3.3 

Dimensions  

 

CHAPTER 4 
 

FUNCTION

 

 
 

4.0 

 
 
 
 
 

Function description  
    

All of the following information and instructions are intended for use by authorized 

electricians.  All  times  may  vary  slightly  due  to  component  tolerances  and  ambient 
temperatures.   
 
QuietAir QT150 VS can be continuously  operated by  e.g. connecting an external 3-
Amp Stepless Speed Controller (accessory) or 0-10 V set point generator. 

 
1. Speed setting  

The  adjustment  of  the  speed  can  be  limited  internally  via  internal  potentiometer 
settings. In delivery condition, the full scope of the control range becomes available.

  

 
2. Scaling 

Scaling  can  be  set  through  the  internal  potentiometer,  i.e.  it  will  set the  assignment 
set point input (0-10 V) for speed control (20-100%).  
No  change  must  in  principle  be  carried  out  in  default  activation  with  an  external 
potentiometer. Change can be made e.g.  when connecting a sensor sense, when a 
smaller control range is to be used.     

 
3. Relay output  

When  the  fan  is  running  regardless  of  the  speed  an  operational  message  is 
displayed.  The relay output is, for example, for connecting an external flap. 

 

  

 
 

 

Содержание QT 150VS

Страница 1: ...nd Operating Instructions QuietAir 150mm Axial Fan MODEL QT 150VS Variable Speed Fan 50 260m3 hr With Adjustable Timer control Variable Speed with timer Low Energy Quiet Long Life Extra Safe 80000309...

Страница 2: ...ance Chapter 3 SPECIFICATIONS DIMENSIONS M1 150 0 10V 3 0 Specifications 3 1 Product lifetime 3 2 Accessories 3 3 Dimensions Chapter 4 FUNCTION 4 0 Function description Chapter 5 CLEANING DEINSTALLATI...

Страница 3: ...and accident prevention regulations must be observed All electrical work and commissioning must be carried out only by authorized and qualified electricians Maintenance and installation work must be c...

Страница 4: ...rly installed and used for its intended purpose product complies with the valid regulations and CE guidelines at the time of its production 1 5 Transport The fan is factory packed so that it is protec...

Страница 5: ...ectrical data this must be conformed to the local supply network On the test stand fan performance was complied with DIN EN ISO 5801 1 10 Noise data The noise data which relate to distances is valid u...

Страница 6: ...on inhibit activates the fan for 15 sec to protect the motor from rapid on off switching CHAPTER 3 SPECIFICATIONS DIMENSIONS M1 150 0 10 V 3 0 Specifications Impeller 137 Electrical supply NYM 0 2 x1...

Страница 7: ...be limited internally via internal potentiometer settings In delivery condition the full scope of the control range becomes available 2 Scaling Scaling can be set through the internal potentiometer i...

Страница 8: ...sible housing parts the external housing of the fan with a damp cloth Do not use any aggressive paint solvent cleaning agents High pressure cleaner or spray water is not permitted 5 1 Cover Dismantlin...

Страница 9: ...ter unpacking and before installation the following points must be checked if any transport damage is noticed broken or bent parts free running of the impeller 6 2 Installation The QuietAir 150 is des...

Страница 10: ...and wall plugs 3 Backdraft shutter and guide vane If required backdraft shutter scope of delivery can be installed behind the guide vane fig 6 During the housing installation the guide vane must be mo...

Страница 11: ...must take place in one wire Insertion of 2 wires in the grommet is not allowed In the wiring make sure that wires are placed not on the board but on the edge along the housing fig 9 10 For LiYY contr...

Страница 12: ...with supply cable through NYM O 4 1 5mm 2 Relays with low voltage consumers Connection combined with control line through LiYY 5 0 34mm 2 Wire transfer not over the board 1 Insert and tighten the ter...

Страница 13: ...an the following need to be checked regularly Appearance of dust or dirt in the housing on the motor and impeller Free running of the impeller Appearance of excessive vibration and noise In case of pr...

Страница 14: ...rminal N L Terminal N and L have to be connected to the 230V operating voltage Terminal 5 Terminal 1 activates the low stage Terminal 6 Terminal 2 activates the high stage Terminal 7 10 VDC Terminal 3...

Страница 15: ...rocessing work wherein the setpoint of 10 V the controller will reach the maximum value of 100 Thus in the delivery state complete bandwidth set is available for both setpoint input and speed control...

Страница 16: ...peed Note Minimum air operation and minimum rate of air can be achieved by electronic temperature sensors such as the ETR Type see accessories 4 Relay output An operating message will be displayed on...

Страница 17: ...5 Schematic overview for QuietAir QT150 VS Fig 17...

Страница 18: ...failure in Chapter 8 1 Bearing noise Vibrations see Chapter 8 1 Power consumption according to the specifications on the type plate see Chapter 8 1 8 1 Troubleshooting Safety instructions listed in C...

Страница 19: ...ion mechanical loading fatigue and or other effects that could not be directly discerned should be disposed in accordance with local and international laws and regulations The same applies to auxiliar...

Страница 20: ...le electrical supply 3 Has not been subjected to issue neglect or damage 4 Has not been modified or repaired by any person not authorised by Airflow Developments Ltd 5 Has been installed in accordance...

Отзывы: