En-15

8.  PIPE INSTALLATION II

Fig. A Connection system

Fig. B

Outdoor unit

Pressure 
gauge

Vacuum 
pump

Scale

Pressure regu-
lating valve

Nitrogen

Indoor 
unit

Indoor 
unit

Service hose 
with valve core

Charging 
port

Charging 
port cap

3-way 
valve

Connecting 
pipe

Blank cap

Hexagon wrench
4 mm (5/32")

Table. A

Pipe

3-way valve

Blank cap

Charging  port  cap

Liquid valve

7.0 to 9.0 N·m

(70 to 90 kgf·cm)

20.0 to 25.0 N·m

(200 to 250 kgf·cm)

12.5 to 16.0 N·m

(125 to 160 kgf·cm)

Gas valve

11.0 to 13.0 N·m

(110 to 130 kgf·cm)

30.0 to 35.0 N·m

(300 to 350 kgf·cm)

12.5 to 16.0 N·m

(125 to 160 kgf·cm)

8.1. Sealing 

test

CAUTION

Use only nitrogen gas.
Never use refrigerant gas, oxygen, in 

fl

 ammable gas or poisonous gas to pressurize the 

system. (If oxygen is used, there is the danger of an explosion.)

Do not apply shock during sealing test.
It can rupture the pipes and cause serious injury.

Do not turn on the power unless all operations are complete.

Do not block the walls and the ceiling until the sealing test and the charging of the refrig-
erant gas have been completed.

After connecting the pipes, perform an sealing test.
Recheck that the 3-way valve are closed before performing a sealing test. 
(Fig. B)
Pour nitrogen gas through both the liquid pipe and the gas pipe.
Pressurize nitrogen gas to 4.2 MPa to perform the sealing test.

Check all 

fl

 are connection areas and brazed areas.

Then, check that the pressure has not decreased.
Compare the pressures after pressurizing and letting it stand for 24 hours, and check that 
the pressure has not decreased.
*  When the outdoor temperature changes 5 °C, the test pressure changes 0.05 MPa.

If the pressure has dropped, the pipe joints may be leaking.

If a leakage is found, immediately repair it and perform a sealing test again.
*  Decrease the pressure of nitrogen gas before blazing
After completing the sealing test, release the nitrogen gas from both valves.
Release the nitrogen gas slowly.

8.2. Vacuum 

process

CAUTION

Do not turn on the power unless all operations are complete.

If the system is not evacuated suf

fi

 ciently, its performance will drop.

Be sure to evacuate the refrigerant system using a vacuum pump.

The refrigerant pressure may sometimes not rise when a closed valve is opened after 
the system is evacuated using a vacuum pump. This is caused by the closure of the 
refrigerant system of the outdoor unit by the electronic expansion valve. This will not 
affect the operation of the unit.

Use a clean gauge manifold and charging hose that were designed speci

fi

 cally for use 

with R410A. Using the same vacuum equipment for different refrigerants may damage 
the vacuum pump or the unit.

Do not purge the air with refrigerants, but use a vacuum pump to evacuate the system.

•  If moisture might enter the piping, follow below. (i.e., if doing work during the rainy 

season, if the actual work takes long enough that condensation may form on the 
inside of the pipes, if rain might enter the pipes during work, etc.)

•  After operating the vacuum pump for 2 hours, pressurize to 0.05 MPa (i.e., vacuum 

breakdown) with nitrogen gas, then depressurize down to -100.7 kPa (-755 mmHg) for 
an hour using the vacuum pump (vacuum process).

•  If the pressure does not reach -100.7 kPa (-755 mmHg) even after depressurizing for 

at least 2 hours, repeat the vacuum breakdown - vacuum process.

After vacuum process, maintain the vacuum for an hour and make sure the pressure 
does not rise by monitoring with a vacuum gauge.

Evacuation procedure

(1)  Remove the blank caps of the gas pipe and liquid pipe and check that the valves are 

closed.

(2)  Remove the charging port cap.
(3)  Connect a vacuum pump and a pressure gauge to a charging hose and connect it to 

the charging port.

(4) Activate 

the 

vacuum 

pump 

and vacuum the indoor unit and connection piping until the 

pressure gauge becomes -100.7 kPa (-755mm Hg).
Evacuate from both the gas pipe and the liquid pipe.

(5) Continue 

evacuating 

the 

system 

for 

hour 

after the pressure gauge reads -100.7 kPa 

(-755mm Hg).

(6) Remove 

the 

charging 

hose 

and 

reinstall the charging port cap.

8.3. Additional 

charging

CAUTION

Do not turn on the power unless all operations are complete.

After evacuating the system, add refrigerant.

Do not charge the system with a refrigerant other than R410A.

Always keep to the limit on the total amount of refrigerant. Exceeding the limit on the 
total amount of refrigerant will lead to malfunction during charging of refrigerant.

Do not reuse recovered refrigerant.

Use an electronic scale to measure the charging amount of refrigerant. 
Adding more refrigerant than the speci

fi

 ed amount will cause a malfunction.

Charge refrigerant using the liquid pipe.
Adding refrigerant through the gas pipe will cause a malfunction.

Add refrigerant by charging the system with the refrigerant in the liquid state. If the refrig-
erant cylinder is equipped with a siphon, it is not necessary to place the cylinder upright.

