background image

19 

User manual – Controller CP Touch 

Table of notifications (blue triangle)

   

Set orientation 
(only applies to DUPLEX 
Flexi and DUPLEX 
ECH/ECVH)

 

The unit’s orientation is not 
set, i.e. it is not determined 
which fan is the supply fan 
and which is the extraction 
fan.  

This parameter blocks the 
operation of the unit and must be 
set in the service menu.  Contact a 
service technician. 

Heater setting 

The heater type is not set 
(water or electrical). 

This parameter blocks the 
operation of the unit and must be 
set in the service menu.  Contact a 
service technician. 

Manometer failure 

If the unit is fitted with air 
flow rate gauges, one of them 
does not measure correctly or 
is faulty.    

Contact a service technician. 

Unbalanced flow rate 

The flow rate through the unit 
is out of balance, the fans do 
not work as per settings.  

Contact a service technician. 

AHU overheat 

One of the temperature 
sensors has detected a 
temperature higher than 77°C. 

Disconnect the unit from power 
supply and, if there is no risk of 
overheating in the room (fire etc.), 
reconnect it.  

Communication error 

Breakdown of communication 
between the controller and 
AHU. 

Check whether the cable between 
the unit and controller is not 
interrupted or contact a service 
technician. 

Clogged filter 

The filters in the unit are clogged, 
they are not working properly.  

The filters in the unit must be 
replaced.  

Heat recovery 
exchanger defrosting 

Frost deposits in the heat recovery 
exchanger; the unit is not recovering 
the heat but defrosting. 

The air extracted from the 
building is likely to be very 
humid and the outside 
temperature is low. This 
condition usually lasts for 
several minutes and the unit 
goes back to normal 
operation after the heat 
recovery exchanger has been 
defrosted. 

Insufficient heating 
capacity of Heater 1 

The heating capacity of the unit’s 
heater is not sufficient. 

Check the status of primary 
heating. The unit has 
switched to heating from its 
back-up source. 

High tariff 

The unit does not start the electric 
heater due to high electricity prices. 

Power supply in a high tariff. 
Electrical heating is blocked.  

Table 6 

Содержание CP Touch

Страница 1: ...DATUM N ZEV SPOLE NOSTI Adresa spole nosti USER MANUAL CONTROLLER CP Touch Version 03 EN Issue 06 11 2018 Code M_19_V03_EN_2018_11...

Страница 2: ...tween HS NHS 11 6 1 3 HS NHS temperature 11 6 1 4 Current season 11 6 2 Control settings 11 6 2 1 Blocking input IN1 No HS NHS 11 6 2 2 Blocking input IN2 No HS NHS 12 6 2 3 Heating hysteresis 12 6 2...

Страница 3: ...roller 6 8 Note The CP Touch controller s commissioning and connection to a DUPLEX units may only be done by a specialist company with up to date training certification for DUPLEX units with RD5 contr...

Страница 4: ...n follow the wiring diagram located in the lid of the AHU s cabinet If there more controllers connected they must be in a series as shown in Fig 1 Note According to the diagram up to four controllers...

Страница 5: ...roller in the series must be terminated with a T CAN jumper Number of controllers connected A1 A2 T CAN 1 0 0 1 0 0 0 2 0 1 0 0 0 2 0 0 3 0 1 0 0 0 2 0 0 3 0 0 4 Table 1 0 Unconnected jumper Connected...

Страница 6: ...iting for communication with the control board if this takes more than 3 minutes the screen switches to Communication Error Main screen appears but data are 0 The controller s application has loaded p...

Страница 7: ...program Temporary manual change of the weekly program Group 3 Party Holiday mode active Bank holiday mode active Group 4 Symbol indicates heating Symbol indicates cooling Group 5 Active alarm symbol y...

Страница 8: ...s icon Service settings accessible after entering a password any data in the service settings may be edited only by an authorized service technician Table 5 5 Blocks on the main screen 5 1 Power block...

Страница 9: ...en input status changes Dn INk Ventilation The unit is ventilating at a power level set or higher as set by an external input which is active Night pre cooling The unit is in OFF mode If starts ventil...

Страница 10: ...gram If that is the case the zone requirement is generated by a closed input D1 D4 and parameters set for one of these inputs Note Zone texts can be set for more information see 6 6 The initial zone d...

Страница 11: ...than Temperature HS NHS the Non heating season is selected automatically If outside temperature is lower than Temperature HS NHS and at the same time room temperature is higher than the required tempe...

Страница 12: ...ture difference compared to the temperature required to start heating The setting range is between 0 1 C and 5 C 0 1 C steps 6 2 4 Cooling hysteresis To set a temperature difference compared to the te...

Страница 13: ...ding to the weekly program and should be switched temporarily to economy mode for example for a week when there is no occupancy in the house When the parameters set for the Holiday Party function have...

Страница 14: ...is activated and deactivated according to the start and end times set After pressing this button changes to the Deactivate button 6 4 Weekly program setting The weekly program is set separately for th...

Страница 15: ...and to move between all eight intervals days The weekly program allows copying and pasting the settings of a given day as follows Into each day of the week Into selected days Into Bank holidays Schoo...

Страница 16: ...t the basic parameters of the display Backlight setting The display backlight is changed using the setting arrows see Fig 16 Internet time sync Time sync with the internet is done by checking this opt...

Страница 17: ...summer and standard time 6 8 SW information unit type configuration specifications version Information on the type of the unit its manufacturing number and the version of the control software 7 Filte...

Страница 18: ...dition usually lasts for several minutes and the unit goes back to normal operation after the heat recovery exchanger has been defrosted Temperature sensor downstream TA2 external heater Communication...

Страница 19: ...unit from power supply and if there is no risk of overheating in the room fire etc reconnect it Communication error Breakdown of communication between the controller and AHU Check whether the cable b...

Страница 20: ...ss damper is primarily controlled by setting the required temperature Tp and cannot be controlled manually 9 3 Circulation damper The circulation damper also known as the mixing damper is used for mix...

Отзывы: