![AIREDALE TurboChill TCC11R04G-01 Скачать руководство пользователя страница 163](http://html.mh-extra.com/html/airedale/turbochill-tcc11r04g-01/turbochill-tcc11r04g-01_technical-manual_2876557163.webp)
Notes:
TCC11R04G-01
TCC11R06G-01
TCC11R08G-01
SEPR
1,3,5
7.4
8.1
8.6
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
239842.0
242104.7
236773.9
Rated Refrigerant Capacity P
A
1,3,5 kW
239.2
264.0
273.9
Rated Power Input D
A
kW
70.1
72.1
70.7
Rated EER
DC,A
3.41
3.66
3.87
Declared Refrigerant Capacity P
B
1,3,5 kW
223.2
246.3
255.6
Declared Power Input D
B
kW
46.8
47.3
46.4
Declared EER
DC,B
4.77
5.21
5.51
Declared Refrigerant Capacity P
C
1,3,5 kW
207.2
228.7
237.3
Declared Power Input D
C
kW
30.5
30.8
30.3
Declared EER
DC,C
6.80
7.42
7.82
Declared Refrigerant Capacity P
D
1,3,5 kW
191.2
211.0
218.9
Declared Power Input D
D
kW
19.2
19.3
18.7
Declared EER
DC,D
9.94
10.91
11.69
SSCEE
2,3,5
%
204.2
219.2
229.6
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2,4,5 kW
240.0
265.0
275.0
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
239.2
264.0
273.9
Declared EER
d
35°C
3.41
3.66
3.87
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
176.0
194.3
201.6
Declared EER
d
30°C
4.34
4.76
5.03
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
113.2
124.5
129.2
Declared EER
d
25°C
5.72
6.06
6.38
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
97.7
94.6
92.8
Declared EER
d
20°C
6.78
7.32
7.58
Sound Power Level
dB(A)
88
87
87
Air Volume
m³/h
82650
123975
165301
Off mode P
OFF
kW
0.249
0.249
0.249
Thermostat-off mode P
TO
kW
0.832
0.989
1.076
Standby Mode P
SB
kW
0.330
0.340
0.350
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data - TCC R
Ecodesign
TCC11R04G-01, TCC11R06G-01, TCC11R08G-01
Introduction
Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
163
Chiller Technical Manual 7752785 V1.12.0_10_2018
Te
ch
nic
al
Introduction
Te
ch
nic
al
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.