Check if the steel cylinder has a siphon installed or not before 

fi

 lling. (There is an indica-

tion “with siphon for 

fi

 lling liquid” on the steel cylinder.)

Filling method 
for cylinder with 
siphon

Liquid

Gas

R410A

Set the cylinder vertical and 

fi

 ll with 

the liquid.
(Liquid can be 

fi

 lled without turning 

bottom up with the siphon inside.)

Filling method 
for other cylin-
ders

Liquid

Gas

R410A

Turn bottom up and 

fi

 ll with liquid.

(Be careful to avoid turning over 
the cylinder.)

Be sure to use the special tools for R410A for pressure resistance and to avoid mixing of 
impure substances.

If the units are further apart than the maximum pipe length, correct operation can not be 
guaranteed.

Make sure to back closing valve after refrigerant charging. Otherwise, the compressor 
may fail.

Minimize refrigerant release to the air. Excessive release is prohibited under the Freon 
Collection and Destruction Law.

8.3.1  Procedure for charging the system with refrigerant

(1) Remove 

the 

charging 

port 

cap from the liquid pipe.

(2)  Attach a charging hose to the refrigerant cylinder, and connect it to the charging port.
(3) Add 

refrigerant 

by 

calculating 

the 

additional refrigerant volume in accordance with the 

calculation formula indicated below.

(4)  Remove the charging hose and install the charging port cap.
(5)  Remove the blank caps (gas pipe and liquid pipe) and open the valves.
(6) Close 

the 

blank 

caps.

(7) After 

adding 

refrigerant, 

indicate 

the added charging volume on the unit.

*  Tighten the blank caps and charging port caps to the torque values speci

fi

 ed in the Table 

A. To open and close the valves, use an M4 hexagon wrench.

8.3.2  

Checking total amount of refrigerant and calculating the 
amount of refrigerant charge to be added

•  The amount of refrigerant charge to be added is the total value of the basic refrigerant 

charge amount and the value calculated from the length of the liquid pipe.

•  Round up the value to 2 decimal places.

Model

“B”

Factory charged 

amount (kg)

Diameter of liquid 

pipe (mm)

“a”

Additional amount 

for pipe length (kg/m)

AJ*040LBLAH

4.80

AJ*045LBLAH

5.30

Ø 6.35

0.021

AJ*054LBLAH

5.30

Ø 9.52

0.058

9380545170_IM.indb   15

9380545170_IM.indb   15

5/19/2016   2:23:17 PM

5/19/2016   2:23:17 PM

Содержание AJH040LBLAH

Страница 1: ... DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli için ...

Страница 2: ...c shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation m...

Страница 3: ...n or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failur...

Страница 4: ...e installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out ...

Страница 5: ...of the unit Otherwise the suction grilles on the sides of the unit may be deformed Front view Rear view Fig B Handle Handle Suction grille Fig A 3 5 Installing the unit Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure ba...

Страница 6: ...n method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 4 SYSTEM CONFIGURATION 4 1 System configuration CAUTION Always keep to the limit on the total amount of refrigerant...

Страница 7: ...ontal line View D View C Horizontal line Vertical line Gas pipe Liquid pipe Outdoor unit side Outdoor unit side H1 0 to 10 mm H2 0 to 10 mm α1 0 to 1 β1 10 to 10 α2 0 to 1 β2 10 to 10 PROHIBITED CAUTION Do not connect a separation tube after a header Leave the distance 0 5 m or more for straight part to branch tube and header Main pipe 0 5 m or more To indoor unit To indoor unit To indoor unit Mai...

Страница 8: ...ve any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked o...

Страница 9: ...breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is installed outdoors place it und...

Страница 10: ...g 2 NOTE Do not use loop wiring This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 F H L G K J E 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enab...

Страница 11: ...rminal Sleeve Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent...

Страница 12: ... This is the output signal for base heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity ...

Страница 13: ...efrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant circuit address 0 99 Setting example 63 0 0 0 1 0 1 2 0 2 REF AD 10 REF AD 1 Rotary Switch REF AD 1 Factory setting 0 Rotary Switch REF AD 10 Factory setting 0 98 9 8 99 9 9 7 4 Push button setting Various functions can be set Set when necessary Perform settings after all indoor units have...

Страница 14: ...s Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Continue to press the SELECT button until the desired number app...

Страница 15: ...e 7 segment display When ERROR is displayed inspect the units Use the MODE EXIT SELECT and ENTER buttons on the outdoor unit PC board to configure settings according to the procedures below 1 Function setting The display when the main power is turned on When F4 to F9 are displayed continue to press the SELECT button until F3 is displayed Press the SELECT button until 11 is displayed Press the ENTE...

Страница 16: ...uation procedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe...

Страница 17: ... has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units Fig A Putty Insulation 9 TEST RUN 9 1 Indoor unit connection check Normal operation will not be possible without performing the Indoor unit connection check 9 1 1 Things to confirm before startin...

Страница 18: ...he EN TER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SE LECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation check the following items 1 Is there a gas leakage At pipe connections flange connections and brazed areas 2 Is the system charged with the specified v...

Страница 19: ...r E 8 3 2 Outdoor unit liquid pipe temp thermistor 2 error E 8 4 1 Outdoor unit current sensor 1 error permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 ...