 

fi

 rst command: Priority is given to the operation mode which is set 

fi

 rst.

•  Priority given to external input of outdoor unit: Priority is given to the operation mode 

which is set by the external input terminal (CN132).

•  Priority given to administrative indoor unit: Priority is given to the operation mode of the 

administrative indoor unit which is set by the wired remote controller.

22

(Forbidden)

2

2

0

0

(Factory default)

23

(Forbidden)

2

3

0

0

(Factory default)

9380545170_IM.indb   12

9380545170_IM.indb   12

5/19/2016   2:23:17 PM

5/19/2016   2:23:17 PM

Содержание AJH040LBLAH

Страница 1: ... DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli için ...

Страница 2: ...c shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation m...

Страница 3: ...n or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failur...

Страница 4: ...e installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out ...

Страница 5: ...of the unit Otherwise the suction grilles on the sides of the unit may be deformed Front view Rear view Fig B Handle Handle Suction grille Fig A 3 5 Installing the unit Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure ba...

Страница 6: ...n method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 4 SYSTEM CONFIGURATION 4 1 System configuration CAUTION Always keep to the limit on the total amount of refrigerant...

Страница 7: ...ontal line View D View C Horizontal line Vertical line Gas pipe Liquid pipe Outdoor unit side Outdoor unit side H1 0 to 10 mm H2 0 to 10 mm α1 0 to 1 β1 10 to 10 α2 0 to 1 β2 10 to 10 PROHIBITED CAUTION Do not connect a separation tube after a header Leave the distance 0 5 m or more for straight part to branch tube and header Main pipe 0 5 m or more To indoor unit To indoor unit To indoor unit Mai...

Страница 8: ...ve any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked o...

Страница 9: ...breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is installed outdoors place it und...

Страница 10: ...g 2 NOTE Do not use loop wiring This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 F H L G K J E 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enab...

Страница 11: ...rminal Sleeve Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent...

Страница 12: ... This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity ...

Страница 13: ...efrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Set when necessary Perform settings after all indoor units have...

Страница 14: ...s Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Continue to press the SELECT button until the desired number app...

Страница 15: ...e 7 segment display When ERROR is displayed inspect the units Use the MODE EXIT SELECT and ENTER buttons on the outdoor unit PC board to configure settings according to the procedures below 1 Function setting The display when the main power is turned on When F4 to F9 are displayed continue to press the SELECT button until F3 is displayed Press the SELECT button until 11 is displayed Press the ENTE...

Страница 16: ...uation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe...

Страница 17: ... has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units Fig A Putty Insulation 9 TEST RUN 9 1 Indoor unit connection check Normal operation will not be possible without performing the Indoor unit connection check 9 1 1 Things to confirm before startin...

Страница 18: ...he EN TER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SE LECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation check the following items 1 Is there a gas leakage At pipe connections flange connections and brazed areas 2 Is the system charged with the specified v...

Страница 19: ...r E 8 3 2 Outdoor unit liquid pipe temp thermistor 2 error E 8 4 1 Outdoor unit current sensor 1 error permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 ...

Отзывы: