6.5.2 Wiring procedure
• Remove the service panel. And connect the cable to the terminal in accordance with the
terminal name plate.
• Use a ring terminal to connect the electric cables to the power supply terminal board.
• Keep the earth cable longer than the other cables.
• After connecting the electric cable, secure them with a cable clamp.
• Connect the cable without applying excessive tension.
• Use the speci
fi
ed cable type and connect the cable securely.
Secure with a cable
clamp as shown in the
fi
gure below.
Tightening
torque
M3 screw
0.5 to 0.6 N·m (5 to 6 kgf·cm)
M5 screw
2.0 to 3.0 N·m (20 to 30 kgf·cm)
Power supply terminal
Ring terminal (M5)
Transmission terminal (M3)
About 550 mm
Power supply cable
Power supply
cable
Transmission cable
Transmission cable
About 520 mm
Cable tie
(accessory)
Cable tie
(accessory)
Cable
clamp
Cable tie
Earth (ground)
cable
8 to 1
0 mm
45 to 50 mm
25 to
40 mm
25 to
30 mm
How to connect wiring to the terminal
Caution when wiring cable
(1) Use ring terminals with insulating sleeves as shown in the
fi
gure to connect to the
terminal block.
(2) Securely
clamp
the
ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
(3) Use
the
speci
fi
ed cables, connect them securely, and fasten them so that there is
no stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent
the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table below for the terminal screw tightening torques.
Strip 10 mm
Cable
Screw with
special washer
Ring terminal
Terminal block
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Cable
Shielding the transmission cable
Connect both ends of the shielded wire of the transmission cable to the earth (ground)
terminal of the equipment or to the earth (ground) screw near the terminal.
Be sure to use one side of a twisted-pair cable when using transmission cable with 2 sets
of twisted-pair cables.
Wind with insulation tape to prevent short circuit
Use one side of the
twisted-pair cable
Connect both ends of shielded wire to earth (Ground).
6.6. External input and external output
6.6.1 Terminal position
Base heater
(CN115: Black)
Outdoor unit PC board
Input 4
(CN134: Red)
Input 3
(CN133: White)
Input 2
(CN132: Green)
Input 1
(CN131: Yellow)
Input 5
(CN135:
Orange)
Output 1
(CN136:
Black)
Output 2
(CN137:
Blue)
CAUTION
Do not bundle the cable for base heater with other cables.
When connecting cable to Input 2
Cable (for external
input and output)
Cable tie (tightened with transmission cable)
Cable (for external input and output)
* If the outdoor unit is not installed in the wall, cover the
exposed part of cable with a 1 mm thick or more insula-
tion
tubing.
About 550 mm
6.6.2 External input terminal
Setting to low noise mode, cooling priority/heating priority selection, outdoor unit operation
peak control setting, emergency/batch stop and electricity meter pulse are possible from
the outside.
Wiring method and speci
fi
cations
* A twisted pair cable (22 AWG (0.33 mm²)) should be used. Maximum length of cable is
150 m.
* Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed
* For each input, pin No. 1 is of positive polarity and pin No. 2 is of ground level.
connected unit connected unit connected unit
connected unit connected unit
Input1
CN131
(Yellow)
Input2
CN132
(Green)
Input3
CN133
(White)
Input4
CN134
(Red)
Input5
CN135
(Orange)
P.C.B