Manual test mode
This corresponds to
automatic test mode,
with the exception
that the test pressu-
re must be adjusted
manually by chan-
ging the fan speed
to the entered target
value.
The program prompts
for the same data as
for automatic test
mode.
When the Start but-
ton is pressed the
data are transferred
to the tester and the
test begins with minimum compressor (fan) speed.
The manual test can be ended prematurely by pres-
sing the Stop button.
Press the sTOP (F3)
button on the tester
to interrupt the test
process at any time.
After starting the test process the current pressure in
Pa, the volume flow in l/s (with two decimal places),
the test duration and the compressor (fan) speed are
displayed continuously.
The compressor (fan) speed control buttons can be
used to adjust the speed between 0 (speed = 0) and
4095 (maximum speed).
Whenever the test pressure is within the tolerance
window the measured values are recorded and the
test duration decreases.
After the test time has expired the following data is
displayed:
•
average test pressure [Pa]
•
average volume flow, i.e. leakage volume [l/s and
m
3
/h]
•
maximum permitted volume flow (leakage volume)
according to class and surface [l/s and
m
3
/h]
•
Test passed (ok) or failed (not ok)
The “Test” button is
pressed wot switch
back to input and the
“Start” page button
is pressed to switch
back to the Main
menu.
If “Save record” is
pressed the data is
saved as a PDF file in
the mobile terminal
device. This record
can then be sent by
email or can also be
deleted manually.