Te
ch
ni
ca
l
Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
58
Chiller Technical Manual 7752785 V1.12.0_10_2018
A
ir C
oo
led
Mechanical Data
Notes Units
TCC11X04G-01
TCC11X06G-01
TCC11X08G-01
Cooling Duty - EC Fans
(1)
kW
200
225
250
Nom Input -Cooling Only
kW
56.9
56.6
60.0
EER
(2)
3.51
3.98
4.16
ESEER
(3)
4.53
5.41
5.57
Nominal Output - Free Cooling
(4)
kW
N/A
N/A
N/A
Ambient when Free Cooling
= 100% Nominal DX
(5)
°C
N/A
N/A
N/A
Capacity Steps
(6)
%
30-100%
30-100%
30-100%
Dimensions (H x W x L)
(9) mm 2800 x 2200 x 2626
2800 x 2200 x 3758
2800 x 2200 x 4890
Machine Weight
(7)
kg
2745
3300
3785
Operating Weight
(7)
kg
2845
3400
3885
Construction Material
Base: Plain Galvanised Steel, Panels: Galvanised Sheet
Steel, Epoxy Baked Powder Paint, Light Grey (RAL 7035)
Evaporator - Type
Flooded - Shell and Tube Evaporator
Insulation
Class O, UV stable Insulation
Total Max. Water Flow
l/s
21.9
21.9
21.9
Total Min. Water Flow
l/s
7.3
7.3
7.3
Condenser - Type
Epoxy Coated Aluminium Microchannel & Aluminium Fins
Face Area Total
m²
9.5
14.21
18.9
Maximum Airflow - EC Fans
m³/s
17.7
26.5
35.3
Condenser Fan & Motor
Sickle Bladed Axial Fan
Quantity
4
6
8
Diameter
mm
800
800
800
Maximum Speed - EC Fans
rpm
730
730
730
Compressor - Type
Turbocor - Oil Free Compressor
Quantity
1
1
1
Capacity Control
Variable Frequency Drive (VFD) for Linear Capacity Modulation
Refrigeration
Single Circuit
Refrigerant Pre-charged
R1234ze(E)
R1234ze(E)
R1234ze(E)
Charge (Total) CCT1 + CCT2
kg
110
115
125
GWP Tonnes Equivalent CO
2
tC02
0.77
0.81
0.88
Refrigeration Control
Electronic Expansion Valve (EEV)
Water System
Grooved Type Coupling and Pipe Assembly
Water Inlet / Outlet
DN100
DN100
DN100
Water Drain / Bleed - Evap
inch
1/2
1/2
1/2
Water Volume
l
102
102
102
Minimum System Water Volume
(8)
l
953
1059
1166
Max System Operating Pressure
Barg
10
10
10
Flow Rate
l/s
7.9
8.9
9.9
Pressure Drop
kPa
19.3
23.4
27.9
Technical Data TCC (X)
Mechanical Data
TCC11X04G-01, TCC11X06G-01, TCC11X08G-01
(1) Based on AC units performance at 13/7°C return/supply temperatures, 35°C ambient, 100% water.All performance data is supplied in accordance with BS EN 14511-1:2013
(2) EER = DX cooling output / (compressor input power + fan input power)
(3) ESEER based upon unit operating at 12 / 7 °C return / supply temperature, 35°C ambient.
(4) Nominal Free Cooling output at 16/10°C return/supply temperatures, 2°C ambient, 20% ethylene glycol.
(5) Ambient temperature that maximum nominal DX duty can be achieved using Free Cooling only.
(6) This is a nominal figure based on full compressor duty, actual turndown depends on both condensing and evaporating temperatures.
(7) Based on standard unit without options, machine weight includes refrigerant charge, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please contact Airedale.
(8) For minimum system water volume calculation, refer to Design Features & Information - Minimum System Water Volume Calculations.
(9) Height based on standard fan, for optional fan dimensions please contact Airedale